Thermador HPWB30FS Installation Manual

INSTALLATION MANUAL
MODELS: HPWB30
HPWB36 HPWB48
LI3FEA Ed.04/08
APPROVED FOR RESIDENTIAL APPLIANCES
FOR RESIDENTIAL USE ONLY
READ AND SAVE THESE INSTRUCTIONS
PLEASE READ ENTIRE INSTRUCTIONS BEFORE PROCEEDING. INSTALLATION MUST COMPLY WITH ALL LOCAL CODES. IMPORTANT: Save these Instructions for the Local Electrical Inspector’s use. INSTALLER: Please leave these Instructions with this unit for the owner. OWNER: Please retain these instructions for future reference. Safety Warning: Turn off power circuit at service panel and lock out panel, before wiring this appliance. Requirement: 120 V AC, 60 Hz. 15 or 20 A Branch Circuit
2
IMPORTANT SAFETY INSTRUCTIONS
Read All Instructions Before Using theAppliance.
READ AND SAVE THESE INSTRUCTIONS
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING: A. Use this unit only in the manner intended by the
manufacturer. If you have questions, contact the manufacturer.
B. Beforeservicing or cleaning the unit, switch
power off at service panel and lock service panel disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warningdevice, such as a tag, to the service panel.
C. Installation Work and Electrical Wiring Must Be
Done By Qualified Person(s) In Accordance With All ApplicableCodes & Standards, Including Fire-ratedConstruction.
D. Sufficient air is needed for proper combustion
and exhausting of gases through the flue (chimney) of fuel burning equipment to prevent back- drafting. Follow the heating equipment manufacturers guideline and safety standards such as those published by the National Fire Protection Association (NFPA), the American Society for Heating, Refrigeration and Air Conditioning Engineers(ASHRAE), and the local code authorities.
E. When cutting or drilling into wall or ceiling, do
not damage electrical wiring and other hidden utilities.
F. Ducted systems must always bevented to the
outdoors.
CAUTION FOR GENERAL VENTILATING USE ONLY. DO NOT USE TO EXHAUST HAZARDOUS OR EXPLOSIVE MATERIALS OR VAPORS.
CAUTION To reduce risk of fire and to properly exhaust air, be sure to duct air outside - do not vent exhaust air into spaces within walls, ceilings, attics, crawl spaces,
WARNING TO REDUCE THE RISK OF FIRE, USE ONLY METAL DUCT WORK.
Install this hood in accordance with all requirements specified.
WARNING
To Reduce The Risk of Fire or Electric Shock, Do Not Use This Hood With Any External Solid State Speed Control Device.
OPERATION a. Always leave safety grills and filters in place.
Without these components, operating blowers could catch onto hair, fingers and loose clothing.
The manufacturer declines all responsibility in the event of failure to observe the instructions given here for installation, maintenance and suitable use of the product. The manufacturer further declines all responsibility for injury due to negligence and the warranty of the unit automatically expires due to improper maintenance.
or garages.
This unit is manufactured for indoor use only. Do not use this unit outdoors.
3
IMPORTANT SAFETY INSTRUCTIONS
Read All Instructions Before Using theAppliance.
READ AND SAVE THESE INSTRUCTIONS
Electrical requirements
IMPORTANT
Observe all governing codes and ordinances.
It is the customer’s responsibility: To contact a qualied electrical installer. To assure that the electrical installation is adequat e and in conformance with National Electrical Code, ANSI/NFPA 70 — latest edition*, or CSA Standards C22.1-94, Canadian Electrical Code, Part 1 and C22.2 No.0-M91 - latest edition** and all local codes and ordinances.
If codes permit and a separate ground wire is used, it is recommended that a qualied electrician determine that the ground path is adequate.
Do not ground to a gas pipe. Check with a qualied electrician if you a re not sur e range hood is properly grounded. Do not have a fuse in the neutral or ground circuit.
IMPORTANT
Save I nstallation Instructions for e lectrical inspector’s use.
The range hood must be connected with copper wire only.
The range hood should be connected directly to the fused disconnect ( or circuit breaker) box through metal electrical conduit.
Wire sizes must conform to the requirements of the National Electrical Code ANSI/NFPA 70 — latest edition*, or CSA Standards C22.1-94, Canadian Electrical Code Part 1 and C22.2 No. 0-M91 - latest edition** and all local codes and ordinances.
A U.L. - or C.S.A.- listed conduit connector must be provided at each end of the power supply conduit (at the range hood and at the junction box) .
Copies o f the standards listed may be obtained from:
* National Fire Protection Association Batterymarch Park Quincy, Massachusetts 02269
** CSA International 8501 East Pleasant Valley Road Cleveland, Ohio 44131-5575
4
Parts Included with your Hood
CAUTION: Vent unit to outside o f
building, only.
Two people are necessary for installation.
On average 2 hours are necessary to complete installation (without considering cut to be done on wall and o r on cabinet, installation of ducts , conduit and electrical connections to the mains) .
installation steps:
11 installation steps are required for both installation methods Wall mount installation steps or in a lternative Cabinet installation
The hood is tted with Screws and Drywal l
Anchors suitable for most surfaces, consult a Qualied Installer, check if they perfectly f it with your cabinet/wall.
Do not use ex ducting.
COLD WEATHER installations should have an
additional backdraft damper i nstalled to minimize backward cold air ow and a nonmetallic thermal break to minimize conduction of outside temperatures as part of the ductwork. The damper should be on the cold air side of the thermal break. The break should be as close as possible to where the ducting enters the heated portion of the house.
Make upair: Local building codes may require
the use of M ake-Up Air Systems when using Ducted Ventilation Systems greater t han specied CFM of a ir movement. The specied CFM varies from location to location. Consult your HVAC professional f or specic requirements in your area.
Hood Canopy Assembly with blower already installed
Grease lters
Drip tray for each lter.
Drip trays holding brakets + plastic wahers and knobs
1 Transition with back dra ft damper
Use & Care / Installation Instructions
Fittings bag with: 4 W ashers
6 Drywall anchors 2 Hooks with regulating screws 6 S crews 5X35 4 Screws for transition
Optional accessory
Duct cover s Ductless recirculation kit available only for HPWB30 model.
Parts Not Included with your Hood
Duct Tape
1/2" Conduit
Wire Nuts
Round Duct.
Wiring clamp
4 #10 pan head wood screws for installation on
3 prong plug
CAUTION! Lamps are not supplied, use ONLY 120 Volt, 50 Watt (maximum) 50°
halogen light made o r a GU10 base, suitable for use in open luminarie.
a bottom of a cabinet
Tools required
Flat blade and Phillips screwdrivers Pencil and tape measure Metal snips (in some applications) Electric drill Saw (saber or keyhole) Pliers Level Caulking F lashlight Wire s
tripper Safety glasses Gloves Step ladder
For the most ecient air f low exhaust, use a
straight run or as few elbows as possible.
INSTALLING THE HOOD
5
Typical installation
The height from the countertop to the bottom of the hood is 30” to 36”. These hoods are not recommended to be used over indoor grills.
1. Choose vent options
The hood is designed to be used for vertical discharge as shown below. Note: see also Fig. 1-2-3 for Cabinet preparation.
Install a 1/2” conduit from the service panel long enough to reach the hood once it is installed. Power supply must be rated for 120 VAC, 60Hz. 15 or 20 A.
Examples of possible ducting
Ceiling
*Deector
Lamp
Hood
30” to 36”
RECIRCULATING
Transition
Blower
*Charcoal lters
Filter
Round duct
Ceiling
Lamp
Hood
30” to 36”
VERTICAL DISCHARGE
Transition
Blower
Filter
* Charcoal lters
* Optional accessory - Ductless recirculation kit * Only for 30” model
6
Table 1. Ventilator performance calculation
eceiPtcuD
Use this chart to compute maximum permissable lengths for duct runs to outdoors.
Do not exceed maximum permissable
Note:
equivalent lengths!
Maximum recommended duct length for these hoods: 150 feet
Flexible ducting:
If exible metal ducting is used, all the equivalent f eet values in the table should be doubled. The flexible metal duct shou ld be straight and smooth and extend ed as much as possible.
Do NOT use exible plastic ducting
Any home ventilation system, such as a
Note:
gas furnaces, gas water heaters and other naturally vented systems. To minimize the chance of interruption of such naturally vented systems, follow the heating equipment manufacturer’s guidelines and safety standards such as those published by NFPA and ASHRAE.
.
*Hoods are supplied with a 10"
round transition. A locally supplied transition is required for other sizes.
Outlet on top of hood is
Note:
8-1/8" x 8".
10" roun d to 8" roun d 5 ft.
Round , 1 ft. straight (per foot
length)
3-1/4" x 10" 1 ft. 3-1/4" x 12 " (p er f oot straight length)
8" Dia. 17 ft.
90° elbow 10" Dia. 24 ft .
8" Dia. 10 ft.
45° elbow 10" Dia. 14 ft .
3 -1⁄4" x 12" 15 ft. 3-1/4" x 10" 14 ft. 90° elbow
3-1/4" x 10 " 8 ft. 3-1/4" x 12 " 9 ft. 45° elbow
3-1/4" x 10" 33 ft. 3-1/4" x 12" 36 ft. 90° at elbow
10"round transition to 3-1/4" x 10" or 3-1/ 4" x 12" 9 ft.
3-1/4" x 10" or 3-1/4" x 12" to 10" round transiti on 6 ft.
10" round to 3-1/4" x 10" 16 ft. 3-1/4" x 12" transition 13 ft. 90° elbow
3-1/4" x 10 " 9 ft. 3-1/4" x 12" t o 10" r ound 8 ft. transiti on 90° elbow
Roun d 8" Dia. 32 ft. wall c ap 10" Dia. 41 ft. wi th d a m p er
3-1/4" x 10" 24 ft. 3-1/4" x 12" wall cap 26 ft. wi th d a m p er
Round 8" Dia. 44 ft. roof cap 10" Di a. 56 ft .
7
To t a l D u c t R u n
TABLE 2. DUCTWORK INSTALLATION GUIDELINES
For safety reasons, ducting should vent directly outdoors (not into an attic, underneath the house, into the garage or into any enclosed space). Keep duct runs as short and straight as possible. Duct ttings (elbows and transitions) reduce air ow efciency. Back to back elbows and „S“ turns give very poor delivery and are not recommended. A short straight length of duct at the inlet of the remote blower gives the best delivery. Transition to duct from the integral blower to remote duct transition as close as possible.
In order opreference, use:
1st. 10” round duct 2nd. 8round duct 3rd. 3-1/4” x 14” duct 4th. 7” round duct 5th. 3-1/4” x l0” duct 6th. 6” round duct
The use of exible metal round duct should only be used when no other duct tting exists. Limit use to short lengths
1. Prepare duct and conduit cut outs, see gures 1 and 2 as needed.
and do not crush when making corners.
Assembly of the 10” transition:
2. The transition supplied with the hood mounts to the top.
Figure 1
10-1/2
Model
X
30”
2-3/4”
36”
4-9/16”
48”
10-9/16”
Do not install transition until hood is xed on cabinet or wall.
a. Place the transition piece over the hood
outlet and secure with 4 screws provided.
X
22
(Figure3)
b. Wrap all joints (metal transition and hood)
with duct tape for an airtight seal.
c. Remove tape holding damper.
5- 7/8”
Hood outlet
Figure 3
Figure 2
Transition
23-1/8”
Screws (4)
8
Loading...
+ 18 hidden pages