GENERAL INFORMATION:
The Pin Adapter is designed to provide reliable termination of stranded aluminum conductors with insulation rated not more than 90° C (194° F) in mechanical connectors listed for Al-Cu use and connectors suitable for stranded copper conductor installed in accordance with the National Electrical Code. Reliability is obtained by terminating the aluminum conductor in one end of a compression aluminum sleeve, the other end of which has a factory installed copper pig-tail. The copper end is then installed in the mechanical connector.
The following installation instructions are provided as a means of assuring the electrical equipment and its mechanical connectors, into which Pin Adapter is to be installed, are physically compatible with the dimensions of the Pin Adapter. They should be read carefully before installing the Pin Adapter in electrical equipment.
INSTALLATION A:
Pin Adapter for use with listed connector, marked Al-Cu and for use with connectors in electrical equipment marked to indicate its suitability FOR USE WITH ALUMINUM WIRE.
1. Select the Pin Adapter marked for the aluminum wire size to be terminated.
2. Check the copper pig-tail length against the equipment connector to be sure sufcient contact is made with the pressure plate or set screw in the mechanical equipment connector. Do this with the mated insulating cover (600V 90° C) supplied, in place over the Pin Adapter.
WARNING
RISK OF SHOCK, DISCONNECT
POWER BEFORE INSTALLATION.
CAUTION
This adaptor is to be used only in accordance with the limitations of clearance and bending radii as specied in the following instruction. It is recognized that there is equipment within which this adaptor cannot be use in accordance with these instructions.
4. Check wiring room leading to the mechanical equipment lug to be sure use of the Pin Adapter will not reduce the minimum wire bending space required by Table 312.6(A) of the National Electrical Code**. (Measured without cover installed as shown in Step 5).
National Fire Protection Association.
5. Bend cable to t in equipment before installing the Pin Adapter. (Check wire bending space from Adapter rear to inside face of housing or nearest obstruction.Measurement is perpendicular to the rear of Adapter).
**Registered trademark of the
Copper Pig-Tail
3. Check diameter of mated insulating cover to assure that there is no interference in any direction when it is installed
CAUTION
DO NOT INSTALL the Pin Adapter in opposite holes if mated insulating covers are closer together than shown. Spacing must be more than 1/4" for 300V or less and more than 1/2" for 301-600V.
TA01773 C Page 1 of 2
6. Strip insulation to length of compression barrel as shown in table in column "A" to permit full insertion of wire. Scratch brush the aluminum conductor before installation. Select appropriate tool and dies as shown in the table, and make the required number of crimps.
7. After installing the Pin Adapter on the conductor, slip the insulating cover completely over the compression barrel. Use of the insulating cover assures that minimum electrical spacing will not be violated.
8. Insert pig-tail fully into connector body and tighten set screw to equipment manufacturer’s recommended torque (if no torque recommendation is provided, tighten to recommended values given in table).
Page 2
†Overlap Compressions
INSTALLATION B:
Pin Adapter for use with listed connectors and with connectors in UL listed equipment, SUITABLE FOR COPPER WIRE ONLY.
(NOTE: UL listed connectors and electrical equipment suitable for copper wire only do not bear marking to indicate such use.)
1a. Determine equipment,
rating(ampacity) and/or ampacity service required for the specic connector.
1b. Based on (a), determine copper wire
gauge size that normally would be selected.
1c. Select appropriate Pin Adapter and
the associated catalog number for insulation by locating the required COPPER wire size and the table titled "Catalog and Specication Information."
2a. Continue with steps 2 through 8 as
above. NOTE: Referring to step 5 — installer is cautioned to assure that the use of Pin Adapter in UL listed equipment will provide a full minimum wire bending space.
L
C
A
ID
OD
SOLID KNURL OR INK MARK
BARRIER
WARRANTY: Thomas & Betts sells this product with the understanding that the user will perform all necessary tests to determine the suitability of this product for the user's intended application. Thomas & Betts warrants that this product will be free from defects in materials or workmanship for a period of two (2) years following the date of purchase. Upon prompt notication of any warranted defect, Thomas & Betts will, at its option, repair or replace the defective product. Misuse, misapplication or modication of Thomas & Betts Products immediately voids all warranties.
Limitations and Exclusions: THE ABOVE
WARRANTY IS THE SOLE WARRANTY CONCERNING THIS PRODUCT, AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, WHICH ARE SPECIFICALLY DISCLAIMED. LIABILITY FOR BREACH OF THE ABOVE WARRANTY IS LIMITED TO COST OF REPAIR OR REPLACEMENT OF THE PRODUCT, AND UNDER NO CIRCUMSTANCES WILL THOMAS & BETTS BE LIABLE FOR ANY INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Thomas & Betts Corporation
Memphis, Tennessee
www.tnb.com
D
E
4.
HOW TO MAKE A GOOD ALUMINUM CONNECTION:
Insert the conductor all the way into the barrel and using the proper die (see chart) crimp the connector.
1.
Select Pin Adapter marked for the wire size to be used.
NOTE: Overlap crimps are to be made between knurl or ink marks. Multiple crimps are to be made adjacent to each other between knurl or ink marks. Make sure that the connector is used with a die that matches the die index, code number or color marked
2.
Do not nick or ring the conductor
on the connector.
strands when stripping the wire insulation.
5.
Use circumferential or hex dies. Compress from base of socket toward
3.
Remove oxide lm with wire brush from the stripped portion of the conductor.
CATALOG AND SPECIFICATION INFORMATION
ALUM.
WIRE
SIZE
COPPER
WIRE
SIZE
CODE
INDEX
A C D L OD ID
DIE
UT3 UT5 TBM5 TBM6 TBM8
76 or
TX
76H
BURNDY DIES
DIE
Y34A MD6 MD6
BG perm. Gr.
with BG insert U-BG
T&B DIES
CAT
NO.
PA06 #6 #8 1 1.344 0.875 2.219 0.640 0.191 35 100 ORANGE 50 2 BG/243 3
PA04 #4 #6 1 1.344 0.875 2.219 0.640 0.247 35 100 ORANGE 50 2 BG/243 3
PA02 #2 #4 1 1.344 0.875 2.219 0.640 0.310 50 125 ORANGE 50 2 BG/243 3
PA01 #1 #3 1 1.344 1.000 2.344 0.640 0.360 50 125 ORANGE 50 2 BG/243 3
PA11 1/0 #2 1.250 1.594 1.250 2.844 0.906 0.393 50 150 RED 76 2 324 2
PA21 2/0 #1 1.250 1.594 1.250 2.844 0.906 0.440 50 150 RED 76 2 324 2
PA31 3/0 1/0 1.250 1.875 1.375 3.250 0.906 0.494 200 RED 76 2 324 2
PA41 4/0 2/0 1.250 1.875 1.375 3.250 0.906 0.549 200 RED 76 2 324 2
PA25 250 MCM 3/0 1.375 2.062 1.500 3.562 1.155 0.595 250 BROWN 87H 2 299 2
PA30 300 MCM 4/0 1.375 2.062 1.625 3.687 1.155 0.650 250 BROWN 87H 2 299 2
PA35 350 MCM 4/0 1.375 2.062 1.625 3.687 1.155 0.705 250 BROWN 87H 2 299 2
PA40 400 MCM 250 1.375 2.087 1.875 3.962 1.375 0.762 250 BLACK 106H 2 300 3
PA50-BB 500 MCM 350 1.375 2.087 1.875 3.962 1.375 0.848 300 BLACK 106H 2 300 3
PA60 600 MCM 350 1.875 2.750 1.875 4.625 1.500 0.924 300 YELLOW 115H 3 936 3
PA75BB 750 MCM 500 1.875 2.750 2.000 4.750 1.500 1.015 300 YELLOW 115H 3 936 3
ALUM. WIRE SIZE
#6 - #1 50 5/8 TU Orange 15529
1/0 - 4/0
250 MCM - 350 MCM 87H TH 13468 11746 15506 11176 400 MCM - 500 MCM 106H 11749 15515 11140
600 MCM - 750 MCM 115H 11753 15504 11157
ALUM. WIRE SIZE
#6 - #1 BG/243 A243 MD5 - 3
1/0 - 4/0 324 A29AR U29ART U29ART C29AR F29AR
250 MCM - 350 MCM 299 U31ART U31ART C31AR F31AR
400 MCM - 500 MCM 300 U34ART U34ART C34AR F34AR
600 MCM - 750 MCM 936 U39ART-2 C39ART-2 F39ART-2
cable. Remove ash. Remove excess inhibitor before slipping the insulating sleeve into place.
RECOMMENDED
13472 Red 13476 Red
TIGHTENING
TORQUE
(INCH - LBS.)
SCREW
WRENCH
DRIVER
13467 11744 15512 11170
Y35
& Y35L
DIE
COLOR
CODE
TBM12PCR-LI
13642
12 TON
Y46
*
U243 C243 U243
Use with Burndy adapter Cat. No. P-UADP
*
COMPRESSION DIES
T&B BURNDY
DIE COMP. INDEX COMP.
TBM15CR-LI
TBM15
TBM15I
UT15
Y48B Y486RB Y39
21920
20 TON
U29ART
U31ART
U34ART
U39ART-2
TA01773 C Page 2 of 2© 2014 Thomas & Betts Corporation. All Rights Reserved