TemperZone OPA 330RKT, OPA 205RKT Installation & Maintenance

OPA 330RKT
Packaged Reverse Cycle R410A Air Cooled Air Conditioner
GENERAL
This OPA 330RKT unit must be installed in accordance with all national and local safety codes.
CONFIGURATIONS
1. Horizontal supply/return air with box mounting channel (RKTH), or
2. Downward supply air with box mounting channel (RKTU).
REFRIGERATION SYSTEM General
The refrigeration system has been charged with 9.7 kg each of HFC-410A (R410A) refrigerant. Tapping points are provided to measure discharge and suction operating pressures.
Compressors
The compressor is directional scroll type. The compressor lubricant is polyol ester oil (POE). Note, this oil absorbs moisture quickly if exposed to open air. On commissioning, the compressor must be checked for correct rotation (refer Start Up Procedure).
ECONOMISER (Option)
If the outdoor air heat content or temperature is below that of the return air, the fresh air damper opens and the return air damper closes to provide the first stage of cooling. The compressor will then operate to provide more cooling if required.
INSTALLATION
Unpacking
Units configured with Downward supply air and mounting rails, have their spigots shipped loose inside the return air cavity.
Positioning
Refer to dimension diagrams for minimum clearances. If multiple units are to be placed side-by-side then allow at least 2 m between coil faces.
Mounting
The unit should be fastened to a firm flat horizontal base using the holes supplied in the box mounting channel.
When the unit is being installed on a roof it is recommended that the unit is installed on a substantial structure with vibration isolating springs beneath the unit. These springs are not supplied with the unit.
Flexible duct connections are recommended between the supply and return ducts and the unit.
Condensate Drain
The condensate drain should be 'U' trapped outside the unit. The trap should have a Downward height of at least 100 mm. The drain should have a slope of at least 1 in 50 and must not be piped to a level above the unit drain pipe (see figure 3).
Electrical Requirements
Electrical work must be done by a qualified electrician. The outdoor unit must be wired directly from a distribution board by means of a circuit breaker or H.R.C. fuse, and a mains isolator provided - preferably close to the unit. Note: DO NOT USE REWIRABLE FUSES.
The OPA 330 is provided with a 24V AC control circuit for a thermostat, on/off switch and/or time clock.
The control transformer 240V primary voltage is used for countries with 230-240V power supply. For countries with supply voltages 200-220V, change the primary voltage on the transformer to 208V.
Standard units are suitable for use with thermostats with either manual Heat/Cool selection or automatic changeover subject to the contact ratings of the thermostats.
A 24 hour power supply to the compressor crank case heater is required, otherwise the warranty is void.
CHECK TESTS
1. Leave the on/off switch in the off position and close the mains isolating switch. A four hour delay period is required to allow the crankcase heaters to drive any liquid refrigerant out of the compressor oil.
2. Check that the shipping block beneath the compressor has been removed and that the compressor is secure on its mounts.
3. Check that all fan motors are free running.
4. Check that the thermostat is correctly wired to the unit and is set at the desired temperature.
5. Check that the air filters have been correctly installed if fitted.
6. Check air diffuser dampers are open if appropriate.
START UP PROCEDURE
Use the supplied Commissioning Sheet to help you complete the following procedure:
1. After the four hour delay period has expired, switch on the unit.
Installation & Maintenance
2. The compressor fitted is directional. Check for correct rotation. If rotation is incorrect the compressor will not pump, be noisy, and will draw minimal current. To correct motor rotation, change the phasing at the main power terminal. If changing the phasing, check the indoor air fan then runs in the correct direction also.
3. Check the supply voltage between each phase and neutral.
4. Measure the current draw on each phase to the compressor motor and measure the current draw of each fan motor. Check all readings against the specified values in the wiring diagram.
5. Fit gauges and measure the suction and discharge pressures of both refrigeration circuits.
6. Check that the outdoor air fan motors are running smoothly.
7. Test the operation of the reversing valve by running the unit in both the heating and cooling mode.
8. Check the indoor unit's fan belt tension after 20 mins of operation and adjust if necessary (refer Commissioning Sheet).
9. Check the supply air flow at each outlet.
10.Check the tightness of all electrical connections and sign the check label.
11.Touch up any outdoor unit paintwork damage to prevent corrosion.
SETTING SUPPLY AIR FLOW
Consult OPA 330 Technical Data pamphlet for details of airflow/duct static pressure, if required.
If the indoor air returning to the unit is regularly expected to be above 50%RH, then the coil face velocity should be limited to be 2.5 m/s or less (refer Air Handling graph in Technical Data pamphlet).
High humidity levels can occur in tropical or subtropical conditions, and/or when heavily moisture laden fresh air is introduced. Select a fan speed that avoids water carry­over problems.
In a free blow or low resistance application, beware of exceeding the fan motor's full load amp limit (refer wiring diagram).
The indoor air fan motor is fitted with a factory set adjustable pitch pulley. Instructions for the adjustment of pulleys is included on the back page of the supplied Commissioning Sheet. One revolution of adjustment is equal to approx. 7% change in air volume flow rate.
PROJECTION
OUTDOOR UNIT CONTROLLER (OUC)
The Outdoor Unit Controller (OUC) includes a temperature sensing head pressure control which enables the system to com­pensate for outdoor ambient temperatures below 20°C on cooling cycle, and above 15°C on heating cycle. The OUC also has features which protect against icing or overheating of coils, rapid cycling of the compressor and loss of refrigerant charge.
If the outdoor unit fans take some time to begin rotating when the system is powered on, or they don't appear to be rotating appropriately while the compressor is running, consult the OUC label on the electrical box. If necessary, refer to temperzone for further diagnostic information.
MAINTENANCE Monthly
1. Check air filters, if fitted, and vacuum or wash clean as necessary.
2. Check condensate drain for free drainage.
3. Check compressor compartment for oil stains indicating refrigerant leaks.
Three Monthly (or every 1200 hrs of operation)
Check the indoor unit's fan belt tension and adjust if necessary.
Six Monthly
1. Check the tightness of electrical connections.
2. Check the tightness of fans, motor mountings, pulleys and belt tension.
3. Check suction and discharge operating pressures.
4. Replace indoor air filters (if fitted).
5. Check condensate drain for free drainage.
Yearly
1. Check all refrigerant piping for chafing and vibration.
2. Check the operation of electric heaters, if fitted.
3. Check air supply at all diffusers.
4. Check for excessive noise and vibration and correct as necessary.
5. Check for insulation and duct damage and repair as necessary.
6. Remove lint and dust accumulation from outdoor coil fins.
7.Touch up any paintwork damage to prevent corrosion.
NOTE
The manufacturer reserves the right to make changes in specifications at any time without notice or obligation. Certified data is available on request.
This pamphlet replaces the previous issue no. 2941 dated 08/08.
Wiring revision B.
DIMENSIONS (mm)
Fig. 1 OPA 330RKTH – Horizontal Supply & Return Air
1490
W
500 MIN. CLEARANCE
Z
1000 MIN. CLEARANCE
ACCESS
PANEL
ELECTRICAL BOX
1000 MIN. CLEARANCE
1670
OPTIONAL WEATHER
HOOD
X
Y
5555
RETURN
SUPPLY
60
AIR
AIR
150
375
FILTER
ACCESS
PANEL
420
OPA 330RKT
POINT LOads (kg)
W X Y Z
116 98 115 133
Net Weight 462 kg
Note : A 2 m clearance
is required above the
exhaust air fans
95
600
OPTIONAL
WEATHER
HOOD
Not to Scale
1335
405
413
88
1605
MOUNTING CENTRES
DRAIN 1" BSP FEMALE
100
35
1402
MOUNTING CENTRES
770
210
DIMENSIONS (mm)
PROJECTION
OPEN DRAIN
MINIMUM SLOPE 20 mm PER m (1 IN 50)
100 mm MINIMUM
200 mm
APPROX.
'U' TRAP
100 mm
APPROX.
VENT PIPE FOR LONG CONDENSATE DRAIN RUNS
SUPPLY
& RETURN AIR
210
170
365
445
330
745
180
115
400
60
Fig. 2 OPA 330RKTU – Downward Supply & Return Air
OPA 330RKT
Not to Scale
Note: Supply and return air spigots are shipped loose inside the return air cavity.
Fig. 3 Condensate Drain
06/09 Pamphlet No. 3103
© temperzone limited 2009
Loading...