Thermador HNI, HTNI Installation Instructions

®
INSTALLATION INSTRUCTIONS
ISLAND HOOD SERIES: HNI, HTNI
FOR RESIDENTIAL USE ONLY
PLEASE READ ENTIRE INSTRUCTIONS BEFORE PROCEEDING.
INSTALLATION MUST COMPLY WITH ALL LOCAL CODES.
INSTALLER: Please leave these Instructions with this unit for the owner.
OWNER: Please retain these instructions for future reference.
INSTALLATION:  Requires remote blower model VTR1000Q or VTR1400Q.
 Requires Transition from 8 duct at hood to 10 duct at remote blower
 Requires 5-wire installation from remote blower to hood.
 Power supply required: 120V, 60Hz, 15A min
IMPORTANT SAFETY INSTRUCTIONS
WARNING - TO REDUCE THE RISK
OF FIRE, ELECTRIC SHOCK, OR
INJURY TO PERSONS, OBSERVE
THE FOLLOWING:
CAUTION: FOR GENERAL VENTI-
LATING USE ONLY. DO NOT USE
TO EXHAUST HAZARDOUS OR
EXPLOSIVE MATERIALS OR
VAPORS.
A. Use this unit only in the manner
intended by the manufacturer. If you
have questions, contact the manufac-
turer.
B. Before servicing or cleaning unit, switch
power off at service panel and lock the
service disconnecting means to prevent
power from being switched on
accidentally. When the service
disconnecting means cannot be locked,
securely fasten a prominent warning
device, such as a tag, to the service
panel.
C. Installation work and electrical wiring
must be done by qualified person(s) in
accordance with all applicable codes &
standards, including fire-rated
construction.
D. Sufficient air is needed for proper
combustion and exhausting of gases
through the flue (chimney) of fuel
burning equipment to prevent back
drafting. Follow the heating equipment
manufacturers guideline and safety
standards such as those published by the
National Fire Protection Association
(NFPA), and the American Society for
Heating, Refrigeration and Air Condi-
tioning Engineers (ASHRAE), and the
local code authorities.
E. Due to size and weight of this unit two
installers are recommended.
F. When cutting or drilling into wall or
ceiling, do not damage electrical wiring
and other hidden utilities.
G. CAUTION - To reduce risk of fire and
to properly exhaust air, be sure to duct
air outside. Do not vent exhaust air
into spaces within walls, ceilings, attics,
crawl, spaces or garages.
H. Install this hood in accordance with all
requirements specified by the manufac-
turer of your cooktop/range.
I. WARNING - TO
REDUCE THE
RISK OF FIRE,
USE ONLY
METAL DUCT
WORK.
FILE # E21958
READ AND SAVE THESE INSTRUCTIONS
Page 1
LI1LKA
LES INSTRUCTIONS DE SÉCURITÉ IMPORTANTES
Avertissement de Sécurité:
Avant l' entretien ou le nettoyage de l'appareil, couper le courant au tableau de service, et fermer à clef la moyenne de débrayage de service pour empêcher l'alimentation d' être allumée par hasard. Quand la moyenne de débrayage de service ne peut pas être fermée à clef, attacher une étiquette au tableau de service pour indiquer que l' alimen
AVERTISSEMENT - POUR RÉDUIRE LE RISQUE
D’INCENDIE, DE CHOC ÉLECTRIQUE, OU DE LA BLESSURE AUX PERSONNES, OBSERVER LE SUIVANT:
ATTENTION: SEULEMENT POUR L’UTILISATION D’AÉRATION. NE PAS L’UTILISER POUR ÉPUISER LA VAPEUR OU LES MATIÈRES EXPLOSIVES OU DANGEREUSES.
A. Utiliser cet appareil seulement
dans la manière destinée par le fabricant. Si vous avez des questions, contacter le fabricant.
B. Avant l’installation, l’entretien
ou le nettoyage de l’appareil, couper le courant au tableau de service, et fermer à clef le tableau de service pour empêcher l’alimentation d’être allumée par hasard.
D. L’écoulement comburant pour
le fonctionnement sûr du matériel de la combustion du combustible peut être affecté par le fonctionne- ment de cet appareil. Suivre la directive des fabricants du matériel chauffant et les normes de sécurité tel que ceux publiées par l’Association du Protection de Feu National (NFPA), et la Société Américaine pour les Ingénieurs de Chauffage, de Réfrigération et de Climatisation (ASHRAE), et les autorités des codes locales.
E. Par suite de la dimension et le
poids de cet appareil, deux installateurs sont recommandés.
F. En coupant ou en forant dans
un mur ou dans un plafond, ne pas endommager le câblage électrique et des autres utilités cachées.
G. Les ventilateurs canalisés
doivent être toujours déchargés à l’extérieur et vers le haut. Ne pas décharger au grenier ou au vide sanitaire.
H. Installer ce capot conformé-
ment aux toutes exigences spécifiées par le fabricant de votre cooktop/cuisinière.
C. Le Travail d’Installation et de
Câblage Électrique Doit Être Fait Par les Personne(s) Qualifiées
Page 2
W
TT
B*
H
B*
H
T
A
OO
OO
T
D
W
A
D
Page 3
HTNI
HNI
*B See Page 5, Fig. A
Table 1
HEIGHT
H
Min. to Max.
33 - 47
33 - 47
33 - 47
33 - 49
33 - 49
33 - 49
MODEL #
HTNI42
HTNI48
HTNI54
HNI42
HNI48
HNI54
CARTON
WEIGHT
Pounds
108,7
112,5
128,7
87,8
99,6
117,6
* Transition from 8 to 10 round required to connect to remote ventilator.
CANOPY HT
A
15-3/4
15-3/4
15-3/4
11-1/2
11-1/2
11-1/2
TRANSITION HT
T
18-3/4
18-3/4
18-3/4
16-5/8
16-5/8
16-5/8
WIDTH
W
42
48
54
42
48
54
DEPTH
D
35-7/16
35-7/16
35-7/16
27
27
27
DUCT
SIZE *
(Inches)
8
8
8
8
8
8
LIGHTS
#OF Total
Watts
4 80W
4 80W
4 80W
2 18W
2 18W
2 18W
Parts Included with your Hood
Hood Canopy Assembly with Light
Bulbs Installed
Care & Use /Installation Instruc-
tions
Parts Not Included with your Hood
Duct Tape
1/2" Conduit
Wire Nuts
Ducting
Registration Card
Filters number depends on model
and size
Metal Transition
Screws
Mounting Template
2 or 3 Piece Duct Cover,
depending on model
Contents Sheet
CONSIDERATIONS BEFORE INSTALLING HOOD
1. For the most efficient air flow
exhaust, use a straight run or as
few elbows as possible.
CAUTION: Vent unit to outside
of building, only.
2. Do not use flex ducting.
3. COLD WEATHER installations
should have an additional
backdraft damper installed to
minimize backward cold air flow
and a nonmetallic thermal break
to minimize conduction of outside
temperatures as part of the
ductwork. The damper should be
on the cold air side of the thermal
break. The break should be as
close as possible to where the
ducting enters the heated portion
of the house.
4. Hood installation height above
cooktop is the users preference
The closer the hood is to the
P.
cooktop the more efficient it will
be in capturing of cooking odors,
grease and smoke. Be sure the
hood model fits your installation.
K = Kitchen Height
C = Counter Height (36" standard)
P = Installation Height of Hood
above countertop
A = Canopy Height ( Table 1)
= Hood Height, your installation
H = K  C  P
Chimney Structure Height, your
B=
installation.
=H  A
B
H
A
K
P
C (36"std.)
Fig. A
Page 4
PREPARATION OF
MOUNTING SURFACE
1. A) Select a hood installation height P
above the cooktop that is comfortable
for the user.
Thermador recommends a distance of
30-36 between the countertop and
bottom of the hood.
B) Compute the hood height H by
using Fig. A. If the hood height is out
of the range specified in table 1 select
a new installation height P.
C) Calculate chimney structure
height B by using formulas in Fig.
A and dimensions in Table 1.
Note: Take into consideration the
hood depth; some models are
much deeper than the cooktop.
2. Mark center lines of cooktop or
range on ceiling above. Use
centerlines marked on ceiling to
position the mounting template.
Note location of hood front side
and mounting holes indicated on
template.
3. Remove and save template. Cut and
remove ceiling drywall. Install suitable
length 2" x 4" lumber between joists
to provide chimney mounting points
as shown in Fig. C and D. Use
template for dimensions and required
clearance.
HTDI
Fig. C
Fig. D
Note the weight of the appliance
(see Table 1). Make sure to affix the
added lumber firmly and level. Consult
a professional if you have difficulties
or your installation is unique. Consult
template and Figs. B. C. D.
4. REMOTE VENTILATOR AND DUCT
INSTALLATION. Refer to
instructions shipped with remote
ventilator model VTR1000Q or
VTR1400Q for installation of remote
blower and ducting. The remote
ventilator inlet fits 10 round duct.
Transition down to 8 round for
clearance in the chimney structure
shown in Fig. B. Female end shall be 4-
1/2" below finished ceiling and
securely fastened to joists.
Fig. B
HTNI HNI
Page 5
5. Install wiring for remote ventilator
and power supply. See electrical
Installation on page 9.
The conduit for the remote ventilator
and power supply must extend a
distance B (see Fig. A) from the ceiling
to reach the hood junction box.
6. Install drywall around duct and
conduit. Finish drywall surface to
match ceiling.
7. Tape mounting template to ceiling
using centerlines for alignment.
Appliance Installation: (Note:
three people may be required for
proper installation of HTNI, two
people for the HNI).
1. Install transition to top of hood
(if removed for shipping).
2. Adjust chimney mounting
structure to B dimension as
determined in Step 1, page 5.
Use 2 screws per attachment
leg. For HTNI
use a minimum
of 12 screws. See Fig. B. Do not
fasten to ceiling now.
3. Set chimney mounting structure
on top of hood canopy. Attach
nuts loosely. See Fig. F and G.
4. Fit duct piece on transition so
that top end is 5-1/2" below top
of chimney structure, male end
up.
5. Remove chimney structure from
hood canopy.
6. Install Ducting. For HNI
hoods fasten duct to transition
with screws and tape per code.
Loosely fasten starter collar
(included) flush to top of duct.
Fig. E
Fig. G
Fig. F
Fig. H
7. To install Chimney
Structure to
ceiling, use a
10mm or adjustable wrench or
flat head screwdriver. Drill
holes into ceiling. Attach
mounting structure to joists with
lag screws provided. (Keep
the 4
conduit inside structure.) See
1/2"
Fig. B.
8. Remove Chimney Cover's
plastic protective film.
Reassemble and fasten all 3
covers together with one
vertical screw. See Fig. E. Slide
over chimney structure and
secure with 2 screws near
ceiling.
9. To fasten the canopy use a
10mm or adjustable wrench.
Attach nuts (with washers on
HTNI) to top of canopy .
pilot
For HTNI hoods fasten duct to
ceiling with screws and tape per
code. Loosely fasten starter
collar (included) flush to bottom
of duct.
Page 6
Do not tighten. Raise canopy
up to chimney structure and
twist in place. See Fig. G.
Tighten nuts securely.
10. Ducting for all units: There
should be no more than 1" gap
between canopy ducting and
house ducting. Adjust starting
collar over both ducts. Tighten
collar. Fasten duct with screws
and tape per code. Make final
angular adjustment to unit at
ceiling if necessary, then securely
tighten 4 ceiling lag screws if not
already tightened. Chimney
cover must be lowered to do
this.
Gently slide the outer and
middle covers down and set on
canopy. Raise the middle cover,
align holes with lower cover and
insert pin or wire to temporarily
hold up. Fasten covers together
using 2 screws provided.
NOTE: Do not overtighten and
deform metal.
In model HTNI, if the hood
installation height H is less than
36-3/4", the middle cover will
not be raised. Instead the
middle cover is located behind
the bottom cover and no hori-
zontal screws are used.
11. To connect conduit and
wiring see Wiring section on
page 9. Then replace J-box
cover.
12. For final Chimney Cover
installation, DO NOT USE
ELECTRIC SCREW
DRIVER. Raise chimney covers
and fasten in place with 2 screws
if not already fastened. Fig. E.
Remove one vertical screw
holding covers together. See Fig.
H.
Fig. I
13. In model HTNI fasten lower
chimney cover to canopy from
inside the hood with 8 screws
included. See Fig. I.
Page 7
ELECTRICAL INSTALLATION
Warning: Switch power off at service
panel and lock the service
disconnecting means before wiring
this unit.
Wiring Remote Ventilator
VTR1000Q or VTR1400Q:
1. Run five wires #14 AWG (black,
white, blue, red, and green) in 1/
2 conduit from the remote
ventilator to the hood.
2. Install conduit connector at the
end of the conduit. Remove the
knockout on top of the junction
box. Attach conduit connector
to the junction box.
3. Use the four wire bundle and
ground wire in the junction box
for connecting to the remote
ventilator wires. Connect black
wire from the remote ventilator
to the black wire in the junction
box, red to red, blue to blue,
white to white, and green to
green. Do not connect to the
power supply wire bundle
containing a black and white
wire. See Figure J.
HNI
HTNI
Wiring To Power Supply:
1. Installation requires a 15A
circuit. Run three wires: black,
white, and green using #14
AWG from the service panel to
the junction box.
2. Remove junction box cover as
shown in Figure J.
3. Remove the knockout and install
1
/2 conduit connector.
4. Connect black wire from service
panel to black in junction box,
white to white, and green to
green. See Figure J.
5. Close junction box cover.
Fig. J
Page 8
Loading...