Thermador H, HT, HB, H Series, HT Series Installation Instructions Manual

...
Page 1
PLEASE READ ENTIRE INSTRUCTIONS BEFORE PR OCEEDING.
INSTALLATION MUST COMPLY WITH ALL LOCAL CODES.
IMPORTANT: Save these instructions for the Local Electrical Inspector’s use.
INSTALLER: Please leave these Installation Instructions with this unit for the owner.
OWNER: Please retain these instructions for future reference.
IMPORTANT SAFETY INSTRUCTIONS
READ AND SAVE THESE INSTRUCTIONS
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PER­SONS, OBSERVE THE FOL­LOWING:
CAUTION: FOR GENERAL VENTILATING USE ONLY. DO NOT USE TO EXHAUST HAZ­ARDOUS OR EXPLOSIVE MA­TERIALS OR VAPORS.
A. Use this unit only in the manner
intended by the manufacturer. If you have questions, contact the manufac­turer.
B. Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service dis­connecting means cannot be locked, securely fasten a prominent warning
INSTALLATION INSTRUCTIONS
MODELS H/HT/HB WALL HOOD
FOR RESIDENTIAL USE ONLY
device, such as a tag, to the service panel.
C. Installation work and electrical wiring must be done by qualified per­sons in accordance with all applicable codes & standards, including fire-rated construction.
D. Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burn­ing equipment to prevent backdrafting. Follow the heating equipment manu­facturers guideline and safety standards such as those published by the Na­tional Fire Protection Association (NFPA), the American Society for Heat­ing, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
E. When cutting or drilling into wall or ceiling, do not damage electrical
wiring and other hidden utilities.
F. CAUTION: To reduce risk of fire and to properly exhaust air, be sure to duct air outside. Do not vent exhaust air into spaces within walls, ceilings, attics, crawl spaces or garages.
G. WARNING – TO REDUCE THE RISK OF FIRE, USE ONLY METAL DUCT WORK.
H. Install this hood in accordance with all requirements specified by the manufacturer of your cooktop/range.
I. This appliance has a polarized plug (one blade wider than the other). To reduce the risk of electric shock, this plug is intended to fit in a polarized outlet one way. If the plug does not fit fully in the outlets, reverse the plug. If it still does not fit, contact a qualified electrician. Do not attempt to defeat this safety feature.
WARNING - TO REDUCE THE RISK OF A RANGE TOP GREASE FIRE:
Boilovers cause smoking and greasy spillovers that may ignite. Heat oils slowly on low or medium settings.
B. Always turn hood ON when cooking at high heat or when cooking flaming foods.
C. Clean ventilating fans frequently. Grease should not be allowed to accumulate on fan or filter.
D. Use proper pan size. Always use cookware appropriate for the size of the surface element.
WARNING: - TO REDUCE THE RISK OF INJURY TO PERSONS IN THE EVENT OF A RANGE TOP GREASE FIRE, OBSERVE THE FOLLOWING:
A. SMOTHER FLAMES with a close-fitting lid, cookie sheet, or metal tray, then turn off the burner. BE CAREFUL TO PREVENT BURNS. If the flames do not go out immediately, EVACUATE AND CALL THE FIRE DEPARTMENT.
B. NEVER PICK UP A FLAMING PAN C. DO NOT USE WATER, including wet dishcloths or
towels – a violent steam explosion will result. D. Use an extinguisher ONLY if:
1) You have a Class ABC extinguisher, and you already know how to operate it.
2) The fire is small and contained in the area where it started.
3) The fire department is being called.
4) You can fight the fire with your back to an exit.
PAGE 1
– You may be burned.
Page 2
Parts included with your Hood:
Hood Canopy Assembly Rough-in Plate * Transition/Damper for ducting Mounting Screws (8, #10 x 1") - may
not need all screws (depending
on hood size) Installation Instructions Care & Use Manual Registration Card Filters (3 or 4 depending on hood size) Hex nuts (10 pieces) Blower Mounting Bracket
To be purchased separately:
* NOTE: The 19-11-943 (equiva-
lent to VM410) Ventilator and Transition are included with all HB Model hoods.
• Ventilator: choose one of the
following:
* VM410 – 400CFM, integral
ventilator.
VTN600Q – 600 CFM, integral
ventilator.
VTR600R – 600 CFM, remote
ventilator.
VTR1000Q – 1000CFM, remote
ventilator.
H and HT models require Transi-
tion HTR8 or HTR10.
For integral ventilator installations,
choose one of the following ex­haust outlets:
RJ310 (roof outlet)WC310 (wall outlet)WC8WC10
Halogen Bulbs (2), size R20, 50 watt maximum.
Duct Tape, 2" wide
Wall Anchors (if needed)
1/2"Diameter Conduit
Keep Hot Shelf Accessory-KHS
(Optional)
Wire Nuts
Keep hot lamps (2) Size R40 250W maximum (H/HT Hoods only)
• Tools Needed:
Phillips Screw Driver 3/8" Hex Socket Driver 1-1/2" Drill bit (Wood) Electric Drill Hammer Pencil Level Saber Saw
CONSIDERATIONS BEFORE INSTALLING HOOD
1. For efficient air flow exhaust, use a straight run or as few elbows as possible.
2. Do not use flex ducting.
3. COLD WEATHER installations should have an additional backdraft damper installed to minimize back­ward cold air flow and a non­metallic thermal break to mini­mize conduction of outside tem­peratures as part of the ductwork.
PAGE 2
The damper should be on the cold air side of the thermal break. The break should be as close as pos­sible to the location where the ducting enters the heated portion of the house.
Page 3
CABINET OR SOFFIT PREPARATION
Cabinet Front
Bottom of Cabinet or Soffit
Cabinet
Vertical Discharge
HOOD LENGTH DIM. "A"
30" 13-11/32" 36" 15-1/2" 42" 16" 48" 17-1/2"
12"
12"
4-1/2"
1/2"
4-1/2"
"C"
Rear Wall
Hood Length
"A"
1/2"
Figure 1
TYPICAL INSTALLATION
The hoods are designed for either vertical or horizontal discharge as shown in Figure A and B respectively.
The recommended height from the countertop to the bottom of the hood is 30" to 36". These hoods are not recommended to be used over solid fuel fire barbecues.
8-1/2"
1-7/8"
1-1/2"Dia. Holes
Optional Rear Discharge
Note: It is important to select the ventilator to be used before cutting the duct opening on the cabinet or wall.
"B"
4"
22"
Figure 2
Hood Type Height "B" DIM. C
H series 10" 18" HB series 10" 13" HT 18" 18"
PAGE 3
Page 4
Round Duct
Soffit
Rough-in Plate
Heat Lamp
Hood
Back Splash (with Warming Shelf)
Transition
Ventilator (VTN600Q)
Filter
Rough-in Plate
Heat Lamp
Hood
Soffit
Filter
Outside Wall
Wall Cap
Transition
Ventilator
30" to 36"
Cooktop
Figure A – Vertical Discharge
INSTALL THE ROUGH-IN PLATE:
Note: Before installing the rough-in plate to the bottom of
the cabinet or soffit, make sure that the cabinet or soffit is level.
1. Detach the rough-in plate from the hood assembly by removing three shipping screws on the back and three shipping screws on the top of the hood assembly.
2. Remove the proper knockout panels on the rough-in plate for the selected ventilator. The rough-in plate is reversible to allow either horizontal or vertical dis­charge for both knockout panels.
3. Attach the rough-in plate to the cabinet or wall with the mounting screws (#10 x 1") provided. Use all holes provided in the rough-in plate. (Use wall anchors as necessary on drywalls.)
30" to 36"
Back Splash (with Warming Shelf)
Cooktop
Figure B – Horizontal Discharge
Longer Bracket (Provided with H/ HT Hoods)
7-1/2"
8"
12-3/4"
Figure C
H/HB/HT HOOD SERIES
Hex Nut
VM410
INSTALL THE INTEGRAL VENTILATOR MODEL VM410 (H and HT only):
Note: For HB series hood the ventilator is shipped and pre
mounted to the rough-in plate. For H/HT series hood the VM410 is to be purchased separately.
1. Remove and discard the Z-shape bracket from the VM410.
2. Remove the blower mounting bracket and replace with a longer bracket provided with the H/HT hood. See Fig. C.
Figure D
3. Insert one end of the blower mounting bracket into the ventilator mounting channel located on the rough-in plate, and slip the other end over the weld stud on the rough-in plate. Secure assembly with the hex nut pro­vided with the hood. See Fig. D.
PAGE 4
Page 5
INSTALL THE INTEGRAL VENTILATOR MODEL VTN600Q:
INSTALL THE REMOTE VENTILATOR MODEL VR600, VTR600R OR VTR1000Q:
Insert one end of the blower mounting bracket into the ventilator mounting channel located in the rough-in plate, and slip other end of bracket into the weld stud on the rough-in plate and tighten it with the hex nut provided with the hood. See Fig. D.
DUCTING CONNECTION:
FOR INTEGRAL VENTILATOR MODEL VM410, 19-11-943 (HB Hoods):
1. Attach the transition (3-1/4" x 10") provided to the top
of the rough-in plate, using the two shipping screws. Make sure the knockout on the rough-in plate is re­moved. Seal all joints between the rough-in plate and the transition with duct tape.
2. Install 3-1/4" x 10" duct from the transition to the wall
or roof (use roof exhaust outlet RJ310 or wall exhaust outlet WC310, purchased separately).
FOR INTEGRAL VENTILATOR MODEL VTN600Q:
1. Attach the transition Model # HTR8 (purchased sepa-
rately) to the top of the rough-in plate. Make sure the proper knockout on the rough-in plate is removed. Seal all joints between the rough-in plate and the transition with duct tape.
For installing the remote ventilator on the roof or side wall, refer to the Installation Instructions provided with the ventilator.
2. Install 8" round duct from the HTR8 transition to the
side wall (use wall cap Model # WC8, purchased separately).
FOR REMOTE VENTILATOR MODEL VTR600R, VTR1000Q:
1. For the VTR600R, attach transition Model HTR8 (pur-
chase separately) or for VTR1000Q attach transition Model HTR10 (purchase separately), to the top of the rough-in plate. Make sure the proper knockout on the rough-in plate is removed. Seal all joints between the rough-in plate and the transition with duct tape.
2. Use 8-inch round duct for the VTR600R or10-inch
round duct for the VTR1000Q. Install duct from the transition to the remote ventilator.
ELECTRICAL CONNECTION:
1. Install three wires: black, white and green (#16 AWG) in 1/2" conduit from the service panel to the hood junction box. Power supply must be rated for 120v, 60Hz, 15 amps (minimum)
2. Remove the knockout and install the strain relief (con­duit) connector in the rough-in plate hole.
3. Remove the junction box cover from the rough-in plate. Connect black wire # 9 to power supply black wire, white wire # 5 to power supply white wire, and green wire # 18 to power supply green wire. See wiring diagram on page 7.
PAGE 5
Page 6
WIRING TO INTEGRAL VENTILATOR MODEL VM410, VTN600Q:
1. Plug the power cord from the ventilator motor to the receptacle located inside the hood assembly. See wiring diagram.
2. Install the junction box on the rough-in plate.
WIRING TO REMOTE VENTILATOR MODEL VTR600R, VTR1000Q FOR H AND HT HOOD ONLY:
1. Remove the knockout and install the strain relief (con­duit) connector on the rough-in plate hole. Run three wires black, white and green (#16 AWG) in 1/2" conduit from the remote ventilator to the hood junction box.
INSTALL HOOD ASSEMBLY:
1. Install the hood assembly to the rough-in plate by aligning the weld studs on the rough-in plate with slotted holes on the back of the hood assembly.
2. Connect wires from step 1 above to the remote venti­lator wires using color codes (black to black, white to white, and green to green). See wiring diagram on Page
7. Important: Individually cap the blue and red wires in
the remote ventilator wiring compartment with wire nuts.
3. Connect the wires from Step 1 to the hood assembly. Wiring: Black wire to red wire #19, white wire to white wire #5, and green wire to green wire #18. See wiring diagram on Page 7.
4. Reinstall the junction box on the rough-in plate.
4. Insert filter into the bottom rear slot of the hood assembly and fully compress the spring.
5. Holding the filter by the handle, snap it into place.
2. Using the hex nuts provided secure the hood assembly to the rough-in plate.
3. Install two halogen bulbs, size R20, 50 watts maximum. Also install two heat lamp bulbs, size R40, 250 watts maximum for H and HT Hood. Bulbs are not provided.
PAGE 6
Page 7
WIRING DIA GRAMS FOR H, HT AND HB HOODS
WIRING DIAGRAM
HB HOODS
19-11-987B
WIRING DIAGRAM
H AND HT
HOODS
19-11-928C
PAGE 7
Page 8
Thermador reserves the right to change specifications or design without notice. Some models are certified for use in Canada. Thermador is not responsible for products which are transported from the United States for use in Canada. Check with your local Canadian distributor or dealer. Thermador, 5551 McFadden Avenue, Huntington Beach, CA 92649.
FILE # E21958
5551 McFadden Avenue • Huntington Beach, CA 92649 • 800/735-4328
ECO# 71532 • 19-11-930F • © Thermador Corporation,1998 • Litho in U.S.A. 9/99
PAGE 8
Loading...