Optional Contents:Connector, Cable Support Bracket.
DANGER
All apparatus must be de--energized during installation
or removal of part(s).
All apparatus must be installed and operated in
accordance with individual user,local, and national work
rules. These instructions do not attempt to provide for
every possible contingency.
Do not touch or move energized products.
Excess distortion of the assembled product may result in
its failure.
Inspect parts for damage, rating and compatibility with
mating parts.
FOR MORE INFORMATION ON PARTS, INSTALLATION RATINGS AND COMPATIBILITY, CALL THE NEAREST ELASTIMOLD OFFICE.
This product should be installed only by competent
personnel trained in good safety practices involving
high voltage electrical equipment. These instructions
are not intended as a substitute for adequate training or
experience in such safety practices.
Failure to follow these instructions will result in damage
to the product and serious or fatal injury.
If this product is supplied with a protective shipping
cover(s), remove this shipping cover(s) and replace with
the appropriate HV insulated cap(s) or connector(s)
before submerging or energizing the circuit.
WARRANTY: Thomas & Betts warrants that this product will be free from defects in materials and workmanship for the period of two (2) years from the
date of shipment.Upon prompt notification of any warranted defect,Thomas & Betts will, at its option, repair, replace orrefund thepurchase price.Proof
of purchase is required. Unauthorized modification or improper installation will void all warranties.
Limitations and Exclusions: THE ABOVE WARRANTY IS THE SOLE WARRANTY CONCERNING THIS PRODUCT, AND IS IN LIEU OF ALL
OTHER WARRANTIES EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MARCHATABILITY OR
FITNESS FOR A PARTICULARPURPOSE, WHICH ARE SPECIFICALLY DISCLAIMED. LIABILITYFOR BREACHOF THEABOVE WARRANTYIS
LIMITED TO COST OF REPAIR OR REPLACEMENT OF THE PRODUCT, AND UNDER NO CIRCUMSTANCES WILL THOMAS & BETTS BE
LIABLE FOR ANY INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
IMPORTANT
1. Check contents of package to ensure they are complete
and undamaged.
2. Check all components to ensure proper fit with cable
and/or mating products.
Termination Selection Chart
Catalog
Number
R2T15M1 0.64--1.12 (15--30)1.35 (35) MAX
R2T15M2 0.84--1.38 (20--35)1.72 (45) MAX
R2T15M4 1.30--2.10 (35--55)2.55 (65) MAX
R2T28M2 0.84--1.38 (20--35)1.72 (45) MAX
R2T28M4 1.30--2.10 (35--55)2.55 (65) MAX
Dia. Over Insulation
Inches (mm)
Tape Shield -- Page 2
Wire Shield -- Page 5
UniShield-- Page 8
Dia. Over Jacket
Inches (mm)
Typical 15kV Cables
(100% level, 175mil)
#1--250 Kcmil*
* Confirm Cable Insulation Diameter is with the Ranged Listed
4/0--500 Kcmil*
750--1250 Kcmil*
3. Read entire installation instructions before starting.
4. Have all required tools at hand and maintain cleanliness
throughout the procedure.
1. Check to be sure cable size fits within kit range as shown in the Termination Selection Chart, Page 1.
2. Train cable into position and cut to length required for installation.
3. Prepare cable using dimensions shown. Be sure to allow for depth of terminal lug. To prevent tape shield from unrolling,
hold down edge with a single wrap of the supplied copper foil tape as shown. Provide additional exposed conductor
distance to account for growth during crimping of ALUMINUM lugs or connectors as follows:
Aluminum Lug
Growth Allowance
2”(50mm)
1”(25mm)
Cable Jacket
2/0--350
1/4”(6mm)
400--650
1/2”(13mm)
Jacket Removal Length
See “A” in Table 1
Semi--Con
750--1000
3/4”(19mm)
Insulation
Depth of
Terminal Lug
Plus Growth
Allowance
Tape Shield
Copper Foil Tape
STEP 2 Install Ground Braid
1. Using 50% stretch, carefully wrap one (1) band of mastic around the cable jacket 1/4”(6mm) from jacket end as shown.
Position mastic carefully, it also serves as a marker for positioning the terminator. Cut mastic flush, do not overlap.
2. Position preformed ground braid with short tail over tape shield and solder block centered over mastic strip. Secure ground
braid to cable jacket using vinyl tape. Press solder block into mastic. See figure below.
Cable Jacket
Vinyl Tape
Ground Braid
3. Using 50% stretch apply a second mastic band over the solder block and previously applied mastic maintaining the 1/4” (6mm)
dimension. Cut flush, do not overlap.
4. Wrap two half--lapped layers of vinyl tape around mastic seal,carefully maintaining the 1/4” (6mm) dimension.
5. Wrap ground braid around cable tape shield one complete wrap, trim excess to prevent overlap and secure in place with
constant force spring. Wrap spring in same direction as ground braid. Cinch (tighten) the spring after wrapping the final
winding. Secure spring with two (2) wraps of vinyl tape.
SPECIAL NOTE FOR CLOTH OR PAPER SEMI--CON INSULATION SHIELD
In cable with cloth or paper semi--conductive shields it is recommended the shield be over wrapped
with one half--lapped layer of highly stretched semi--conductive rubber tape such as Scotcht No. 13.
2nd Mastic Seal
2--1/2”(64mm)
1/4” (6mm)
Solder Block
Semi--Con
Semi--Con
Tape Shield
Mastic Seal
Constant Force Spring
Trim
Ground Braid
1/4” (6mm)
Vinyl Tape over Mastic
1” Min. Exposed
Semi--Con
Vinyl Tape over Constant Force Spring
Cable Tape Shield
Page 3
IS--1138
February 2011
Page 3 of 10
STEP 3 Install Lug or Connector
1. Check to insure termination assembly fits over the selected lug. If lug will not fit through the termination core, clean the
insulation and slide termination on cable before installing lug. Do not remove core at this time.
2. Position connector/lug and crimp according to manufacturer’s directions. Do not crimp the last 3/8” to 1/2” of the connector.
Remove excess oxide inhibitor and sharp crimp flashings following crimping.
3/8” to 1/2” Uncrimped Length
STEP 4 Clean Cable Insulation and Lug Barrel Using Standard Practice
1. Wipe the cable insulation with an approved solvent. Do not allow solvent to touch semi--con insulation shield.
2. If abrasive must be used:
a. Use on insulation only. Do not use abrasive on semi--con insulation shield.
b. Use only aluminum oxide abrasive; grit 120 or finer.
c. Be careful not to reduce the cable insulation diameter below that allowed by the kit.
STEP 5 Install Termination
1. IMPORTANT: A track resistant moisture seal must be made between termination insulator and lug/connector using gray
silicone rubber electrical tape (contained in kit). Wrap a band of silicone tape around the base of the terminal lug.
a. If barrel diameter is equal to or greater than cable primary insulation, the tape band should not exceed 2 layers.
b. If barrel diameter is smaller than the cable primary insulation, use tape strip to form the tape band equal to
insulation diameter, see below..
2. Cover the edge of the semi--con insulation shield with a liberal coating of silicone grease. On this product the silicone
grease does not serve as a lubricant. It must be used to fill the step at the semi--con cut off.
Silicone Lubricant
Coils
3. On lowertermination with folddown skirt pullloose end of removable core through top of terminationuntil the core is flush with
bottom of the termination.
Removable core flush with bottom of the termination
4. Slide the termination body onto the cable, align terminator with forward edge of mastic seal as shown below. Carefully
begin to remove core while unwinding, counter--clockwise, starting with looseend. Make sure the terminator body, not the
core is butted up to the leading edge of the mastic seal, see below. Continue to remove core. Do not push or pull on
the termination assembly while removing core.
Mastic Seal
Silicone Tape
Pull Counter--clockwise
Align Terminator
with Leading Edge
of Mastic Seal
Mastic Seal Under
Vinyl Tape
Page 4
IS--1138
February 2011
Page 4 of 10
5. Apply a thin film of silicone lubricant to the skirt and mastic seal area. Do not lubricate the skirt tabs. Carefully fold down skirt
over mastic seal.
Apply Silicone Lubricant
Skirt Tab
6. With termination installed, complete the lug area moisture seal using the remaining gray silicone rubber electrical tape.
Overlap the termination insulator by approximately 1” and extend the tape wrapping over a non--crimped region of the lug/
connector barrel with half lap configuration. See above.
7. Connect ground braid to system ground.
High--K Step should overlap Cable Semi--Con
Silicone Rubber Tape
Not to Exceed 1.5”
8. Confirm that High--K step does not exceed 1.5”.
Page 5
IS--1138
February 2011
Page 5 of 10
Wire Shielded Cable
STEP 1 Prepare Cable
1. Check to be sure cable size fits within kit range as shown in the Termination Selection Chart, Page 1.
2. Train cable into position and cut to length required for installation.
3. Prepare cable using dimensions shown. Be sure to allow for depth of terminal lug. Provide additional exposed
conductor distance to account for growth during crimping of ALUMINUM lugs or connectors as follows:
Aluminum Lug
Growth Allowance
4. Bend leading 1--1/2” (38mm) of exposed shield wires back upon themselves to jacket edge.
Shield Wires
2”(50mm)
Cable Jacket
2--350
1/4”(6mm)
Jacket Removal Length
Semi--Con
400--650
1/2”(13mm)
750--1000
3/4”(19mm)
See “A” in Table 1
Insulation
Depth of
Terminal Lug
Plus Growth
Allowance
1”(25mm)
2”(50mm)
Cable Jacket
Insulation
Shield Wires
STEP 2 Install Ground Braid
1. Using 50% stretch, carefully wrap one (1) band of mastic around the cable jacket 1/4”(6mm) from jacket end as shown.
Position mastic carefully, it also serves as a marker for positioning the terminator. Cut mastic flush, do not overlap.
2. Position preformed ground braid with short tail over tape shield and solder block centered over mastic strip. Secure ground
braid to cable jacket using vinyl tape. Press solder block into mastic. See figure below.
Cable Jacket
Marker Tape
Ground BraidSolder Block
3. Using 50% stretch apply a second mastic band over the solder block and previously applied mastic maintaining the 1/4” (6mm)
dimension. Cut flush, do not overlap.
4. Wrap two half--lapped layers of vinyl tape around mastic seal,carefully maintaining the 1/4” (6mm) dimension.
5. Wrap ground braid around cable tape shield one complete wrap, trim excess to prevent overlap and secure in place with
constant force spring. Wrap spring in same direction as ground braid. Cinch (tighten) the spring after wrapping the final
winding. Secure spring with two (2) wraps of vinyl tape.
2--1/2”(64mm)
1/4” (6mm)
Semi--Con
Shield Wires
Mastic Seal
2nd Mastic Seal
Vinyl Tape
Constant Force Spring
Semi--Con
1” Min. Exposed
Semi--Con
Cable Tape Shield
Vinyl Tape over Constant Force Spring
Trim
Ground Braid
Page 6
IS--1138
February 2011
Page 6 of 10
STEP 3 Install Lug or Connector
1. Check to insure termination assembly fits over the selected lug. If lug will not fit through the termination core, clean the
insulation and slide termination on cable before installing lug. Do not remove core at this time.
2. Position connector/lug and crimp according to manufacturer’s directions. Do not crimp the last 3/8” to 1/2” of the connector.
Remove excess oxide inhibitor and sharp crimp flashings following crimping.
3/8” to 1/2” Uncrimped Length
STEP 4 Clean Cable Insulation and Lug Barrel Using Standard Practice
1. Wipe the cable insulation with solvent saturated pads. Do not allow solvent to touch semi--con insulation shield.
2. If abrasive must be used:
a. Use on insulation only. Do not use abrasive on semi--con insulation shield.
b. Use only aluminum oxide abrasive; grit 120 or finer.
c. Be careful not to reduce the cable insulation diameter below that allowed by the kit.
STEP 5 Install Termination
1. IMPORTANT: A track resistant moisture seal must be made between termination insulator and lug/connector using gray
silicone rubber electrical tape (contained in kit). Wrap a band of silicone tape around the base of the terminal lug.
a. If barrel diameter is equal to or greater than cable primary insulation, the tape band should not exceed 2 layers.
b. If barrel diameter is smaller than the cable primary insulation, use tape strip to form the tape band equal to
insulation diameter, see below..
2. Cover the edge of the semi--con insulation shield with a liberal coating of silicone grease. On this product the
silicone grease does not serve as a lubricant. It must be used to fill the step at the semi--con cut off.
Silicone LubricantSilicone Tape
Coils
3. On lowertermination with folddown skirt pullloose end of removable core through top of terminationuntil the core is flush with
bottom of the termination.
Removable core flush with bottom of the termination
4. Slide the terminationbody onto the cable, alignterminator with forwardedge of mastic seal as shown below. Carefully begin to
remove core while unwinding, counter--clockwise, starting with loose end. Make sure the terminator body, not the core is
butted up to the leading edge of the mastic seal, see below. Continue to remove core. Do not push or pull on the
termination assembly while removing core.
Mastic Seal
Pull Counter--clockwise
Align Terminator
with Leading Edge
of Mastic Seal
Mastic Seal Under
Vinyl Tape
Page 7
IS--1138
February 2011
Page 7 of 10
5. Apply a thin film of silicone lubricant to the skirt and mastic seal area. Do not lubricate the skirt tabs. Carefully fold down skirt
over mastic seal.
Apply Silicone Lubricant
Skirt Tab
6. With termination installed, complete the lug area moisture seal using the remaining gray silicone rubber electrical tape.
Overlap the termination insulator by approximately 1” and extend the tape wrapping over a non--crimped region of the lug/
connector barrel with half lap configuration. See above.
7. Connect ground braid to system ground.
High--K Step should overlap Cable Semi--Con
Silicone Rubber Tape
Not to Exceed 1.5”
8. Confirm that High--K step does not exceed 1.5”.
Page 8
IS--1138
February 2011
Page 8 of 10
UniShieldShield Cable
STEP 1 Prepare Cable
1. Check to be sure cable size fits within kit range as shown in the Termination Selection Chart, Page 1.
2. Train cable into position and cut to length required for installation.
3. Prepare cable using dimensions shown. Be sure to allow for depth of terminal lug. Provide additional exposed
conductor distance to account for growth during crimping of ALUMINUM lugs or connectors as follows:
Aluminum Lug
Growth Allowance
4. Install constant force spring and pull shield wires through semi--conductive jacket to leading edge of spring.
5. Remove constant force spring. Bend shield wires back upon cable jacket 1”(25mm). Cut excess shield wire and discard.
“A” -- 1” See Table 1
2--350
1/4”(6mm)
400--650
1/2”(13mm)
750--1000
3/4”(19mm)
Depth of Terminal
Lug Plus Growth
Allowance
Fold Back
Shield Wires
6. Remove semi--conductive jacket to dimension shown below.
Toease jacket removal, installconstant force spring asshown and ring cut 80%through jacket. Remove jacket sections
by pulling against constant force spring. DO NOT BELL SEMI--CON JACKET. Remove constant force spring.
Some UniShieldcables feature dual--layer semi--conductive jackets. Both layers must be removed during cable preparation.
1”(25mm)
Fold Back Shield Wires
Shield Wires
See “A” in Table 1
1”(25mm)
1”(25mm)
Cut Line
Constant Force Spring
Semi--Conductive Jacket
Depth of Terminal
Lug Plus Growth
Allowance
STEP 2 Install Ground Braid
1. Using 50% stretch, carefully wrap one (1) band of mastic around the cable jacket 1/4”(6mm) from shield wire end as shown.
Position mastic carefully, it also serves as a marker for positioning the terminator. Cut mastic flush, do not overlap.
2. Position preformed ground braid with short tail over tape shield and solder block centered over mastic strip. Secure ground
braid to cable jacket 4--1/2” (114mm)from cablesemi--conedgeusing vinyl tape. Presssolder blockintomastic. See figure below.
2--1/2”(64mm)
Cable Jacket
1/4” (6mm)
Vinyl Tape
Ground Braid
3. Using 50% stretch apply a second mastic band over the solder block and previously applied mastic. Cut flush, do not overlap.
4. Wrap two half--lapped layers of vinyl tape around mastic seal, carefully maintaining the 1/4” (6mm) dimension.
5. Wrap ground braid around cable shield wires one complete wrap, trim excess to prevent overlap and secure in place with
constant force spring. Wrap spring in same direction as ground braid. Cinch (tighten) the spring after wrapping the final winding.
2nd Mastic Seal
Vinyl Tape over Mastic
Solder Block
Constant Force Spring
Semi--Con
Vinyl Tape over Constant Force Spring
Shield Wires
Mastic Seal
Semi--Con
Trim
Ground Braid
Cable Wire Shield
Page 9
IS--1138
February 2011
Page 9 of 10
STEP 3 Install Lug or Connector
1. Check to insure termination assembly fits over the selected lug. If lug will not fit through the termination core, clean the
insulation and slide termination on cable before installing lug. Do not remove core at this time.
2. Position connector/lug and crimp according to manufacturer’s directions. Remove excess oxide inhibitor and sharp crimp
flashings following crimping.
STEP 4 Clean Cable Insulation and Lug Barrel Using Standard Practice
1. Wipe the cable insulation with solvent saturated pads. Do not allow solvent to touch semi--con insulation shield.
2. If abrasive must be used:
a. Use on insulation only. Do not use abrasive on semi--con insulation shield.
b. Use only aluminum oxide abrasive; grit 120 or finer.
c. Be careful not to reduce the cable insulation diameter below that allowed by the kit.
STEP 5 Install Termination
1. IMPORTANT: A track resistant moisture seal must be made between termination insulator and lug/connector using gray
silicone rubber electrical tape (contained in kit). Wrap a band of silicone tape around the base of the terminal lug.
a. If barrel diameter is equal to or greater than cable primary insulation, the tape band should not exceed 2 layers.
b. If barrel diameter is smaller than the cable primary insulation, use tape strip to form the tape band equal to
insulation diameter, see below.
2. Cover the edge of the semi--con insulation shield with a liberal coating of silicone grease. On this product the silicone grease
does not serve as a lubricant. It must be used to fill the step at the semi--con cut off.
Silicone Lubricant
Coils
3. On lowertermination with folddown skirt pullloose end of removable core through top of terminationuntil the core is flush with
bottom of the termination.
Removable core flush with bottom of the termination
4. Slide the termination body onto the cable, align terminator with forward edge of mastic seal as shown below. Carefully
begin to remove core while unwinding, counter--clockwise, starting with looseend. Make sure the terminator body, not the
core is butted up to the leading edge of the mastic seal, see below. Continue to remove core. Do not push or pull on
the termination assembly while removing core.
Pull Counter--clockwise
Align Terminator
with Leading Edge
of Mastic Seal
Mastic Seal Under
Vinyl Tape
Page 10
IS--1138
February 2011
Page 10 of 10
5. Apply a thin film of silicone lubricant to the skirt and mastic seal area. Do not lubricate the skirt tabs. Carefully fold down skirt
over mastic seal.
Apply Silicone Lubricant
Skirt Tab
Fold Down Skirt
6. With termination installed, complete the lug area moisture seal using the remaining gray silicone rubber electrical tape.
Overlap the termination insulator by approximately 1” and extend the tape wrapping over a non--crimped region of the lug/
connector barrel with a half lap configuration, see above.
7. Connect ground braid to system ground.
High--K Step should overlap Cable Semi--Con
Silicone Rubber Tape
Not to Exceed 1.5”
8. Confirm that High--K step does not exceed 1.5”.