Displaying Software Version Number ....................................................................41
Appendix A Fluids
Appendix B NC Serial Communications Protocol
Appendix C International Quick Reference Operating Procedures
W ARRANTY
- 1 -
Page 3
Compliance
WEEE Compliance
Preface
UL Listed to UL3101-1 (UL61010A-1)
Certified to CSA C22.2 No. 1010.1
Complies with IEC/EN 61010-1
Products tested and found to be in compliance with the requirements defined in
the EMC standards defined by 89/336/EEC as well as Low Voltage Directive
(LVD) 73/23/EEC can be identified by the CE label on the rear of the unit. The
testing has demonstrated compliance with the following directives:
LVD, 73/23/EECEN 610010-1:1993
EMC, 89/336/EECEN 61326-1:1998
For any additional information, refer to the Letter of Compliance that shipped
with the unit (Declaration of Conformity).
This product is required to comply with the European Union’s Waste Electrical
& Electronic Equipment (WEEE) Directive 2002/96/EC. It is marked with the
following symbol:
Unpacking
Warranty
Thermo Electron has contracted with one or more recycling/disposal companies
in each EU Member State, and this product should be disposed of or recycled
through them. Further information on Thermo Electron’s compliance with these
Directives, the recyclers in your country, and information on Thermo Electron
products which may assist the detection of substances subject to the RoHS
Directive are available at: www.thermo.com/WEEERoHS
Retain all cartons and packing material until the unit is operated and found to
be in good condition. If the unit shows external or internal damage contact the
transportation company and file a damage claim. Under ICC regulations, this is
your responsibility.
Units have a warranty against defective parts and workmanship for 24 months
from date of shipment. See back page for more details.
- 2 -
Page 4
After-sale Support
Thermo Electron Corporation is committed to customer service both during and
after the sale. If you have questions concerning the unit operation, contact our
Sales Department. If your unit fails to operate properly, or if you have questions
concerning spare parts or Service Contracts, contact our Service Department.
Before calling, please obtain the following information:
- unit BOM number_________________________________
- unit serial number ________________________________
- unit software version ______________________________
- voltage of power source ____________________________
The unit’s BOM number and serial number are printed on the name plate label
located on the rear of the unit. See page 41 for instructions on how to decode
your unit's BOM number. See page 41 for instructions on how to display the
software version.
NES-care Extended
Warranty Contract
Copyright
S/N: 101039026
• Extend p arts and labor coverage for an additional year.
• Worry-free operation.
• Control service costs.
• Eliminate the need to generate repair orders.
• No unexpected repair costs.
Other contract options are available. Please contact Thermo for more
information.
All rights reserved. This document is for informational purposes only and is
subject to change without notice.
Feedback
We appreciate any feedback you can give us on this manual. Please e-mail us
at neslabmanuals@thermo.com. Be sure to include the manual part number
and the revision date listed on the front cover.
- 3 -
Page 5
Warnings
Section I Safety
Warnings are posted throughout the manual. These warnings are designated
by an exclamation mark inside an equilateral triangle and text highlighted in
bold. Read and follow these important instructions. Failure to observe these
instructions can result in permanent damage to the unit, significant property
damage, or personal injury or death.
The lightning flash with arrow symbol, within an equilateral triangle, is intended
to alert the user to the presence of non-insulated "dangerous voltage" within
the unit's enclosure. The voltage may be of significant magnitude to constitute
a risk of electrical shock.
This label, engraved into the front of the tank lip, indicates the presence of hot
surfaces.
Make sure you read and understand all instructions and safety precautions
listed in this manual before installing or operating your unit. If you have any
questions concerning the operation of your unit or the information in this
manual, contact our Sales Department.
Performance of installation, operation, or maintenance procedures
other than those described in this manual may result in a hazardous
situation and may void the manufacturer's warranty.
Transport the unit with care. Sudden jolts or drops can damage the
refrigeration lines. The units weigh approximately: RTE 7, 60 pounds (27
kilograms); RTE 10, 68 pounds (31 kilograms); RTE 17, 71 pounds (32
kilograms); RTE 740, 87 pounds (39 kilograms). Units should be transported with equipment designed to lift these weights.
Observe all warning labels.
Never remove warning labels.
Never operate damaged or leaking equipment.
Never operate the unit without bath fluid in the bath.
The user is responsible for the fluid used. Never use pure ethylene
glycol as a bath fluid, the flash point of 100% ethylene glycol is 111°C.
100% ethylene glycol may produce flammable vapors that can be
ignited by an open flame or an ignition source. When mixed with
water, ethylene glycol is not flammable. Also, at high temperatures
pure ethylene glycol may produce hazardous vapors.
Always turn off the unit and disconnect the line cord from the power
source before performing any service or maintenance procedures, or
before moving the unit.
Always empty the bath before moving the unit.
Never operate equipment with damaged line cords.
Refer service and repairs to a qualified technician.
- 4 -
Page 6
Indicates heater status.
See page 17.
General Information
Section II General Information
Press to start/stop the
unit. See page 17.
Indicates refrigerationsystem status. See
page 17.
Indicates the controller is
displaying the setpoint. Press
the arrow buttons to change the
value. See page 18.
Press to mute the alarm. See page
22. Digital Plus controller only.
Press to select externalsensor. See page 22. Digital
Plus controller only.
Indicates the controller is
displaying the unit's lowtemperature alarm setpoint.
Press the arrow buttons to
change the value. See page 18.
Press to select the serialcommunication mode.
See page 22. Digital Plus
controller only.
Controller. See page 17.
Press to select the timer
function. See page 23
Digital Plus controller
only.
Press to change the
displayed value. See
page 17.
Press to sequence
through the three indicators
and accept the displayed
value. See page 17.
NOTE: None of the three
setpoint indicators are
visible unless this key is
pressed.
Press to select the
temperature offset
mode. See page 23.
Digital Plus controller only.
Indicates the controller is displaying
the high temperature alarmsetpoint. Press the arrow buttons
to change the value. See page 18.
Condenser Access Panel.
See page 33.
Reservoir. See page 16.
High Temperature Cutout.
See page 28.
Autorefill connection.
See page 29.
RS-232/RS-485
connections. See
Appendix B. Digital
Plus controller only.
1/8"OD Autorefill fluid
connection. See page 29.
1/*4" MPT Pumping
Supply Connection. See
page 14.
Drain. See page 14.
Optional External Sensor
Connector. Digital Plus
controller only.
Analog Output
Connector. Digital
Plus controller only.
See page 27.
Circuit Breaker(s).
Power connection.
See page 12.
1/8"OD N2 Nitrogen
Purge. See page 29.
1/4" MPT Pumping
Return Connection. See
page 14.
- 5 -
Page 7
Quick Reference Operating Procedures
Installation
Locate the unit on a sturdy work area. Ambient
temperatures should be inside the range of +50°F to
+104°F (+10°C to +40°C). The maximum operating
relative humidity is 80%.
Never place the unit in a location where excessive
General Information
heat, moisture, or corrosive materials are present.
The unit has an air-cooled refrigeration system. Air
is drawn through the front panel and discharged
through the rear panel. The unit must be positioned
so the air intake and discharge are not impeded. A
minimum clearance of 12 inches (30 centimeters) at
the front and rear of the unit is necessary for
adequate ventilation. Inadequate ventilation will
reduce cooling capacity and, in extreme cases, can
cause compressor failure.
Excessively dusty areas should be avoided and a
periodic cleaning scheduleshould be instituted.
The unit will retain its full rated capacity in ambient
temperatures up to approximately +75°F (+24°C).
Make sure the voltage of the power source meets
the specified voltage, ±10%.
The pump connections are located at the rear of the
pump box and are labelled and . These
connections are angled upward so the recirculating
fluid will drain back into the reservoir when the
hoses are disconnected. Both connections are
capped with stainless steel serrated plugs.
The pump lines have ¼" MPT for mating with
standard plumbing fittings. For your convenience
stainless steel adapters, ¼" FPT to 3/8" O.D.
serrated fitting, are provided.
The bath work area has a high and low level marker
to guide filling. The markers are 1 inch horizontal
slits located in the center of the stainless steel
baffle separating the work area and the pump
assembly. The correct fluid level falls between
these two markers. The unit will not start if the fluid
level is below the lower slit.
Operation
Before starting the unit, double-check all electrical
and plumbing connections. Make sure the bath is
properly filled with fluid.
To start the unit, press . To turn the unit off
press
The
illuminates to indicate the heater is on.
The LED indicates the status of the refrigeration system. It illuminates to indicate the refrigera-
tion system is removing heat from the cooling fluid.
Temperature Adjustment
To display the temperature setpoint, press on
the controller. The indicator will illuminate and
the display will flash the current setpoint value. To
adjust the temperature setpoint, press the arrow
buttons until the desired temperature setpoint is
indicated. Press again to confirm the change.
The display will rapidly flash the new value for a
short time and then return to the recirculating fluid
temperature.
Periodic Maintenance
Periodically inspect the reservoir fluid. If cleaning is
necessary, flush the reservoir with a cleaning fluid
compatible with your application.
The reservoir fluid should be replaced periodically.
Frequency depends on the operating environment
and amount of usage.
Before changing the reservoir fluid ensure it is
at a safe handling temperature.
Periodic vacuuming of the condenser fins is necessary. The frequency of cleaning depends on the
operating environment. We recommend a monthly
visual inspection of the condenser after initial
installation. After several months, the cleaning
frequency will be established.
again.
LED indicates the status of the heater. It
- 6 -
Page 8
Description
General Information
The NESLAB RTE Refrigerated Bath/Circulators are designed to provide
temperature control for applications requiring a fluid work area or pumping to an
external system. Units consist of a non-CFC air-cooled refrigeration system, circulation
pump, seamless stainless steel bath, work area cover, and a microprocessor temperature
controller.
Specifications
Temperature Range
Temperature Stability
Cooling Capacity
1
RTE 7RTE 10 RTE 17 RTE 740
2
3
4,
-25°C to +150°C -22°C to +150°C -40°C to +200°C
±0.01°C
1100
1000
900
800
B
A
700
600
500
400
300
Heat Removal (Watts)
200
100
-40-30-20-10 0 10 20 30 40 5060 70 80 90100
A=115/60 RTE-740 units
B=230/50 RTE-740 units
C=RTE-7, 10, 17
C
Temperature °C
Pump Capacity
4
Meters Feet
4.916
3.712
e
r
u
s
s
e
r
P
2.48
1.24
0.81.62.43.24.0 Gpm
3691215Lpm
Flow
- 7 -
Page 9
Time to Temperature
115V/60 Hz units
General Information
230V/50 Hz units
RTE-740 units
- 8 -
Page 10
Heater (Watts)
115V/60 Hz Models
230V/50 Hz Models
100V/50-60Hz Models
Refrigerant
RTE 7RTE 10RTE 17 RTE 740
800 1600 800
2000 2000 2000
800 1200 800
R134a (6 ounces)
R404a (8 ounces)
General Information
Bath Work Area
(W x L x D)
Inches
Centimeters
Bath Volume
Gallons
Liters
Air Flow Requirements
SCFM
Weight
Pounds
Kilograms
5
65/8 x 7¼ x 6
16.8 x 18.3 x 15.2
1.9
7.2
8¾x 9 3/8 x 6
22.4 x 23.9 x 15.2
2.6
9.8
8¾ x 9 3/8 x 9
22.4 x 23.9 x 22.9
4.5
17.0
65/8 x 7¼ x 6
16.8 x 18.3 x 15.2
1.9
7.2
200170
5
60
27.2
1. Specifications subject to change.
2. Baths are tested at temperatures below freezing with denatured alcohol. This fluid is HIGHLY
flammable and is not recommended by Thermo. Above 80°C, baths are tested at with silicone
oil. This fluid is known to release a formaldehyde vapor (which is carcinogenic) above 150°C.
3. 20°C ambient. 20°C bath temperature using water. Sea level. Measured at the center of the
work area, work cover on, no external flow, stable ambient, full refrigeration (RTE-740 in
Energy Saving Mode). For some applications, agitation and stability above ambient may be
improved by connecting a small length of hose between the pump connections on the rear of
the unit.
4. 20°C ambient. 20°C bath temperature using water. Pump fully loaded. Sea level.
5. See next page for unit dimensions.
6. Add approximately 3 pounds (1.4 kilograms) for shipping weight.
68
30.8
71
32.2
87
39.5
- 9 -
Page 11
Unitl Dimensions (inches)
C
General Information
30°
E
F
7
/8
1
3¼
15/8
D
B
Rear View Side View
Unit Dimensions
105°
½
17/8
1½
RTE 7RTE 10RTE 17RTE 740
A
Dimension A
Dimension B
Dimension C
Dimension D
Dimension E
Crate Dimensions
(D x W x H)
23 5/823 5/826 5/826 5/8
9 1/411 3/811 3/811 3/8
1920 1/820 1/820 1/8
17 3/817 3/820 3/820 3/8
10 5/810 5/810 5/812 3/8
26½ x 18 x 33½
- 10 -
Page 12
Site
Section III Installation and Operation
Locate the unit on a sturdy work area. Ambient temperatures should be inside
the range of +50°F to +104°F (+10°C to +40°C). The maximum operating
relative humidity is 80%.
Never place the unit in a location where excessive heat, moisture, or
corrosive materials are present.
The unit has an air-cooled refrigeration system. Air is drawn through the
front panel and discharged through the rear panel. The unit must be
positioned so the air intake and discharge are not impeded. A minimum
clearance of 12 inches (30 centimeters) at the front and rear of the unit is
necessary for adequate ventilation. Inadequate ventilation will reduce
cooling capacity and, in extreme cases, can cause compressor failure.
Excessively dusty areas should be avoided and a periodic cleaning schedule
should be instituted (see Section IV, Condenser Cleaning).
Using 20°C water as a bath fluid, 115/60 units will retain their full rated capacity in ambient temperatures up to +20°C. Reduce the cooling capacity approxi-mately 15 watts for every 1°C above +20°C, to a maximum ambient temperature of +40°C. For 230/50 units, reduce the cooling capacity approximately 18
watts for every 1°C. Lower reductions in cooling capacity occur as the bath
fluid temperature increases.
Installation and Operation
- 11 -
Page 13
Electrical
Requirements
Installation and Operation
The unit construction provides protection against the risk of electrical
shock by grounding appropriate metal parts. The protection may not
function unless the power cord is connected to a properly grounded
outlet. It is the user's responsibility to assure a proper ground connection is provided.
We recommend the use of a dedicated outlet.
Refer to the serial number label on the rear of the unit to identify the specific
electrical requirements of your unit. Ensure the voltage of the power source
meets the specified voltage, ±10%.
The RTE-7 is not designed to be used beyond the voltage range or have
momentary power interruptions. Install an “un-interruptible power supply” or a
line loss detection method.
All units are:
Pollution Category 2
Overcurrent Protection II
The following power options are available:
UnitAmps
1
BreakerPower Inlet
RTE 7115/60/11215AIEC 320-C-13
100/50-60/11215AIEC 320-C-13
230/50/11215AIEC 320-C-19
RTE 10115/60/11215AIEC 320-C-13
100/50-60/11215AIEC 320-C-13
230/50/11215AIEC 320-C-19
RTE 17115/60/11620AIEC 320-C-19
100/50-60/11620AIEC 320-C-19
230/50/11215AIEC 320-C-19
RTE 740 115/60/11620AIEC 320-C-19
100/50-60/11620AIEC 320-C-19
230/50/11215AIEC 320-C-19
1. Average Amp draw.
- 12 -
Page 14
Unit Type
115/60/115NEMA 5-15
115/60/120NEMA 5-20
1
AmperagePlug Type
100/50-60/115NEMA 5-15
100/50-60/120NEMA 5-20
230/50/1AllCountry Specific
1. Power cord length, if supplied, is 2 meters.
Power Cord Set
230 Volt, 50 Hertz units do not come with a power cord set. To select the
proper power cord, follow these guidelines:
The cord set must consist of a plug, cable and receptacle.
If the unit is rated greater than 12 Amps, use a cord set rated for 20A.
If the unit is rated less than 12 Amps, use a cord set rated for 15A.
The cord set must be approved by local electrical authority or other
acceptable agency.
Ensure the plug is compatible with your local outlets and receptacles.
Installation and Operation
- 13 -
Page 15
Plumbing Requirements
Ensure the unit is off before connecting tubing to the unit.
To prevent damage to the plumbing lines, always support the fittings
while installing/removing the pumping caps and lines.
Hose Connections
The pump connections are located at the rear of the pump box and are labelled
(pump outlet) and (pump inlet). These connections are bent upward
so the recirculating fluid will drain back into the reservoir when the hoses are
disconnected. Both connections are capped with stainless steel serrated plugs.
The pump lines have ¼" MPT for mating with standard plumbing fittings. For
your convenience stainless steel adapters, ¼" FPT to
3
/8" O.D. serrated fitting,
are provided. (To assure proper fit, they should be installed using 1½ turns of
Teflon® tape around the threads.)
Installation and Operation
Drain
Make sure all tubing connections are securely clamped. Avoid running
tubing near radiators, hot water pipes, etc. If substantial lengths of tubing
are necessary, insulation may be required to prevent loss of cooling capacity.
Tubing and insulation are available from Thermo. Contact our Sales Department
for more information (see Preface, After-sale Support).
It is important to keep the distance between the unit and the external system
as short as possible, and to use the largest diameter tubing practical. Tubing
should be straight and without bends. If diameter reductions must be made,
make them at the inlet and outlet of the external system, not at the unit.
If substantial lengths of cooling lines are required, they should be pre-filled with
bath fluid before connecting them to the unit. This will ensure that an adequate
amount of fluid will be in the bath once it is in operation.
Ensure the bath fluid is at a safe handling temperature before draining
the unit.
The unit is equipped with a drain located at the back of the unit labelled .
To drain the reservoir attach a hose to the barb and loosen the fitting.
The fitting has a stop to prevent it from coming off.
Pumping
The pump is designed to deliver a flow of 15 liters per minute (4 gallons per
minute) at 0 feet head. To prevent external circulation, the pump inlet and
outlet lines on the rear of the unit are capped. The caps must be removed when
external circulation is required.
To properly secure external hose connections to the unit, wrap Teflon® tape
around the pipe line threads before installation. Once the hose connections are
made, the hoses must be properly plumbed to an external system. It is
important the bath is not in operation until all plumbing is complete.
- 14 -
Page 16
Circulating to an open container
Outlet
Inlet
Levelling
Device
Installation and Operation
Bath (Rear View)
Open Container
A stainless steel leveling device is available to aid circulation to an open
vessel. Contact our Sales Department for more information (see Preface).
Support the leveling device over the open container with a ringstand. Stagger
the tubes in the leveling device so one tube is submerged in the vessel fluid,
and the other tube is level with the fluid surface. Connect the deeper tube to
the pump outlet and the shorter tube to the pump inlet.
Adjust the flow rate using the accessory flow control valve connected to the
pump outlet, or by partially restricting the outlet tubing. When properly
adjusted, the pump inlet will draw an occasional air bubble to prevent over
flow, and the pump outlet will force fluid through the submerged tube to
prevent aeration of the vessel.
To avoid siphoning the bath work area when the unit is shut off, lift the
leveling device out of the vessel and above the level of the unit.
Circulating through two closed-loops
Pump Box
Bath
Work Area
Bath (Top View)
System #1
System #2
The pump can be used to circulate through two closed-loop systems. Connect
the shortest practical length of flexible tubing from the pump outlet to the inlet
of external system #1. Connect the outlet of system #1 directly into the bath
work area. Connect tubing from the bath work area to the inlet of system #2.
Connect the outlet of system #2 to the pump inlet.
- 15 -
Page 17
Fluids
Installation and Operation
The user is always responsible for the fluid used. Never use flammable
or corrosive fluids with this unit. The use of chlorine or sodium
hypochlorite in the baths will cause pitting that could leave to failure of
the refrigeration system.
Handling and disposal of liquids other than water should be done in
accordance with the fluid manufacturers specification and/or the MSDS
for the fluid used.
For fluid selection consider application requirements, operating temperature
range, material compatibility, safety concerns, and environmental issues.
Wetted materials of bath include; 316 and 304 Stainless steels, Ryton® (PPS),
®
Teflon
Deionized (up to 18 Meg-ohm/cm) and distilled water are recommended to
control corrosion and algae bloom. See Water Quality Standards and Recommendation in Appendix A.
(PTFE) and Ethlyene-Propylene rubber (EPDM).
Filling
Requirements
Ethylene glycol, propylene glycol, silicone oil, and filtered water are acceptable
fluids.
NOTE: Kinematic viscosity of the selected fluid should not exceed 50
centistokes at the lowest operating temperature.
Please call Thermo customer service to discuss high and low temperature fluid
selections. However, we will often refer you to chemical companies specializing in heat transfer fluids.
Ensure the drain on the back of the unit is closed before filling the unit.
The bath work area has a high and low level marker to guide filling. The
markers are 1 inch horizontal slits located in the center of the stainless steel
baffle separating the work area and the pump assembly. The correct fluid
level falls between these two markers.
NOTE: The unit is equipped with a reservoir level float switch. The switch
prevents the unit from starting if the fluid is below the lower slit.
When pumping to an external system, keep extra fluid on hand to maintain
the proper level in both the circulating lines and the external system.
Avoid overfilling, fluids expand when heated.
- 16 -
Page 18
Controller
(Digital One/Digital Plus)
The controller controls temperature using a Proportional-Integral-Derivative
(PID) algorithm. It is designed with self-diagnostic features and easy to use
operator interface. Two controller options are available: Digital One and Digital
Plus. The information on the following two pages applies to both controllers.
Installation and Operation
Digital One Controller
Yes
No
ON/OFF. Use this key to toggle the unit on or off and to clear error mes-
sages.
SCROLL. Use this key
to scroll through the controller's LEDs. It is also
used to save new changes.
YES/ARROW. Use this key to increment numerical values when setting
values and to accept new settings.
NO/ARROW. Use this key to decrement numerical values when setting
values and to abort new settings.
Indicates refrigeration system status. It illuminates to indicate the refrigeration
system is removing heat from the bath fluid. The indicator is off when heat is not
being removed.
Indicates heater status. It illuminates to indicate the heater is adding heat from
the bath fluid. The indicator is off when heat is not being added.
- 17 -
Page 19
Installation and Operation
NOTE: The following indications are not visible until is depressed.
Setpoint. Indicates the controller is displaying the current setpoint.
Low Temperature Alarm. Indicates the controller is displaying the current
low temperature alarm.
High Temperature Alarm. Indicates the controller is displaying the current
high temperature alarm.
To adjust the displayed value use the arrow buttons. Pressing an arrow button
will cause the display to stop flashing and to indicate the new setpoint value.
Save the change by pressing SCROLL. The new setpoint value will rapidly flash
for two cycles and then the controller will return to the reservoir fluid temperature display.
If SCROLL is not pressed within 60 seconds the change will time out and revert
to the original setpoint. The controller will automatically return to the reservoir
fluid temperature display.
NOTE: You can not adjust the setpoint closer than 0.1°C of either temperature
limit, and you can not adjust either temperature limit within 0.1°C of the
setpoint. Trying to do so will cause the indicator to flash and, on Digital Plus
controllers, the alarm to beep.
On units with the Digital Plus controller, pressing the Mute button prior to
pressing SCROLL will abort any changes and return to the reservoir fluid
temperature display.
- 18 -
Page 20
Start Up/Shut Down
(Digital One/Digital Plus)
Installation and Operation
Controller
Pre-Start
Starting
Full Range Cooling
Setpoint
Before starting the unit, recheck all electrical and plumbing connections.
Ensure the bath reservoir is properly filled. The unit will not start if the reservoir
fluid level is below the lower horizontal slit.
The unit can be configured for automatic restart. If the unit shuts down as
a result of a losing power, once power is restored the unit will restart.
See Setup/Tuning Loop on page 21 to enable this feature.
Press
Digital Plus units momentarily sound the alarm), then quickly displays the
setpoint before displaying the reservoir fluid temperature. The pump starts and,
after a 30 second delay, the refrigeration comes on. The RTE-740 refrigeration
system is designed to start with the pump.
NOTE: If the unit's recirculating fluid is outside either temperature limit, the unit
will start but the appropriate indicator will flash until the fluid is within the limit.
If refrigeration is needed for operation above 50°C, turn on the Full Range
Cooling Mode. See Setup/Tuning Loop on page 21 to enable this feature.
To display/change the setpoint press until illuminates. The display
. The controller does a self-test (sequences through the LEDs, and
will flash the current setpoint value. Use the arrow buttons to change the value.
The controller will not allow you to enter a setpoint closer than 0.1°C of either
temperature alarm setting, see next page. Attempting to causes the indicator
to flash and, on Digital Plus controllers, sounds the alarm.
Once an arrow button is depressed starts to flash. If an arrow button is not
pressed within 10 seconds the display will return to the reservoir temperature.
On units with the Digital Plus controller, pressing Mute prior to pressing
SCROLL will abort any change and return you to the fluid temperature display.
Once the desired setpoint is displayed, press again to confirm the
change. The display will rapidly flash the new value twice and then return to the
recirculating fluid temperature. If the new value is not confirmed within 60
seconds the display will return to the fluid temperature and ignore any change.
- 19 -
Page 21
Low Temp Alarm
To display/change the low temperature alarm setting press until
illuminates. The display will flash the current limit value. Use the arrow buttons
to change the value. You can not set the alarm closer than 0.1°C below the
setpoint. Attempting to causes the indicator to flash and, on Digital Plus
controllers, sounds the alarm.
On units with the Digital Plus controller, pressing Mute prior to pressing
SCROLL will abort any change and return you to the fluid temperature display.
Once an arrow button is depressed starts to flash. If an arrow button is not
pressed within 10 seconds the display will return to the current reservoir
temperature.
Installation and Operation
High Temp Alarm
Once the desired setting is displayed, press again to confirm the change.
The display will rapidly flash the new value twice and then return to the recircu-
lating fluid temperature. If the new value is not confirmed within 60 seconds the
display will return to the fluid temperature and ignore any change.
To display/change the high temperature alarm setting press
until
illuminates. The display will flash the current setting value. Use an the arrow
buttons to change the value. You can not set the alarm closer than 0.1°C
above the setpoint. Attempting to causes the indicator to flash and, on Digital
Plus controllers, sounds the alarm.
On units with the Digital Plus controller, pressing Mute prior to pressing
SCROLL will abort any change and return you to the fluid temperature display.
Once an arrow button is depressed starts to flash. If an arrow button is not
pressed within 10 seconds the display will return to the current reservoir
temperature.
Once the desired limit is displayed, press again to confirm the change.
Stopping
The display will rapidly flash the new value twice and then return to the recirculating fluid temperature. If the new value is not confirmed within 60 seconds the
display will return to the fluid temperature and ignore any change.
To turn the unit off, press . The pump will stop and the refrigeration will
shut down. NOTE: The RTE-740 refrigeration system is designed to shut down
thirty seconds after the pump.
Thermo recommends waiting a minute before restarting the unit.
- 20 -
Page 22
Setup/Tuning Loop
(Digital One/Digital Plus)
HOLD
XX.X
No
The Setup/Tuning Loop is used to tune the controller's PID parameters
(CooL HEAt); enable/disable auto restart (AStrt); determine how the unit
will react when a fault occurs (FAUlt) — either shut down (on) or continue
to run (oFF); to configure the temperature display to indicate to a tenth or a
hundredth of a degree (rES); and to enable/disable full range cooling (FrC)
and energy saving (ESAuE) modes.
Installation and Operation
No
NOTE: For RTE-7,
10, and 17 units the
COOL PID display
only appears if the
Energy Saving
mode is enabled,
see below.
CooL
No
No
No
No
No
tunE
CooL
HEAt
AStrt
FAULt
rES
Yes
To enter the loop you must be displaying the reservoir fluid temperature,
press and hold and then press . The display will indicate tunE. Use
the arrow keys to sequence through the loop and to change a display. Use
to confirm any changes.
Thermo recommends that only a qualified technician change
PID parameters. Incorrect PID values will hamper unit performance. See page 40 for factory preset PID values.
Yes
Yes
Yes
on
AStrt
oFF
on
FAULt
oFF
0.1
rES
0.01
Yes
No
Factory preset = off
Yes
No
Factory preset = off
Yes
No
Factory preset = 0.1
RTE-7, 10, 17 only
No
FrC
ESAuE
StorE
Accept Changes
Yes
All
Changes made in the Tuning/Setup Loop take affect when
the StorE prompt. Pressing No at the prompt aborts all changes.
on
on
- 21 -
Yes
No
Factory preset = off
Yes
No
Factory preset = off
Full range cooling mode allows the refrigeration to
operate throughout the entire temperature range. If
off, refrigeration is available only below 50°C.
The Energy Saving mode is primarily designed for
applications running under a stable load. Enabling
the mode saves energy by reducing the unit’s
heater power requirements. This can result in
substantial energy savings over the life of the unit.
Yes
is pressed at
Page 23
Controller
(Digital Plus Only)
Mute
Sensor
Installation and Operation
Alarm. If the alarm sounds, use this button to toggle the alarm off and on. If
the cause of the alarm is cleared but then reoccurs, the alarm will sound again.
The button is also used to abort changes to the setpoint and temperature
alarms. It is also used to abort changes when configuring the unit for external
probe, serial communication, timer operation, or offset mode.
NOTE: Pressing and holding any of the following buttons for five seconds takes
you to their calibration or setup loop.
External Probe. Pressing the Sensor button displays the external probe
temperature and lights the LED indicating that the bath is monitoring and
controlling to this temperature. The unit will continue to monitor the internal
bath temperature to ensure the bath is running in a safe operating mode.
NOTE: If there is no sensor attached (or the circuit is open), or serial communications is enabled, the button will flash, and the alarm will beep three times.
The display will momentarily show an error message and then return to the
reservoir fluid temperature.
Computer
NOTE: The temperature display may drift for up to 10-15 seconds when
transitioning between temperature sensors. This is normal operation.
Serial Communication. Pressing Computer enables/disables the serial
communications mode of operation. In this mode all changes to the setpoint,
alarm limits, etc. must now be sent by a remote device using RS-232 or
RS-485 protocols. You can still view all settings locally but cannot alter them.
Once enabled, the Computer LED will flash when sending and receiving
signals. See Appendix B for additional information.
You can also turn the unit off by pressing but the unit will remain in the
serial communication mode. To restart, send another start command.
NOTE: If the unit is shut down in the serial communication mode and you need
to start the unit using the local controller, simultaneously depress and hold
both arrow keys for approximately 10 seconds. The display will then show the
internal probe temperature, and the alarm will sound. Press the
Computer
LED
and turn off the LED and disable serial communications. Turn the controller off
using . You can now start and operate the unit with the keypad.
- 22 -
Page 24
Timer
Timer. Pressing the Timer button enables/disables the Timer function of the
bath. You can define the current time, a turn-on time, and a turn-off time.
To setup the bath for timer operation see Timer Setup Loop on page 25.
Offset
If the bath is turned off using with the timer mode enabled, the Timer LED
Installation and Operation
will go out and the timer mode will be disabled. With the bath off, you have to
press the Timer button to enable the timer mode and light the LED.
NOTE: Enabling serial communications; time-on not defined; time-off not
defined; or clock not set, causes an error condition and disables the TIMER
mode. In this case the button will flash, the unit will beep three times, and the
display will momentarily show an error message.
If a power disruption occurs, the timer mode is disabled. The Timer Setup Loop
will have to be used to restore the settings.
Temperature Offset Mode. Pressing the Offset button, with the bath on,
enable/disables the temperature offset mode. This mode changes the temperature displayed on the bath a user defined amount. The LED will be lit when this
mode is enabled indicating that the temperature displayed is an offset value.
NOTE: The temperature offset only affects the displayed value when the offset
mode is enabled, the other setpoint values still dictate unit performance.
To setup the bath for offset mode operation see Offset Setup Loop on page 26.
If you press the Offset button when an offset is 0 or not defined, or if serial
communications is enabled, the button will flash, the unit will beep three times,
and the display will momentarily show an error message (Er53 for offset
undefined, Er54 for serial comm on). In either case the function can not be
enabled.
NOTE: Use this feature only when the bath is at a stable temperature.
In either local or Computer mode with offset disabled, the unit controls to and
displays the calibrated value for the internal or external probe, whichever is
selected.
In either local or Computer mode with offset enabled, the unit still controls to
the calibrated value, not the offset value, for the internal or external probe.
The display shows the calibrated value with the offset value added.
In Computer mode if you send a signal to the bath to display internal or
external probe temperatures, the calibrated value is returned. If you send a
signal to change the display value the offset value is returned.
- 23 -
Page 25
Computer Setup Loop
A
(Digital Plus Only)
NOTE: The Computer Setup Loop is not available if the serial communications
mode is enabled. Review/change the settings before entering the mode.
Computer
Installation and Operation
XX.X
The Computer Setup Loop is used to set the serial communications protocol
parameters. With the bath on, press and hold the Computer button for five
seconds. The controller will display SErL. Press the arrow buttons to toggle
between 232 and 485. Press the Computer button to hold the protocol and
advance you through the loop to adjust the remaining parameters. Press the
arrow buttons to adjust any parameter. When StorE is displayed press YES to
accept any new values, NO to abort them.
If the Computer button is not pressed for 60 seconds the function will time-out
and the changes will not be saved. Pressing the Mute button will also exit the
Computer Setup Loop and return you to the reservoir fluid temperature display.
Once enabled, the Computer LED will flash when sending and receiving
signals. See Appendix B for additional serial communication information.
Hold for 5 seconds
SErL
Computer
232
485
A In
Factory preset = RS232
Yes
A In = Analog In, Optional
No
See page 27.
Computer
19200
9600
bAud
Computer
Addr
Computer
No
StorE
Yes
ccept All Changes
4800
2400
1200
600
300
1 to 100
Factory preset = 19200
Yes
No
Yes
Factory preset = 1
(RS-485 only)
No
- 24 -
Page 26
Timer Setup Loop
(Digital Plus Only)
Timer
To set the timer, with the bath on, press and hold the Timer button for five
seconds to access the controller's Timer Setup Loop. The display will indicate
diSP. Use the arrow buttons to select the desired clock display. Press the
Timer button and the controller will display cloc. Use the arrow buttons to
display the correct time.
Press the Timer button and the controller will display t-On. Press the arrow
buttons to set the desired turn-on time. Press the Timer button and the
controller will display t-OFF. Press the arrow buttons to set the desired turn-off
time. Pressing the Timer button after entering the clock time will display StorE.
Press YES to accept the values, NO to abort them.
If the Timer button is not pressed for 60 seconds the function will time-out and
the changes will not be saved. Pressing the Mute will also exit the Timer Setup
Loop and return you to the temperature display.
If the bath is turned off using with the timer mode enabled, the Timer LED
will go out and the timer mode will be disabled. With the bath off, you have to
press the Timer button to enable the timer mode and light the LED.
NOTE: Enabling serial communications disables the
TIMER mode. If an error condition exists: serial
communications enabled; time-on not defined; timeoff not defined; or clock not set, the unit will beep and
will not enable the function. The display will then
indicate the reservoir fluid temperature.
If a power disruption occurs, the timer mode is
disabled. The Timer Setup Loop will have to be used
to restore the settings.
Installation and Operation
- 25 -
Page 27
Offset Setup Loop
A
(Digital Plus Only)
NOTE: Use this feature only when the bath is at a stable temperature.
Press the Offset button to display the current offset temperature value and
illuminate the LED.
Offset
Installation and Operation
To change the value press and hold the Offset button for five seconds to enter
the controller's Offset Setup Loop. The bath will alternately flash oFSEt with the
current temperature.
Use the arrow buttons to change the value. For example, if the bath is at
+40°C and the desired offset is +5°C, change the display to +45°C. Press the
Offset button once the desired offset is displayed. (If the Offset button is not
pressed the function will time-out and the change will not be saved.) The
display will show StorE. Press YES to accept the value, NO to abort it.
If, after pressing YES, the display returns to +40°C, not +45°C, the Offset
button was not depressed when you entered the Offset Setup Loop. Press the
Offset button to display the offset temperature and illuminate the LED.
XX.X
Offset
OFSEt
Offset
Hold for 5 seconds
xxx.x
Yes
No
No
StorE
Yes
ccept All Changes
NOTE: Offset only changes the display of the enabled probe. Setpoint and
alarm values will display the non-offset value.
If you press the Offset button when an offset is 0 or not defined, or if serial
communications is enabled, the button will flash, the unit will beep three times,
and the display will momentarily show an error message (Er53 for offset
undefined, Er54 for serial comm on). In either case the function can not be
enabled.
With offset disabled, the unit controls to and displays the calibrated value for
the internal or external probe, whichever is selected.
With offset enabled, the unit still controls to the calibrated value, not the offsetvalue, for the internal or external probe. The display shows the calibrated value
with the offset value added.
In Computer mode if you send a signal to the bath to display internal or
external probe temperatures, the calibrated value is returned. If you send a
signal to change the display value the offset value is returned.
- 26 -
Page 28
Analog Port - Optional
(Digital Plus Only)
A I/O Analog Port
The 15-pin female receptacle located on the rear of the controller is used for
optional analog interface.
The analog signal is setup using the unit's Computer Setup Loop. With the
bath on, press and hold the Computer button for five seconds. The controller
will display SErL. If needed, press the arrow buttons to toggle between 232,
485, and A In. With A In displayed, press the Computer button again until
StorE is displayed, press YES. Use the Computer button to enable/disable theanalog signal. The button will flash when A in is enabled.
Contact Ratings, Pins 1, 2, and 3
Maximum Voltage = 30 V AC/DC
Maximum Current = 1 Amps @ 30 V
Minimum permissible load 10uA, 10mVDC
Pin #Function
1Status relay NO. Status relay pins 1 and 3 close on start up, and open
on stop and all errors.
Installation and Operation
2Status relay NC. Status relay pins 2 and 3 open on start up, and close
on stop and all errors.
8 7 6 5 4 3 2 1
15 14 13 12 11 10 9
3Status relay common
4- 5Not used
6Analog Ground. The analog ground is physically separated from the
power ground throughout the unit. To prevent offsets that result from
ground currents, the analog and power grounds are only connected at
the unit's power supply. Analog ground should only be used as a
reference pin.
7Temp out.The fluid temperature, as measured by the enabled sensor,
can be read at this pin. The temperature scale is 10mV/°C, referenced
to analog ground, pin 6 (example: +150mV = +15.0°C).
8Not used
9Digital output ground, reference for pin 14. Digital output ground should
only be used as a reference pin.
10-13Not used
14Digital output +5VDC at 15mA max. 70mA max inrush current. This
power supply energizes on start up and de-energizes on stop and all
errors.
15Setpoint in. The temperature setpoint can be controlled by applying a
known voltage to this pin. The temperature scale is 10mV/°C, refer-
enced to analog ground, pin 6 (example: +230mV = +23.0°C).
The analog output requires calibration, see page 36.
- 27 -
Page 29
High Temperature Cutouts
(Digital One/Digital Plus)
Adjustable High Temperature Cutout
To protect your application, the adjustable High Temperature Cutout ensures
the heater will not exceed temperatures that can cause serious damage to
your unit. A single temperature sensor is located in the bath fluid. A High
Temperature fault occurs when the temperature of the sensor exceeds the set
temperature limit. The safety has a range of 0°C to 230±20°C.
In the event of a fault the unit will shut down and the controller will display HtC.
The cause of the fault must be identified and corrected before the unit can be
manually restarted.
The cutout is not preset and must be adjusted during initial installation. To set
the cutout, locate the small black adjustment dial on the rear of the controller.
Turn the dial fully clockwise and turn the power switch off then back on.
Installation and Operation
Start the unit. Adjust the setpoint for a few degrees higher than the highest
desired fluid temperature and allow the bath to stabilize at the temperature
setpoint. Turn the dial counterclockwise until you hear a click and the unit
shuts down.
Before you can restart the bath it has to cool down a few degrees. Then,
without moving the adjustment dial, turn the power switch off then back on.
NOTE: We recommend rechecking operation if the unit is moved.
High Temperature Cutout
N2 Nitrogen Purge
Non-Adjustable High Temperature Cutout
For added safety, the unit also has a non-adjustable High Temperature Cutout.
With fluid in the bath, it is set to trip at 225°C ±8°C.
If the bath is empty, the cutout has a typical trip point of 300°C. The heater
temperature can continue to rise after the cutout trips up to approximately
314°C.
There will be no indication the High Temperature Cutout activated other than an
audible click. The unit will continue to run but the heater will no longer operate.
Service will be required.
- 28 -
Page 30
Nitrogen Purge
(Digital One/Digital Plus)
Units are equipped with nitrogen purge line designed to accept a constant flow
of dry nitrogen into the reservoir. The nitrogen blankets the cooling fluid reducing fluid evaporation.
Connect your nitrogen line to the N2 1/8" OD tube on the rear of the unit.
Accessories
(Digital One/Digital Plus)
Autorefill Control
Cable Attachment
Installation and Operation
Autorefill Accessory
The autorefill accessory attaches to the rear of the bath. The autorefill provides
makeup water to replace bath fluid lost to evaporation, etc. It will require a tap
water source. A reservoir level float switch and logic/signal are already installed
in the bath.
When tap water is available, the bath is turned on, and the fluid reaches the
lower 1 inch horizontal level indicator located in the reservoir the autorefill
begins filling the bath. The autorefill shuts off when the fluid reaches the upper
indicator, or if the bath is turned off.
Cap Tube
Tap Water Inlet
Autorefill Module
Power Supply Inlet
DescriptionPart Number
100-115V/50/60Hz611012000001
200-240V/50/60Hz, No line cord611028000001
NOTE: Power the Autorefill Accessory with an AC Adapter that is UL Listed
with the following ratings:
- Class 2
- Input rated 100-240 VAC, 47-63 Hz, 0.4A
- Output rated 12VDC, 1.25A Max.
- 29 -
Page 31
Reservoir Overflow Device
The overflow device is designed to act as an automatic drain for the unit's
reservoir. The assembly is stainless steel with the exception of the drain fitting
which is Ryton®. The unit can still be drained as normal, but if the level reaches
the middle of the tee it will begin to overflow out the bent tube.
•Drain the unit's reservoir.
•Remove and discard the stop screw from the
bottom of the unit's drain housing.
•Remove the unit's drain fitting.
Installation and Operation
•Thread the overflow assembly into the drain
Vertical Tube
housing. (You can remove the vertical tube
assembly from the Swagelok® fitting if
there is a clearance issue.)
•After threading the overflow assembly
in as far as it goes, loosen it back out
until the Swagelok® fitting is at the top.
•Install one of the two supplied 4-40 x
Drain Fitting
(Install
finger tight)
Swagelok® Fitting
Drain Housing
¼” phillips head screws into the
bottom of the drain housing where the
stop screw use to be. (Make sure this
screw is tight so that the assembly
Overflow Assembly
doesn’t turn and drain the tank.)
•Reinstall the vertical tube assembly into the Swagelok® if it was removed.
•Install the drain fitting into the end of the new assembly - finger tight.
•Install the other supplied 4-40 x ¼"phillips head screw into the bottom of the
overflow assembly. (This prevents the drain fitting from falling off the unit.)
DescriptionPart Number
RTE 7 and RTE 10 overflow device126000000044
RTE 17 overflow device126000000045
RTE 740 overflow device126000000049
- 30 -
Page 32
The following accessories are also available from Thermo:
Stainless Steel Test Tube Racks
Uni tTest Tubes (maximum)Size (mm)Part Number
RS-232/485 Communication Cables (Digital Plus only)
DescriptionPart Number
10' Cable Assembly 083258
*Ground Fault Current Interrupter. An electrical safety device which opens a circuit upon
observation of electricity leaking to ground through an undefined path, most likely a human
being. GFCI receptacles are required by the NEC in many locations.
- 31 -
Page 33
Accessories
(Digital Plus Only)
RPC Remote Box
An RPC can control the bath from a remote location. It mirrors the controller
displays; and has the ability to store and run up to 16 programs. It operates by
sending and receiving information by RS-485 serial communication. It attaches
to the unit by an RS-485 cable with 9-pin D subminature connectors.
The remote can be mounted to the wall with an included wall bracket, or it can
be used on a desk top with the wall bracket removed.
Installation and Operation
HEAT
COOL
BATH ON
120.0°C
Typical RPC Display
MENU
SETPOINT
DescriptionPart Number
RPC 100-115V/50/60Hz/1Ø604012000401
(with NEMA 5-15P type plug)
RPC 100-240V/50/60Hz/1Ø604028000401
(requires country specific line cord, not included)
NOTE: Power the RPC with an AC Adapter that is UL Listed with the following
ratings:
- Class 2
- Input rated 100-240 VAC, 47-63 Hz, 0.4A
- Output rated 12VDC, 1.25A Max.
- 32 -
Page 34
Service Contracts
Reservoir Fluid
Section IV Basic Maintenance
To avoid electrical shock, disconnect the mains cord prior to removing
any access panels or covers.
Thermo offers on-site Service Contracts designed to provide extended life and
minimal down-time for your unit. For more information, contact our Service
Department (see Preface, After-sale Support).
Periodically inspect the reservoir fluid. If cleaning is necessary, flush the
reservoir with a cleaning fluid compatible with your application.
The reservoir fluid should be replaced periodically. Frequency depends on the
operating environment and time of usage.
Before changing the cooling fluid ensure it is at a safe handling temperature.
Reservoir Cleaning
Algae
Condenser Cleaning
Routine cleaning can be achieved by simply sponging down the seamless
Maintenance
stainless steel tank with tap water. (Dish washing detergent may be used but
the tank must be thoroughly rinsed.)
To restrict the growth of algae in the bath, we recommend that all circulation
lines be opaque. This will eliminate the entrance of light required for the growth
of most common algae.
We recommend the use of Chloramine-T, 1 gram per 3½ liters.
For proper operation, the unit needs to pull substantial amounts of air through
a condenser. A build up of dust or debris on the fins of the condenser will lead
to a loss of cooling capacity.
Periodic vacuuming of the condenser is necessary. To access the condenser
the front grille must be removed.
The unit must be turned off before the front panel is removed.
All units have a one-piece condenser grille assembly held on by spring clips.
Carefully pull forward on the bottom of the panel to remove it.
The cleaning frequency depends on the operating environment. After initial
installation, we recommend a monthly visual inspection of the condenser.
After several months, the cleaning frequency will be established.
- 33 -
Page 35
Internal Temperature
A
X
Sensor (rdt1)
Calibration
Press and Hold
X.X
No
Yes
Should the bath fluid temperature display disagree with your calibrated reference thermometer, the internal temperature sensor (rtd1) may need calibration.
Do not pick calibration points that are outside the safe operating limits of the
fluid in your application. For example with water, 90°C and 5°C would be
typical calibration points.
No
Maintenance
No
CAL
Yes
rtd1
rdt3
A in
No
No
No
Release
NOTE: If it is more convenient, the low-end calibration can be performed before
doing the high-end.
Yes
rtd3 is used to calibrate the
refrigeration system, contact
Thermo.
Optional Display
r1 H
No
r1 L
No
Yes
Yes
r1 H
r1 L
Run the bath to a suitable highend calibration point. Place a
No
calibrated reference thermometer
Yes
200.0
in the bath. Ensure the fluid
temperature is stabilized. Press
Yes
and hold the NO button and then
press the YES button three
No
times. Release the NO button.
Yes
-40.0
The controller will display CAL.
Yes
Press YES and the controller will
display rdt1. Press YES again and
the controller will display
r1 H. Press YES again and the
controller will alternately flash
r1 H and the current probe temperature. Use the arrow
buttons to adjust the temperature to match the reference
thermometer.
Press the SCROLL and NO buttons as shown until
AoUt
No
Optional Display
StorE is displayed, press YES to accept the new value,
press No to abort it.
Repeat for the low-end temperature. Run the bath to a
No
StorE
suitable low-end calibration point. At the r1 L display use
the arrow buttons to adjust the temperature to match a
Yes
ccept All Changes
calibrated reference thermometer.
Press the SCROLL and NO buttons as shown until StorE is displayed, press
YES to accept the new value, press NO to abort it.
NOTE: Both the high and low temperatures must be entered for a valid calibration. If power is lost before the procedure is complete, critical data needed for
the calculation of calibration parameters will be lost. After pressing the YES
button at the StorE prompt wait several seconds before proceeding to ensure
that a bad calibration message does not appear. Premature use of the keypad
after pressing the YES button may cancel the bad calibration error message.
- 34 -
Page 36
External Temperature
A
Sensor (rtd2)
Calibration
(Digital Plus Only)
XX.X
Sensor
rtd2
No
StorE
Hold for 5 seconds
r2 H
YesYes
No
Yes
No
r2 L
No
ccept All Changes
When using any external sensor (rtd2) for the first time, Thermo recommends a
calibration. This calibration will only affect the temperature read by the external
sensor.
Do not pick calibration points that are outside the safe operating limits of the
fluid in your application. For example with water, 90°C and 5°C would be
typical calibration points.
NOTE: If it is more convenient, the lowend calibration can be performed
before doing the high-end.
No
r2 H
Yes
200.0
Run the bath to a suitable high-end
calibration point. Place the sensor and
Yes
a calibrated reference thermometer in
the bath. Ensure the fluid temperature
No
is stabilized. Press and hold the
Yes
r2 L
Yes
-40.0
Yes
Sensor button for five seconds. The
controller will display rtd2. Press YES
and the controller will display r2 H.
Press YES and the display will
alternately flash r2 H and the current
probe temperature. Use the arrow
buttons to adjust the temperature to
match the reference thermometer.
Maintenance
Press the SCROLL and NO buttons until StorE is displayed, pressing YES
accepts the new value.
Repeat for the low-end temperature. Run the bath to a suitable low-end calibration point. At the r2 L display use the arrow buttons to adjust the temperature
to match a calibrated reference thermometer.
Pressing the SCROLL button after the low calibration will display StorE,
pressing YES accepts the new value.
If the SCROLL button is not pressed for 60 seconds the function will time-out
and the changes will not be saved. Pressing Mute will also exit the calibration
and return you to the reservoir fluid temperature display.
NOTE: Both the high and low temperatures must be entered for a valid calibration. If power is lost before the procedure is complete, critical data needed for
the calculation of calibration parameters will be lost. After pressing the YES
button at the StorE prompt wait several seconds before proceeding to ensure
that a bad calibration message does not appear. Premature use of the keypad
after pressing the YES button may cancel the bad calibration error message.
- 35 -
Page 37
Optional Analog Port/
A
X
Calibration (Digital Plus Only)
Press and Hold
X.X
No
Yes
No
Release
The analog signal is setup using the unit's Computer Setup Loop. With the
bath on, press and hold the Computer button for five seconds. The controller
will display SErL. If needed, press the arrow buttons to toggle between 232,
485, and A In. With A In displayed, press the Computer button again until
StorE is displayed, press YES. The Computer button will flash when A in is
enabled. Use the Computer button to enable/disable the analog signal.
No
Maintenance
No
Yes
No
No
No
AoUt
No
CAL
rtd1
rdt3
A in
StorE
Yes
Yes
No
Yes
No
A iH
No
A iL
A oH
No
ccept All Changes
The analog input and output are calibrated at the factory. If you need to
recalibrate follow the diagram until the display indicates A in.
Pressing YES at the A in display and the display will indicate A iH. Press
YES and the display will alternate between A iH and some value. Apply 2.5V
to the analog input pin 15, see page 27 (analog ground is pin 6). Measure the
precise value with a voltmeter.
Change the value on the bath display to match the voltmeter reading.
Press SCROLL to check your value and
Yes
Yes
A iH
A iL
x.xxxx
x.xxxx
Yes
No
then press SCROLL again to display A iL.
If desired, repeat the procedure for A iL.
Yes
Apply 0V to pin 15. Measure the voltage
No
and change the displayed value to match it
Pressing YES at the AoUt display and the
Yes
Yes
A oH
x.xxxx
display will indicate A oH. Press YES and
No
the display will alternate between A oH
and 2.5000, the bath will set the Temp Out
pin 7 output voltage to approximately 2.5V.
Yes
A oL
x.xxxx
Yes
Measure the voltage and change the
No
displayed value to match it. Press
SCROLL to check your value and then
Factory preset values:
A iH = 2.5000
A iL = 0.0000
A oH = 2.5000
A oL = -.5000
press SCROLL again to display A oL.
If desired, repeat the procedure for A oL.
The display will alternate between A oH
and -.5000, the bath will set the Temp Out
pin 7 output voltage to approximately
-0.5V. Measure the voltage and change the
value to match the meter.
At the StorE display press YES to save the calibration, press No to abort it.
NOTE: If error code Er16 appears you will need to recalibrate.
- 36 -
Page 38
Error Codes
Section V Troubleshooting
On Start Up:
ROM checksum. Check with Thermo
Test failure. Locks up the program
Display board failure. Clears when display board is fixed
Critical checksum failure. Check with Thermo
Operational Errors:
Asynchronous communication error, check serial interface
parameters
Bad calibration data entered using Calibration Loop. Redo calibration
Unusual Hardware Conditions
These errors will flash on the display and cannot be cleared. These are internal
controller problems.
through - Interrupt errors during runtime
Synchronous communication error
BOM invalid. Contact Thermo
Functional/ Machine Errors
Warnings self-clear after the cause of the error is identified and corrected.
Faults require pressing I/0 to clear the error message and then pressing
I/0 again to start the unit after the cause of the error is identified and corrected.
Error Display Indication
Low temp setpoint warning/fault, see page 21Low level warning, fluid below safe operating levelHigh temp setpoint warning/fault, see page 21
Refrigeration sensor shorted
Refrigeration sensor open
Shorted external temperature sensor (rtd2)
Open external temperature sensor (rtd2)
Shorted internal temperature sensor (rtd1)
Troubleshooting
Open internal temperature sensor (rtd1)
Fluid low level fault - unit shuts down
Refrigeration assembly high temp fault - unit shuts down
Continued on next page.
- 37 -
Page 39
External Sensor
1 2 3 4 5
6 7 8 9
Connector
High temp fault - unit shuts down, see page 28
Configuration error
Invalid timer setting, see page 25
Offset setting = 0 or not defined, see page 26
Feature not available because serial communication
mode is enabled
Unit reaction to warning/fault errors depend on how the unit is configured, see
Setup/Tuning Loop on page 20. The unit is shipped configured to continue
running. If any other code appears contact Thermo customer service.
Digital Plus units are equipped with a male 9-pin D-connector located on the
rear of the control box. The connector is used with an optional external sensor.
Troubleshooting
Pin #Function
Example
13-wire RTD connection A
2No connection
3No connection
43-wire RTD connection A
5No connection
6No connection.
73-wire RTD connection B
8No connection
9No connection
HardwareInternal ConnectorMating Connector
AMP Part# 745492-2AMP Part# 745491-2
RTD
- 38 -
Page 40
Checklist
Unit will not start
Check the line cord; ensure it is plugged in.
Check the position of the circuit breaker on the rear of the unit.
Check reservoir. Unit will not start if fluid level is below the lower horizontal slit.
On Digital Plus controllers, check Serial Communication Mode on or off.
Check the controller for error codes, see previous page.
Make sure the voltage of the power source meets the specified voltage,
±10%. Refer to the serial number label on the rear of the unit to identify the
specific electrical requirements of your unit.
Loss of cooling capacity
Be sure the cooling capacity of the unit has not been exceeded if circulating to
an external system.
Proper ventilation is required for heat removal. Ensure ventilation through the
front and rear panels is not impeded and the panels are free of dust and debris.
Ice build up on the cooling coils can act as insulation and lower the cooling
capacity. Raise the temperature of the bath to de-ice the cooling coil and
increase the concentration of non-freezing fluid.
RTE 7 "clicking"
Turn the unit off to initiate the 30 second refrigeration pressure equalization “off”
delay. Turn the unit back on to initiate the 30 second refrigeration pressure
equalization “on” delay.
The RTE 7 is not designed to be used beyond the voltage range or have
momentary power interruptions. Install an “un-interruptible power supply” or a
line loss detection method.
Unit not cooling above 50°C
The unit is not in the Full Range Cooling Mode. See Setup Loop on page 21.
No external circulation
Check for obstructions, kinks, or leaks in the circulation tubing.
Circulation will cease when the pump head has been exceeded.
Troubleshooting
- 39 -
Continued on next page.
Page 41
No/poor temperature control
On Digital Plus controllers, check Serial Communication Mode on or off.
Check controller PID values. See next page for factory preset values.
NOTE: Using high viscosity fluids at low temperatures may require PID adjustment, contact Thermo.
All units are tested for serial communications before they leave the factory.
Ensure the Computer indicator on the controller is on.
Check all settings and commands, they must be exact. See Appendix B.
Check all wiring for proper connections or possible shorts.
Software to verify serial communication is available from Thermo.
Service Assistance
Troubleshooting
PID Values
If, after following these troubleshooting steps, your unit fails to operate
properly, contact our Service Department for assistance, see back cover.
Before calling, please obtain the following information:
- unit BOM number
- unit serial number
- software version
- voltage of power source
- fluid used
The factory set PID values for most units are:
PI DPI D
Cool0.60.60.0Heat0.60.60.0
The factory set COOL PID values for 100V and 115V RTE 740s are:
PI D
Cool0.40.60.0
The factory set HEAT PID values for 230V RTE 740s are:
PI D
Heat1.20.60.0
Thermo does not recommend changing the PID values. Incorrect PID values
will hamper unit performance.
- 40 -
Page 42
BOM Decoder
Digit#
The Bill of Material (BOM) number helps identify the configuration of your unit.
The number is printed on the label located on the rear of the unit.
Controller
00 = Digital One
01 = Digital Plus
02 = Digital Plus w/Analog I/O 10mV/ °C
99 = Custom
Reserved
00
These values will be needed when calling Thermo for sales/service information.
The controller can display the installed software version number. For example,
for a unit with software version 082645.1A:
1. Unit is running normally and displaying reservoir fluid temperature.
2. Press and hold No for at least 10 seconds. The display will show the first
two digits, for example: 08.
3. Press
Troubleshooting
The display will show the remaining digits to the left of the decimal, for
example: 2645.
4. Press
The display will show the decimal point and the digit to the right of the
decimal point, for example, 1 .
5. Press
The display will show the revision letter, as its equivalent number, for
example, 1 = A.
6. Press
The display will flash between Csu and the software checksum value.
7. Press
The display returns to the reservoir fluid temperature.
- 41 -
Page 43
Blank Page.
Page 44
Appendix A Fluids
Water Quality Standard and Recommendations
Microbiologicals
(algae, bacteria, fungi)00
Inorganic Chemicals
Calcium<25<0.6
Chloride<25<10
Magnesium<12 <0.1
Sulfate<25<1
Total Hardness<17<0.05
Unfavorably high total ionized solids (TIS) can accelerate the rate of galvanic
corrosion. These contaminants can function as electrolytes which increase the
potential for galvanic cell corrosion and lead to localized corrosion such as
pitting which can be observed at the studs and on the outside surface of
cooling coils. Eventually, the pitting will become so extensive that the coil will
leak refrigerant into the water reservoir.
Permissible (PPM)Desirable (PPM)
For example, tap water in the U.S. averages 171 ppm (of NaCl). The recommended level for use in a water system is between 0.5 to 5.0 ppm (of NaCl).
Recommendation: Initially fill the tank with distilled/deionized water. Do not use
untreated tap water as the total ionized solids level may be too high.
Maintain this water quality at a resistivity of between 1 to 10 megohm-cm
(compensated to 25°C) by using a purification system. Although the initial fill
may be as high as 18 megohm-cm (compensated to 25°C), the desired level
for long time usage is 1 to 3 megohm-cm (compensated to 25°C).
The above two recommendations will reduce the electrolytic potential of the
water and prevent or reduce the galvanic corrosion observed.
Appendix A
A -1
Page 45
RTE Compatibility with
Recommended Fluids
Filtered/Singled Distilled water
This fluid is recommended primarily because it has all microorganisms that cause biological fouling
removed through vaporizing and condensing the water. However, distilled water does not remain pure
for very long when exposed to the atmosphere. Air-born spores can contaminate the water and
activate alga growth. Chloramine-T is a compatible algaecide that can be used to combat growth but a
more effective maintenance plan would include switching out the fluid with newly distilled water every
six month. The particulates that have been filtered out in the process are also preventative in keeping
the system “clean” of contaminants. One thing to note is that distilling water that contains an additive
could increase the concentration of that additive in the water.
50/50 Uninhibited Ethylene Glycol/Water
Ethylene glycol is used to depress the freezing point of water as a coolant. We recommend not
using the uninhibited (no corrosion additives) above 60°C because it breaks down into acidic byproducts faster at high temperatures. These acidic by-products, especially carbonic acid, are
corrosive to copper. The inhibitors are used to control the corrosion rates by passivating the metal
surfaces with an inert film. Uninhibited ethylene is more corrosive to copper that plain water so
therefore it is not recommended unless it is required for the application.
50/50 Inhibited Ethylene Glycol/ Water
Inhibited glycol can be used to increase the operating temperature range of the fluid but should not
be used as a “pre-mixed anticorrosive” solution. Again, this fluid does break down over time at high
temperatures. Dow uses a pH standard of 8 to base when the fluid has become corrosive.
Dowtherm is an ethylene based product that contains dipotassium phosphates in a 4% concentration. The recommended use of Dowtherm is mixing with distilled or deionized water or water that
contains less than 25 ppm chloride and sulfate and less than 100 ppm total hardness of CACO3.
The general term, inhibited glycol/water, almost too close to meaning inhibited water. Inhibited
water can have many types of additives including chromate that will foul our cooling system very
quickly.
Appendix A
50/50 Uninhibited Propylene Glycol/ Water
Although the use of this glycol similar to ethylene glycol, propylene glycol is considered “safe” to
use in the food industry. Propylene is less dense than ethylene and therefore will have a tendency to weep more through mechanical seals.
50/50 Inhibited Propylene Glycol/ Water
Same issues as with uninhibited propylene and uninhibited ethylene glycol.
Deionized water (1-3 megohm, compensated)
This water has the ions controlled so that they will not conduct and cause galvanic corrosion
between dissimilar metals. Deionized water is aggressive to metal when it is too pure since this
is not the normal state of water. The leaching of metallic ions from the metal surface is seen in
pitting.
NEVER use flammable or corrosive fluids with this unit. Do not use automotive antifreeze. Commercial antifreeze contains silicates that can damage the unit. Use of
automotive antifreeze may void the manufacturer’s warranty.
A -2
Page 46
Appendix B NC Serial Communications Protocol
(Digital Plus Only)
9-pin female
NOTE: This appendix assumes you have a basic understanding of serial
communications protocols.
All data is sent and received in binary form, do not use ASCII. In the following
pages the binary data is represented in hexadecimal (hex) format.
The NC Serial Communications Protocol is based on a master-slave model.
The master is a host computer, while the slave is the bath's controller. Only
the master can initiate a communications transaction (half-duplex). The bath
ends the transaction by responding to the master’s query. The protocol uses
either an RS-232 or RS-485 serial interface with the default parameters: 19200
baud, 1 start bit, 8 data bits, 1 stop bit, no parity, and for RS-485 a selectable
address from 1 to 100.
NOTE: Before the unit will communicate, serial communication must be turned
on using the controller's Computer button.
The unit can be controlled through your computer’s serial port by using the
unit's standard female 9-pin connections.
To connect the bath to your computer, a M/F 9 pin D-Subminiature extension
cable will be required. See page 31 for cables available from Thermo.
All commands must be entered in the exact format shown in the tables on the
following pages. The tables on the last page of this Appendix show all commands available, their format and responses. Controller responses are either
the requested data or an error message. The controller response must be
received before the host sends the next command.
The host sends a command embedded in a single communications packet,
then waits for the controller’s response. If the command is not understood or
the checksums do not agree, the controller responds with an error command.
Otherwise, the controller responds with the requested data. If the controller
fails to respond within 1 second, the host should re-send the command.
During RS-485 operation the bath will wait at least 5 milliseconds after receiving the checksum byte before asserting its transmitter for the purpose of
replying to the host. Therefore, when the host is done sending a command, it
must disable its transmitter in less than 5 milliseconds. When the bath is done
sending its reply, it will disable its transmitter in less than 5 milliseconds.
B -1
Appendix B
Page 47
NC Serial Communications Protocol
NOTE: All byte values are shown in hex, hex represents the binary values that must be sent to the bath. Do not
use ASCII.
The framing of the communications packet in both directions is:
Checksum region
Lead charAddr-MSBAddr-LSBCommandn d-bytesd-byte 1...d-byte nChecksum
CA or CC 00
Lead charRS-232 = CA (hex) RS-485 = CC (hex).
Device address is 1 - 64 hex (1 - 100 decimal)
Addr-msbMost significant byte of device address is 00 hex.
Addr-lsbLeast significant byte of device address is 01 - 64 hex (1 - 100 decimal) for
RS-485, 01 for RS-232.
CommandCommand byte (see Table 1).
n d-bytesNumber of data bytes to follow (00 to 08 hex).
d-byte 11st data byte (the qualifier byte is considered a data byte).
......
d-byte nnth data byte.
ChecksumBitwise inversion of the 1 byte sum of bytes beginning with the most signifi-
cant address byte and ending with the byte preceding the checksum. (To
perform a bitwise inversion, "exclusive OR" the one byte sum with FF hex.)
The master requests information by sending one of the Read Functions as shown in Table 1 on page B-4. Since
no data is sent to the bath during a read request, the master uses 00 for the number of data bytes following the
command byte.
The bath will respond to a Read Function by echoing the lead character, address, and command byte, followed
by the requested data and checksum. When the bath sends data, a qualifier byte is sent first, followed by a two
byte signed integer (16 bit, MSB sent first). The qualifier byte indicates the precision and units of measure for
the requested data as detailed in Table 2.
As an RS-232 example, the master requests to read internal temperature by sending:
command byte
CA 00 01 20 00 DE
0 bytes of data
If the temperature is 62.5°C, the bath would reply:
Appendix B
command byte
The checksum is the bitwise inversion of 21
(00+01+20+00) = 21
byte values are in hex
The qualifier byte of 11 indicates a precision of 1
decimal point and units of °C. The temperature of
62.5°C is 625 decimal = 271 hex.
CA 00 01 20 03 11 02 71 57
3 bytes to follow
The checksum is the bitwise inversion of CB
(00+01+20+03+11+FF+97) = 1CB
Take the LSB = CB
B - 2
Page 48
The master sets parameters in the bath by sending one of the Set Functions as shown in Table 1. The master
does not send a qualifier byte in the data field. The master should be pre-programmed to send the correct
precision and units (it could also read the parameter of interest first to decode the correct precision and units
needed).
As an RS-485 example, if the master wants to set the setpoint to 30°C, it would send :
command byte
The checksum is the bitwise inversion of 22
(00+03+F0+02+01+2C) = 122
Take the LSB = 22
CC 00 03 F0 02 01 2C DD
The bath responds:
2 bytes to follow
command byte
The temperature of 30.0°C is 300 decimal = 012C hex.
The qualifier byte of 11 indicates a precision of 1
decimal point and units of °C. The temperature of
30.0°C is 300 decimal = 012C hex.
CC 00 03 F0 03 11 01 2C CB
3 bytes to follow
The checksum is the bitwise inversion of 34
(00+03+F0+03+11+01+2C) = 134
Take the LSB = 34
B - 3
Appendix B
Page 49
Table 1 (All bytes are in hex)
RS-232. For RS-485 substitute CC for CA as the lead character.
d1 = unit on/off, d2 = sensor enable, d3 = faults enabled, d4 = mute,
d5 = auto restart, d6 = 0.01°C enable, d7 = full range cool enable,
d8 = serial comm enable (di: 0 = off, 1 = on, 2 = no change)
For example, to turn the unit on send CA 00 01 81 08 01 02 02 02 02 02 02 02 cs
BATH ERROR RESPONSES
Bad CommandN/ACA 00 01 0F 02 01 ed cs
Bad ChecksumN/ACA 00 01 0F 02 03 ed cs
Appendix B
command bytes shown in bolded = echo back of the command byte as received
qb = qualifier byte, see Table 3v1,v2 = protocol version
d1,d2 = 16 bit signed integer of the value being sent or received* See Read Status, Table 2
cs = the checksum of the string (see text)** limited to the range of the bath
**LED bits in REQ STATUS1 byte d5
LED StateLED FlashingLED On
OFF00
ON01
FLASHING11
Invalid10
b.7 = most significan bit
b.0 = least signifcant bit
Table 3 Qualifier Byte
10 hex0.1 precision, no units of measure
20 hex0.01 precision, no units of measure
11 hex0.1 precision, °C units
21 hex0.01 precision, °C units
Example: The temperature of 45.6 °C would be represented by the qualifier 11 hex, followed by the 2 bytes 01
C8 hex (456 decimal).
Appendix B
B - 5
Page 51
Appendix C International Quick Reference Operating Procedures
Verkorte handleiding
Het apparaat heeft een luchtgekoeld koelsysteem.
De luchtinlaat is aan de voorzijde. De luchtuitlaat is
aan de twee zijkanten en aan de achterzijde. Plaats
het apparaat zo dat de luchtaanvoer niet geblokkeerd
is. Bij onvoldoende luchtdoorstroming zal het
koelvermogen afnemen. In extreme gevallen zal de
compressor uitvallen. Een minimale afstand van 12
inches (30 centimeter) aan de voor- en achterkant
van de unit is noodzakelijk voor een goede ventilatie.
Wanneer u wilt circuleren naar een extern systeem,
dient u altijd extra vloeistof achter de hand te houden
om het juiste vloeistofniveau, zowel in het interne als
het externe gedeelte van het systeem, te handhaven.
Gebruik het apparaat nooit wanneer het reservoir leeg
is.
Het apparaat is voorzien van een afvoer, welke
bevestigd is aan de achterkant van het apparaat.
Plaats het apparaat niet in stoffige, corrosieve en/of
vochtige ruimtes. Maak het apparaat regelmatig
schoon. Voor een goede werking moet het apparaat
voldoende lucht door de condensor laten stromen.
Een ophoping van stof of andere deeltjes zullen het
koelvermogen nadelig beïnvloeden. Het apparaat zal
de opgegeven specificaties halen tot een
omgevingstemperatuur van ongeveer +77°F(+25°C).
Het voltage moet voldoen aan het opgegeven voltage,
±10%.
De aansluitingen voor de waterslangen zijn gelabeld
en bevinden zich aan de achterzijde. De
aansluitingen zijn naar boven gericht, zodat de
recirculatievloeistof terug in het reservoir stroomt als
de slangen afgekoppeld zijn. Beide connectoren zijn
van roestvrijstaal. De aansluitingen zijn ¼ inch FPT
zodat er standaard aansluitmateriaal gebruikt kan
worden. Voor uw gemak zijn er slangpilaren
bijgesloten.
De slangaansluitingen zijn bevestigd aan de
achterkant van het apparaat en zijn voorzien van het
label en . Deze roestvrijstalen
aansluitingen kunnen aangesloten worden op een 3/8
inch ID flexibele slang. Verwijder de roestvrijstalen
schroefdoppen, indien externe circulatie gewenst is.
Bevestig de aan de ingang van uw applicatie.
Bevestig de aan de uitgang van uw applicatie.
Vul nu het reservoir tot het volgende niveau: tussen
de horizontale markeringen op de roestvrijstalen
scheidingsplaat, die de werkruimte van het
pompgedeelte scheidt.
Gebruik nooit brandbare of andere koelvloeistoffen die
het toestel kunnen beschadigen. De vloeistof die u
gaat gebruiken moet een viscositeit hebben van 50
centistokes of minder bij lage temperatuur werking.
Kraanwater wordt in het algemeen aanbevolen
wanneer u bij temperaturen werkt van +8°C tot
+80°C.
Operationeel gebruik
Alvorens het apparaat in gebruik te nemen, dient u
eerst alle elektrische- en slangaansluitingen te
controleren. Tevens dient u te controleren of het
systeem gevuld is met koelvloeistof.
Om het apparaat te starten druk op . Om het
apparaat uit te schakelen druk nogmaals op .
Temperatuur Instelling
Druk op om de ingestelde temperatuur te zien. De
indicator licht op en de ingestelde waarde knippert.
Druk op de knop met het pijltje totdat de gewenste
temperatuur is ingesteld. Druk nogmaals op om de
wijziging te bevestigen. De display knippert enkele
malen snel en zal dan weer de actuele temperatuur
laten zien.
Periodiek onderhoud
Controleer regelmatig de vloeistof. Als de vloeistof
ververst moet worden handel dan als volgt: Laat de
vloeistof uit het apparaat lopen. Aan de achterzijde van
het apparaat bevindt zich een afvoerkraantje.
Spoel het reservoir door met een spoelvloeistof die
geschikt is voor het apparaat en de koelvloeistof.
Het is noodzakelijk om de ribben van de condensor
regelmatig schoon te maken met behulp van een
stofzuiger.
Check de condensor maandelijks. Na enige maanden
kunt u de frequentie van het schoonmaken bepalen.
C-1
Page 52
WARRANTY
Thermo Electron Corporation warrants for 24 months from date of shipment any Thermo unit according to the
following terms.
Any part of the unit manufactured or supplied by Thermo and found in the reasonable judgment of Thermo to be
defective in material or workmanship will be repaired at an authorized Thermo Repair Depot without charge for
parts or labor. The unit, including any defective part must be returned to an authorized Thermo Repair Depot
within the warranty period. The expense of returning the unit to the authorized Thermo Repair Depot for warranty
service will be paid for by the buyer. Thermo's responsibility in respect to warranty claims is limited to performing
the required repairs or replacements, and no claim of breach of warranty shall be cause for cancellation or
recision of the contract of sales of any unit. With respect to units that qualify for field service repairs, Thermo’s
responsibility is limited to the component parts necessary for the repair and the labor that is required on site to
perform the repair. Any travel labor or mileage charges are the financial responsibility of the buyer.
The buyer shall be responsible for any evaluation or warranty service call (including labor charges) if no defects
are found with the Thermo product.
This warranty does not cover any unit that has been subject to misuse, neglect, or accident. This warranty does
not apply to any damage to the unit that is the result of improper installation or maintenance, or to any unit that
has been operated or maintained in any way contrary to the operating or maintenance instructions specified in
Thermo’s Instruction and Operation Manual. This warranty does not cover any unit that has been altered or
modified so as to change its intended use.
In addition, this warranty does not extend to repairs made by the use of parts, accessories, or fluids which are
either incompatible with the unit or adversely affect its operation, performance, or durability.
Thermo reserves the right to change or improve the design of any unit without assuming any obligation to modify
any unit previously manufactured.
THE FOREGOING EXPRESS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR
IMPLIED, INCLUDING BUT NOT LIMITED TO WARRANTIES OR MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE.
Thermo's OBLIGATION UNDER THIS WARRANTY IS STRICTLY AND EXCLUSIVELY LIMITED TO THE REPAIR OR REPLACEMENT OF DEFECTIVE COMPONENT PARTS AND Thermo DOES NOT ASSUME OR
AUTHORIZE ANYONE TO ASSUME FOR IT ANY OTHER OBLIGATION.
Thermo ASSUMES NO RESPONSIBILITY FOR INCIDENTAL, CONSEQUENTIAL, OR OTHER DAMAGES
INCLUDING, BUT NOT LIMITED TO LOSS OR DAMAGE TO PROPERTY, LOSS OF PROFITS OR REVENUE,
LOSS OF THE UNIT, LOSS OF TIME, OR INCONVENIENCE.
This warranty applies to units sold in the United States. Any units sold elsewhere are warranted by the affiliated
marketing company of Thermo. This warranty and all matters arising pursuant to it shall be governed by the law of
the State of New Hampshire, United States. All legal actions brought in relation hereto shall be filed in the appropriate state or federal courts in New Hampshire, unless waived by Thermo.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.