Thermador HMWB36FS/01, HMWB30FS/01 Installation Guide

i ii i ii ii i i
!_i:_i_i_i_ii_i_ii_i_i:_i!ii_ii_I_III_I__i_i_i_iiiii___i__II_I:II_
VENTILATION
INSTALLATION MANUAL
MODELS: HMWB30
HMWB36
Thermedor' AoA=__°o3_°o+
LI3GJA Ed. 08/08
FOR RESiDENTiAL USE ONLY
READ AND SAVE THESE iNSTRUCTiONS
PLEASE READ ENTIRE iNSTRUCTiONS BEFORE PROCEEDING.
iNSTALLATiON MUST COMPLY WiTH ALL LOCAL CODES. IMPORTANT: Save these Instructions for the Local Electrical Inspector's use.
INSTALLER: Please leave these instructions with this unit for the owner.
OWNER: Please retain these instructions for future reference. Safety Warning: Turn off power circuit at service panel and lock out panel, before wiring this appliance.
Requirement: 120 V AC, 60 Hz. 15 or 20 A Branch Circuit
IMPORTANT SAFETY INSTRUCTIONS
Read All Instructions Before Using the Appliance.
READ AND SAVE THESE INSTRUCTIONS
G
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR iNJURY TO PERSONS, OBSERVE
THE FOLLOWING:
A. Use this unit only in the manner intended by the
manufacturer. Ifyou have questions, contact
the manufacturer.
B. Before servicing or cleaning the unit, switch
power off at service panel and lock service panel disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
C. installation Work and Electrical Wiring Must Be
Done By Qualified Person(s) In Accordance With All Applicable Codes & Standards, including Fire-rated Construction.
D. Sufficient air is needed for proper combustion
and exhausting of gases through the flue (chimney) of fuel burning equipment to prevent back- drafting. Follow the heating equipment manufacturers guideline and safety standards such as those published by the National Fire Protection Association (NFPA), the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the
local code authorities.
E. When cutting or drilling into wall or ceiling, do
not damage electrical wiring and other hidden utilities.
F. Ducted systems must always be vented to the
outdoors.
CAUTION FOR GENERAL VENTILATING USE ONLY. DO NOT USE TO EXHAUST HAZARDOUS OR EXPLOSIVE MATERIALS OR VAPORS.
CAUTION To reduce risk of fire and to properly exhaust
air, be sure to duct air outside - do not vent exhaust air into spaces within walls, ceilings, attics, crawl spaces, or garages.
WARNING
TO REDUCE THE RISK OF FIRE, USE ONLY METAL DUCT WORK.
Install this hood in accordance with all requirements specified.
WARNING To Reduce The Risk of Fire or Electric Shock, Do Not Use This Hood With Any External Solid
State Speed Control Device.
OPERATION a. Always leave safety grills and filters in place.
Without these components, operating blowers could catch onto hair, fingers and loose clothing.
The manufacturer declines a II responsibility in the event of failure to observe the instructions given
here for installation, maintenance and suitable use ofthe product. The manufacturer further declines
all responsibility for injury due to negligence and the warranty of the unitautomatically expires due to
improper maintenance.
This unit is manufactured for indoor use only. Do not use this unit outdoors.
IMPORTANT SAFETY INSTRUCTIONS
Read All Instructions Before Using the Appliance.
READ AND SAVE THESE INSTRUCTIONS
Electrical requirements IMPORTANT
Observe all governing codes and ordinances. It is the customer's responsibility:
To contact a qualified electrical installer. To assure thatthe electrical installation is adequate
and in conformance with National Electrical Code, ANSI/NFPA 70 -- latest edition s-,or CSA Standards C22.1-94, Canadian Electrical Code, Part land
C22.2 No.0-M91 - latest edition_-_-and all local codes and ordinances.
If codes permit and a separate ground wire is used, iris recommended that a qualified electrician determine that the ground path is adequate.
Do notground to a gas pipe. Check with a qualified electrician if you are not sure range hood is properly grounded. Do not have a fuse in the neutral or ground circuit.
IMPORTANT
Save Installation Instructions for electrical inspector's use.
The range hood must be connected with copper
wire only.
The range hood should be connected directly to the
fused disconnect (or circuit breaker) box through metal electrical conduit.
Wire sizes must conform to the requirements of the National Electrical Code ANSI/NFPA 70--latest
edition s-,or CSA Standards C22.1-94, Canadian Electrical Code Part 1 and C22.2 No. 0-M91 - latest
edition_-_-and all local codes and ordinances. A U.L. - or C.S.A. - listedconduit connector must be
provided at each end of the power supply conduit (at the range hood and at the junction box).
Copies of the standards listed may be obtained from:
National Fire Protection Association Batterymarch Park
Quincy, Massachusetts 02269
_CSA International 8501 East Pleasant Valley Road Cleveland, Ohio 44131-5575
4
Parts In cluded with your Hood
Hood Canopy Assembly with blower already installed
Grease filters
Drip tray for each filter.
Drip trays holding brakers + plastic wahers and knobs
1Transition withbackdraftdamper
Use & Care / Installation Instructions
Fittings bag with: 4 Washers
6 Drywall anchors 2 Hookswith regulating screws
6 ScrewsSX3S 4 Screws for transition
Op tion al accessory
Duct covers Ductless recirculation kit available only for HMWB30,
HMWB.36 model.
Parts Not Included with your Hood
Duct Tape
1/2"Conduit
Wire Nuts
Round Duct.
Wiring clamp
A CAUTION! Lamps are not supplied, use ONLY 120 Volt, S0 Watt (maximum) S0°
halogen light made o r a GU10 base,
suitable for usei nopen luminarie .
4 #10 pan head wood screws for installation on
a bottomofa cabinet
3 prong plug
Tools required
Flat blade and Phillips screwdrivers Pencil and tape measure Metal snips (in some applications)
Electric drill Saw (saber or keyhole)
Pliers Level
Caulking
Flashlight
Wire stripper
Safety glasses
Gloves
Step ladder
INSTALLING THE HOOD
For the most efficient air flow exhaust, use a straight run or as few elbows as possible.
il_ CAUTION: Vent unittooutsideof
building, only.
Two peopleare necessary for installation. On average 2 hours are necessary to complete
installation (without considering cut to be done on wall and or on cabinet, installation of ducts, conduit and electrical connections to the mains).
installation steps:
11 installation steps are required for both
installation methods Wall mount installation steps or in a Iternative
Cabinet installation
The hood is fittedwith Screws and Drywall Anchors suitable for most surfaces, consult a
Qualified Installer, check if they perfectly fit with your cabinet/wall.
Do not use flex ducting.
COLD WEATHER installations should have an additional backdraft damper installed to
minimize backward cold air flow and a nonmetallic thermal break to minimize
conduction of outside temperatures as part of the ductwork. The damper should be on the
cold air side of the thermal break.
The break should be as close as possible to
where the ducting enters the heated portion of the house.
Make up air: Local building codes may require the use of Make-Up Air Systems when using Ducted Ventilation Systems greater than specified CFM of air movement.
The specified CFM varies from location to location
Consult your HVAC professional for specific requirements in your area.
Typical installation
The height from the countertop to the bottom of the hood is 30" to 36". These hoods are not recommended to be used over indoor grills.
1. Choose vent options
The hood is designed to be used for vertical discharge as shown below.
Note: see also Fig. 1-2-3 for Cabinet preparation.
Install a 1/2" conduit from the service panel long enough to reach the hood once it is installed. Power supply must be rated for 120 VAC, 60Hz. 15 or 20A.
Examples of possible ducting
Ceiling
*Deflector
Lamp
\
Hood
1
30" to 36"
Transition
Blower
*Charcoal filters
Filter
Round duct
Ceiling
Lam p
Hood
30" to 36"
1
Transition
Blower
Filter
* Charcoal filters
Optional accessory - Ductless recirculation kit
DUCT FITTINGS
Use this chart to compute maximum permissable lengths for duct runs to
outdoors.
Note: Do not exceed maximum permissable
equivalent lengths!
Maximum recommended duct
length for these hoods: 150 feet
Flexible ducting: If flexible metal ducting is used, all
the equivalent feet values in the table should be doubled. The flexible
metal duct should be straight and
smooth and extended as much as
possible.
Do NOT use flexible plastic ducting.
Note: Any home ventilation system, such as a ventilation hood, may interrupt the proper flow of combustion air and exhaust required by fireplaces, gas furnaces, gas water heaters and other naturally
vented systems. To minimize the chance of interruption of such naturally vented systems, follow the heating
equipment manufacturer's guidelines and safety standards such as those published by NFPA and ASHRAE.
*Hoods are supplied with a 10"
round transition. A locally supplied transition is required
for other sizes.
Note: Outlet on top of hood is 8-1/8" x 8".
Q
©
10" round
to 8" roun d
Round, straight
3-1/4" x 10" 3-1/4" x 12 "
straight
90° elbow
45° elbow
3-1/4" x 12" 15 ft. 3-1/4" x 10" 14 ft.
90° elbow
3-1/4" xlO" 8ft. 3-1/4" x12" 9ft.
45° elbow
3-1/4" x 10" 33 ft. 3-1/4" x 12" 36ft.
go° fiat elbow
10" round transition
to 3-1/4" x 10" or
3-1/4" x 12" 9ft. 3-1/4" x 10" or
3-1/4" x 12" to 10" round transition 6 ft.
10" round to 3-1/4" x 10" 16 ft. 3-1/4" x 12" transition 13 ft.
go° elbow
3-1/4" xlO" 9ft. 3-1/4"x12"t o10" round 8ft.
transiti on 90° elbow
Round
wall cap with damper
3-1/4" x 10" 24 ft. 3-1/4" x 12" wall cap 26ft.
with damper
Sft. 1ft.
(per foot length)
1ft. (per foot
length)
8" Dia. 17 ft.
10" Dia. 24 ft .
8" Dia. 10 ft.
10" Dia. 14ft .
8" Dia. 32 ft.
10" Dia.41 ft.
Round roof cap
8" Dia. 44 ft.
10" Di a. 56 ft.
TotalDuct Run
For safety reasons, ducting should vent directly outdoors (not into an attic, underneath the house, into the garage or into any enclosed space). Keep duct runs as short and straight as possible. Duct fittings (elbows and transitions) reduce air flow efficiency. Back to back elbows and "S" turns give very poor delivery and are not recommended.
A short straight length of duct at the inlet of the remote blower gives the best delivery. Transition to duct from the integral blower to remote duct transition as close as possible.
In order opreference, use:
1st. 10" round duct
2nd. 8round duct 3rd. 3-1/4" x 14" duct
4th. 7" round duct 5th. 3-1/4" x 10"duct 6th. 6" round duct
The use of flexible metal round duct should only be used when no other duct fitting exists. Limit use to short lengths and do not crush when making corners.
1. Prepare duct and conduit cut outs, see figures 1 and 2 as needed.
i
Mo0o3o,,36,,
it,8, 1-1,2"o,a..o,os
Bottom of
Cabinet or
Soffit
12"
Rear Wall
11
10-112" " '
I I /_ C_<-_-1_7f/ Vertical conduit
CL
_Hood Width
Figure 1
2. Assembly of the 10" transition: The transition supplied with the hood mounts to
the top. Do not install transition until hood is
fixed on cabinet or wall.
a. Place the transition piece over the hood
outlet and secure with 4 screws provided. (Figure3)
b. Wrap all joints (metal transition and hood)
with duct tape for an airtight seal.
c. Remove tape holding damper.
Hood outlet
Figure 2
Figure 3
Transition
23-1/8"
Screws (4)
Loading...
+ 18 hidden pages