TemperZone OPA 300R Installation & Maintenance

Page 1
OPA 300R
Packaged Reverse Cycle Air Cooled Air Conditioner
GENERAL
This OPA 300R unit must be installed in accordance with all national and local safety codes.
CONFIGURATIONS
1. Horizontal supply/return air with mounting rails,
2. Downward supply air with mounting rails, or
3. Downward supply air with plinth mount.
REFRIGERATION SYSTEM General
The refrigeration system has been charged with 6.6 kg each of HCFC-22 (R22) refrigerant. Tapping points are provided to measure discharge and suction operating pressures.
Compressors
The compressors are directional scroll type. On commissioning, the compressors must be checked for correct rotation (refer Start Up Procedure).
The compressor is fitted with an adjustable anti-rapid cycle timer which provides a delay 'on break' (i.e. stop-to-start).
ECONOMISER (Option)
If the outdoor air heat content or temperature is below that of the return air, the fresh air damper opens and the return air damper closes to provide the first stage of cooling. The compressor(s) will then operate to provide more cooling if required.
INSTALLATION
Unpacking
Units configured with Downward supply air and mounting rails, have their spigots shipped loose inside the return air cavity.
Positioning
Refer to dimension diagrams for minimum clearances. If multiple units are to be placed side-by-side then allow at least 2 m between coil faces.
Mounting
The unit should be fastened to a firm flat horizontal base using the holes supplied in the mounting rails. Refer to figure 4 for plinth mount details.
When the unit is being installed on a roof it is recommended that the unit is installed on a substantial structure with vibration isolating springs beneath the unit. These springs are not supplied with the unit. Two channels are provided under the base for spring mounts or bolting down.
Flexible duct connections are recommended between the supply and return ducts and the unit.
Condensate Drain
The condensate drain should be 'U' trapped outside the unit. The trap should have a Downward height of at least 100 mm. The drain should have a slope of at least 1 in 50 and must not be piped to a level above the unit drain pipe (see figure 5).
Electrical Requirements
Electrical work must be done by a qualified electrician. The outdoor unit must be wired directly from a distribution board by means of a circuit breaker or H.R.C. fuse, and a mains isolator provided - preferably close to the unit. Note: DO NOT USE REWIRABLE FUSES.
The OPA 300 is provided with a 24V AC control circuit for a thermostat, on/off switch and/or time clock.
The control transformer 240V primary voltage is used for countries with 230-240V power supply. For countries with supply voltages 200-220V, change the primary voltage on the transformer to 208V.
Standard units are suitable for use with thermostats with either manual Heat/Cool selection or automatic changeover subject to the contact ratings of the thermostats.
A 24 hour power supply to the compressor crank case heaters is required, otherwise the warranty is void.
CHECK TESTS
1. Leave the on/off switch in the off position and close the mains isolating switch. A four hour delay period is required to allow the crankcase heaters to drive any liquid refrigerant out of the compressor oil.
2. Check that the shipping block beneath the compressor has been removed and that the compressor is secure on its mounts.
3. Check that all fan motors are free running.
4. Check that the thermostat is correctly wired to the unit and is set at the desired temperature.
5. Check that the air filters have been correctly installed if fitted.
6. Check air diffuser dampers are open if appropriate.
START UP PROCEDURE
Use the supplied Commissioning Sheet to help you complete the following procedure:
1. After the four hour delay period has expired, switch on the unit.
2. The compressor fitted is directional. Check for correct rotation. If rotation is incorrect the compressor will not pump, be noisy, and will draw minimal current. To correct motor rotation, change the phasing at the main power terminal.
3. Check the supply voltage between each phase and neutral.
4. Measure the current draw on each phase to the compressor motor and measure the current draw of each fan motor. Check all readings against the specified values in the wiring diagram.
Installation & Maintenance
5. Fit gauges and measure the suction and discharge pressures of both refrigeration circuits.
6. Check that the outdoor air fan motors are running smoothly.
7. Test the operation of the reversing valve by running the unit in both the heating and cooling mode.
8. Check the indoor unit's fan belt tension after 20 mins of operation and adjust if necessary (refer Commissioning Sheet).
9. Check the supply air flow at each outlet.
10.Check the tightness of all electrical connections and sign the check label.
11.Touch up any outdoor unit paintwork damage to prevent corrosion.
SETTING SUPPLY AIR FLOW
Consult OPA 300 Technical Data pamphlet for details of airflow/duct static pressure, if required.
If the indoor air returning to the unit is regularly expected to be above 50%RH, then the coil face velocity should be limited to be 2.5 m/s or less (refer Air Handling graph in Technical Data pamphlet).
High humidity levels can occur in tropical or subtropical conditions, and/or when heavily moisture laden fresh air is introduced. Select a fan speed that avoids water carry­over problems.
In a free blow or low resistance application, beware of exceeding the fan motor's full load amp limit (refer wiring diagram).
The indoor air fan motor is fitted with a factory set adjustable pitch pulley. Instructions for the adjustment of pulleys is included on the back page of the supplied Commissioning Sheet. One revolution of adjustment is equal to approx. 7% change in air volume flow rate.
OUTDOOR UNIT CONTROLLER (OUC)
The Outdoor Unit Controller (OUC) includes a temperature sensing head pressure control which enables the system to compensate for outdoor ambient tempera­tures below 20°C on cooling cycle, and above 15°C on heating cycle. The OUC also has features which protect against icing or overheating of coils, rapid cycling of the compressor and loss of refrigerant charge.
If the outdoor unit fans take some time to begin rotating when the system is powered on, or they don't appear to be rotating appropriately while the compressor is running, consult the OUC label on the electrical box. If necessary, refer to temperzone for further diagnostic information.
MAINTENANCE Monthly
1. Check air filters, if fitted, and vacuum or wash clean as necessary.
2. Check condensate drain for free drainage.
Page 2
3. Check compressor compartment for oil stains indicating refrigerant leaks.
Three Monthly (or every 1200 hrs of operation)
Check the indoor unit's fan belt tension and adjust if necessary.
Six Monthly
1. Check the tightness of electrical connections.
2. Check the tightness of fans, motor mountings, pulleys and belt tension.
3. Check suction and discharge operating pressures.
4. Replace indoor air filters (if fitted).
5. Check condensate drain for free drainage.
Yearly
1. Check all refrigerant piping for chafing and vibration.
2. Check the operation of electric heaters, if fitted.
3. Check air supply at all diffusers.
4. Check for excessive noise and vibration and correct as necessary.
5. Check fan and motor bearings and lubricate or replace as necessary.
6. Check for insulation and duct damage and repair as necessary.
7. Remove lint and dust accumulation from outdoor coil fins.
8.Touch up any paintwork damage to prevent corrosion.
DIMENSIONS (mm)
Fig. 1 Horizontal Supply & Return Air / Mounting Rails
Version 1
1680
OPTIONAL WEATHER
HOOD
1000 MIN. CLEARANCE
1560
MOUNTING CENTRES
X
RETURN
SUPPLY
Y
60
DRAIN 1" BSP FEMALE
AIR
AIR
150
405
365
55
1475
W
OUTDOOR AIR FLOW
500 MIN. CLEARANCE
Z
1330
1000 MIN. CLEARANCE
ACCESS
PANEL
ELECTRICAL BOX
FILTER
ACCESS
PANEL
375
1360
MOUNTING CENTRES
425
105
POINT LOADS (kg)
WX Y Z
119 90 105 134
Net Weight 448 kg
Note : A 2 m clearance is
required above the
600
OPTIONAL
WEATHER
HOOD
770
225
OPA 300R
PROJECTION
Not to Scale
exhaust air fans
Fig. 2 Downward Supply Air / Mounting Rails
Version 2
OUTDOOR
AIR FLOW
ADD-ON
SPIGOTS
(SUPPLIED)
750
405
100
135
425
380
375
150
205
290
SUPPLY
& RETURN AIR
NOTE
The manufacturer reserves the right to make changes in specifications at any time without notice or obligation. Certified data is available on request.
Note: Supply and return air spigots are shipped loose inside the return air cavity.
Page 3
DIMENSIONS (mm)
Fig. 3 Downward Supply Air / Plinth Mounted
Version 3
OUTDOOR AIR FLOW
OPA 300R
PROJECTION
Not to Scale
Note: Refer to Fig.1 for overall dimensions and Fig.4 for further plinth dimensions.
PLINTH PLINTH
Fig. 4 Roof Mounting Plinth (Kitset)
558
53
SUPPLY
AIR
53
447
321
471
1599
INSIDE
53
RETURN
AIR
SUPPLY
& RETURN AIR FLOWS
OPA UNIT
53
SEALER
125
60
125
STRIP
(SUPPLIED)
ROOF MOUNTING
PLINTH
FLASHING
MOUNTING
50
800
1344
INSIDE
53
HOLD DOWN BRACKET
HOLD DOWN BRACKET
SECURED TOGETHER
WITH NUT & BOLT
OPA UNIT’S
SUPPORT ANGLES
ANGLE &
MAXIMUM
ASSEMBLY
ROOF
PLINTH
INSEAL
Fig. 5 Condensate Drain
100 mm
200 mm
APPROX.
MINIMUM
'U' TRAP
OPEN DRAIN
SLOPE 20 mm PER m MINIMUM (1 IN 50)
FLASHING
TYPICAL CORNER ASSEMBLY
NOTE
The manufacturer reserves the right to make changes in specifications at any time without notice or obligation. Certified data is available on request.
This pamphlet replaces the previous issue no. 2234 dated 06/03. OUC added, wiring revision.
Page 4
04/05 Pamphlet No. 2487
© temperzone limited 2005
Loading...