TemperZone OPA 1370RKTMG01-PZ Installation & Maintenance

OPA 1370RKTMG01-PZ (Digital c/w Plug fan and Economiser)
Packaged Reverse Cycle R410A Air Cooled Air Conditioner
GENERAL
This OPA 1370RKTMG Outdoor Unit must be installed in accordance with all national and local safety codes.
OPTION
(eld tted).
2. Viking Controller for Economiser with
enthalpy control (factory tted).
REFRIGERATION SYSTEM General
The OPA 1370 has four independent refrigeration circuits and four compressors
to provide the exibility and economy of
four stage operation, i.e. utilising one to four circuits as conditions vary, plus the advantage of staggered starting.
Each refrigeration system has been charged with HFC-410A (R410A) refrigerant; refer wiring diagram
specication table for amount. Tapping
points are provided to measure discharge and suction operating pressures.
Compressors
The compressors are directional scroll type. One of the four compressors is digital scroll type. This has a variable capacity ability that enables closer control of room temperature.
The compressor lubricant is polyol ester oil (POE). Note, this oil absorbs moisture
quickly if exposed to open air. On
commissioning, the compressors must be checked for correct rotation (refer Start Up Procedure). A time delay prevents simultaneous starting of the compressors.
ECONOMISER
The economiser fresh air intake cowl with water separator is supplied separately and
is best tted after the OPA is mounted on
it's platform. Fitting instructions are supplied with the cowl.
Controls may be supplied by others. If the outdoor air temperature or heat content preferably, is below that of the return air the fresh air damper opens and the return
air damper closes to provide the rst stage
of cooling. A spill air facility in the building may be necessary for when the return air damper is closed. The fresh air damper should return to minimum setting and the return air damper open before compressors are allowed to operate to provide further cooling.
INSTALLATION
Positioning
Refer to dimension diagrams for minimum clearances. If multiple units are to be placed side-by-side then allow at least 2 m between coil faces.
Mounting
The unit should be fastened to a rm at
horizontal base using the holes supplied in the mounting channels.
When the unit is being installed on a roof it is recommended that the unit is installed on a substantial structure with anti-vibration mounts or pads.
Flexible duct connections are recommended
between the supply and return ducts and the unit.
Condensate Drain
The condensate drain should be 'U' trapped outside the unit. The trap should have a vertical height of at least 100 mm. The drain should have a slope of at least 1 in 50 and must not be piped to a level above the unit drain pipe.
OPEN DRAIN
VENT PIPE FOR LONG CONDENSATE DRAIN RUNS
100 mm
APPROX.
100 mm MINIMUM
200 mm
APPROX.
'U' TRAP
Electrical Requirements
Electrical work must be done by a qualied
electrician. The outdoor unit must be wired directly from a distribution board by means of a circuit breaker or H.R.C. fuse, and a mains isolator provided - preferably close to the unit. Note: DO NOT USE REWIRABLE FUSES.
The OPA 1370 is provided with a 24V AC control circuit for a thermostat, on/off switch and/or time clock.
Standard units are suitable for use with thermostats with either manual Heat/Cool selection or automatic changeover subject to the contact ratings of the thermostats.
The system is set up for the compressors to be controlled variably by:
1. TZT-100 Controller (via RS485 modbus),
2. 0-10V dc command via BMS modbus, or
3. 0-10V dc command via a client supplied
external controller.
If option 1 is chosen, then disconnect or remove the Signal Input for Controller 0-10V.
If a TZT-100 Controller is used then variable capacity control is automatically included and no additional wiring is required.
A 24 hour power supply to the control circuit is required, otherwise the warranty is void.
SETTING SUPPLY AIR FLOW
Consult OPA 1370 Technical Data pamphlet
at www.temperzone.biz for details of airow/
duct static pressure, if required.
MINIMUM SLOPE 20 mm PER m (1 IN 50)
Installation & Maintenance
If the indoor air returning to the unit is
regularly expected to be above 50%RH,
then the coil face velocity should be limited to be 2.5 m/s or less (refer Air Handling graph in Technical Data pamphlet).
High humidity levels can occur in tropical or subtropical conditions, and/or when heavily moisture laden fresh air is introduced. Select a fan speed that avoids water carry­over problems.
INDOOR FAN SPEED
The fan speed is continuously variable via the 0-10V DC control signal applied between terminals 'FAN GND' and '0–10V'.
Once the maximum design air ow has
been set, a variable fan speed can be
controlled as follows by applying an external
variable 0–10V DC control voltage to '0–10V' terminal. Connect 0V reference to 'FAN GND'.
CHECK TESTS
1. Check that all the shipping bolts on the back of the compressor frame have been removed and that the compressor is secure on its mounts.
2. Check by hand that all fan motors can turn freely.
3. Check that the air lters have been correctly installed, if tted.
4. Check air diffuser dampers are open if appropriate.
5. Check that the thermostat, or external
24V controller, is correctly wired to the unit and is set at the desired temperature.
6. Check the tightness of all electrical connections.
7. Leave the thermostat, or external 24V
controller, in the off position and close the mains isolating switch. (A four hour delay period is required to allow the crankcase heater to drive any liquid refrigerant out of the compressor oil.)
8. Check the supply voltage between each phase and neutral.
START UP PROCEDURE
After the four hour delay for the crankcase
heater has expired, use the supplied
Commissioning Sheet (Form NS 228) to record results when completing the following
‘Start-up’ procedure. A UC6 Service Interface tool is supplied to read, pressures,
superheat and its set-point, compressor amps etc.
1. Select a sensible Fan speed (or Auto Fan mode), operating cycle (cool or heat), and room temperature set point, depending on the time of year, such that the compressor will start and run at a high capacity.
2. Turn ON the thermostat / external
controller. Wait for the compressor to
start. Measure the current for each
PROJECTION
phase feeding into the compressor’s.
Compare against the compressor amps
specied on the unit’s wiring diagram.
3. Compressors tted are directional. Check
for correct rotation. If rotation is incorrect the compressor will not pump, be noisy, and will draw minimal current. To correct motor rotation, change the phasing at the main power terminal. If changing the phasing, check the indoor air fan then runs in the correct direction also.
4. Measure the current draw of each fan motor. Check all readings against the
specied values in the wiring diagram.
5. Use the UC6 Service Interface tool to check operating pressures and status. If the UC6 Service Interface is not
available, t gauges and measure the
suction and discharge pressures of both refrigeration circuits.
6. Check that the outdoor air fan motors are running smoothly and drawing less than
the full load amps specied.
7. Check the indoor unit's fan belt tension after 20 mins of operation and adjust if necessary (refer Commissioning Sheet).
8. Test the operation of the reversing valve by running the unit in both the heating and cooling mode.
9. Check the supply air ow at each outlet.
10. Touch up any outdoor unit paintwork damage to prevent corrosion.
UNIT CONTROLLER (UC6)
The Unit Controller provides system protection functions such as coil frost protection, de-icing, high head pressure and low suction pressure cut-out. It also protects against rapid cycling of the compressor and loss of refrigerant. The UC regulates the superheat of the refrigeration system by controlling the position of an
Electronic Expansion Valve (EEV). Various
methods of head pressure control (or limiting) are employed in temperzone units including in this particular unit, variation of compressor speed. The particular method used varies from model to model, but is handled by the Unit Controller. In combination, these features deliver optimised performance across a wide operating temperature range.
Refer to UC6 Controller label on the unit for operation & fault diagnostics information. Many operating status conditions can be determined, without gauges, simply by using the UC6 Service Interface graphical display supplied with the unit.
MAINTENANCE Monthly
1. Check air lters, if tted, and vacuum or
wash clean as necessary.
2. Check condensate drain for free drainage.
3. Check compressor compartment for oil stains indicating refrigerant leaks.
Six Monthly
1. Check the tightness of electrical connections.
2. Check the tightness of all fans and motor mountings.
3. Check suction and discharge operating pressures. (Using the UC6 Service
Interface avoids tting and removing
gauges with consequential refrigerant loss.)
5. Check condensate drain for free drainage.
Yearly
1. Check all refrigerant piping for chang
and vibration.
2. Check the operation of electric heaters,
if tted.
3. Check air supply at all diffusers.
4. Check for excessive noise and vibration
and correct as necessary.
5. Check for insulation and duct damage and repair as necessary.
6. Remove lint and dust accumulation from
outdoor coil ns.
7. Touch up any paintwork damage to prevent corrosion.
NOTE
The manufacturer reserves the right to
make changes in specications at any time without notice or obligation. Certied data is
available on request.
DIMENSIONS (mm)
OPA 1370RKTMG01-PZ – Horizontal Supply & Return Air
1000 MIN. CLEARANCE
FILTER
ACCESS PANEL
FAN
ACCESS
DOOR
W
RETURN
AIR
DRAIN 11/2" BSP MALE
MOUNTING
CENTRES
SUPPLY
AIR
2260
UV
ELECTRICAL
ACCESS
DOOR
2430 OA
1000 MIN. CLEARANCE
ELECTRICAL
ACCESS
DOOR
ZYX
OUTDOOR
AIR FLOW
OUTDOOR
AIR FLOW
1000 MIN. CLEARANCE
2000 MIN. CLEARANCE
OPA 1370RKTMG-PZ
Not to Scale
POINT LOADS (kg)
U V W X Y Z
430 347 262 406 419 433
Net Weight 2297 kg
Note : A 2 m clearance
is required above the
exhaust air fans
690
ECONOMISER
WEATHER
HOOD
2320
OVERALL
184
2150 CENTRES
4668 OA
2150 CENTRES
184
1710
380
100
250
617
617
230
225
OPA 1370RKTMG-P – Wiring Diagram Part 1, of 3
Spec data updated.
©temperzone Ltd 2017
SHEET OF
31
CP2W1
F
5-D
H
5-D
CBL15
TFC1
IFM4
230V
CBL20
C8
1-B
B7
1-A
A7
1-A
CBL6
IFM3
L
TB8
MAINS
TFC
settings- Refer table
For SW2 (DIP switch)
FAN
output
R
N
2-D
E
N
TW1
TW2
3-D
TB9
CBL7
IFM2
CBL19
C7
1-B
B6
1-A
A6
1-A
IFCB1 IFCB2
C6
1-B
B5
1-A
A5
1-A
IFM1
CBL5
OFM1
CAP
BB2
RV1
CMC1
CMC2
CBL11
CBL4
C5
1-B
B4
1-A
A4
1-A
C4
1-B
B3
1-A
A3
1-A
BB1
CMM2 CMM3 CMM4
CMOL2CMOL1 CMOL3 CMOL4
C3
1-B
B2
1-A
A2
1-A
CMC1 CMC2 CMC3 CMC4
CMCB1 CMCB2 CMCB3 CMCB4
C2
1-B
CBL1 CBL2 CBL3
Digital
CMM1
OF3&4CB
B1
1-A
OF1&2CB
A1
1-A
CMC1
CMC2
CM1
EEV1
MV
Output
Fault
Fan
A B
A B
Service
Interface
CCBSPSCB
C1
1-B
7-A
A3 4-A
A6
5-A
A5
8-A
5-A
A7
A1 2-A A2 3-A
A4
4-AB67-A
B3
B2 3-A
2-A
B1
L1
MIS TB
MIS
SPS1
4-A
6-A
C6
C3
6-A
B5
5-A
B4
L2
5-A
8-A
C2 3-A
C5
C8
2-A
4-A
8-A
B7
7-A
C1
C4
C7
L3
2
1
ETH2
ETH1
N
BB1
ETH3
ETH4
BB2
ACTIVE
TB1
ACTIVE
N1
ETH
TR
24V
230V
8-F
8-C
V
W
2
FS1FS
N2
TB2
V0-C
N
CBL11
EEV1
EEV2
UC6
24VCB
TFC2
TB10
CBL8
(Refer Table for Part No.)
RS485
L
5-D
CCH1
9-D
BMS
B
2.0-A
2.3-A
A
24V
TB3
CP2W2
G
N
RV2
G
EEV2
IFR
24V
ACTIVE
TFC
For SW2 (DIP switch)
2-D
E
CAP
CBL12 CBL12
CBL15
HR1
COMM1
settings- Refer table
O
24V
TW1
R
8-C
8-C
N
CR1 CMOL1
CR1
COMM2
TB4
I
230V
MAINS
FAN
output
OFM2
CCH2
F
H
I
CR2 CMOL2
24V
COMP1
4-D
TW2
CR2
S
9-C
9-C
9-D
UC6 1 (SYSTEMS 1 & 2)
S
8-D
8-D
O
PLCC12ER
24V
COMP2
3-D
TB11
C12ER
Sensors and Transducer
CR3
24V
COMP3
2.0-A
X
Y
*Refer Page 2
CR4
COMP4
TB5
2.0-A
24V
TFC3
TB12
CBL9
HR1
5-F
L
24V
HEAT1
K
N
HR2
HEAT2
CP2W3
24V
TFC
2-F
CAP
1K
IFR
IFM
E
For SW2 (DIP switch)
P
CMC3
24V
C
Rev:
291-000-581
Drawing No:
Technical information *Refer Page 3
E
BB1
L
5-F
CBL16
230V
MAINS
settings- Refer table
FAN
output
T
3-F
TW1
TW2
TB13
CP2W4
J
5-F
M
4-F
TFC4
230V
MAINS
TFC
W0-C
TB14
settings- Refer table
For SW2 (DIP switch)
FAN
output
U
Q
2-F
L
E
N
TW1
TW2
3-F
TB15
CBL10
OFM3
OFM4
CAP
C34ER
Wiring Schematic
N
BB2
CBL13
RV3
CMC4
CBL13
9-F
CMC4 CMC3
EEV3
EEV4
Output
Fault
UC6
Fan
EEV1
(Refer Table for Part No.)
A B
RS485
A
BMS
B
Service
Interface
D
2.0-A
2.6-A
C
9K1
Y
G
GO
DMF
DMF
HOT
DMR
COM
TB16
E
DMR
DMF
TB6
J
IFR
Cable 18
FAULT
EEV2
Return and
E
COMM
TB7
CCH3
CBL16
HR2
Economiser
Damper
TB17
OUT 1
FAULT
CR3 CMOL3
DMR
FAULT
RV4
CCH4
CBL14 CBL14
K
9-E
L
9-E
M
9-F
UC6 2 (SYSTEMS 3 & 4)
*Refer Page 2
Sensors and Transducer
T
U
8-F
8-E
8-F
8-E
P
Q
PLCC34ER
CMOL4
CR4
Y
G
GO
DMR
E
DMF
HOT
COM
Cable 17
0V
OUT 2
0-10V
OPA 1370RKTMG-PZ-UC6
Title:
27-12-2017
Date:
A.K.B
Drawn:
Apprvd:
Client Wiring
APPROVED
DATE
01-02-19 A.W.G.
SCALE - ASK
DO NOT
ECN
N4188
DESCRIPTION
C
REV
OPA 1370RKTMG-P – Wiring Diagram Part 2, of 3
©temperzone Ltd 2017
SHEET OF
32
Spec data updated.
CBL23
11 14
GND
E1
IFM 4
10V
D1
24V
C
Rev:
291-000-581
Drawing No:
Wiring Schematic
OPA 1370RKTMG-PZ-UC6
CBL22
11 14
GND
E1
IFM 3
10V
D1
24V
C
1.2-F
Title:
27-12-2017
Date:
CBL21
11 14
GND
E1
IFM 2
10V
D1
24V
A.K.B
Drawn:
Apprvd:
CBL20
11 14
GND
E1
IFM 1
10V
D1
24V
A
1.2-D
Client Wiring
APPROVED
DATE
01-02-19 A.W.G.
SCALE - ASK
DO NOT
ECN
N4188
D
1.5-E
1.4-E
1.3-D
1.3-F
IF1
FAULT
TB18
IF2
FAULT
NC7 1
FAULT
NC7 2
FAULT
TB19
FAN
FAN
GND1
GND2
FAN 1/2E1FAN 3/4
E1
X
Y
B
DESCRIPTION
C
REV
OPA 1370RKTMG-P – Wiring Diagram Part 3, of 3
©temperzone Ltd 2017
SHEET OF
33
Crankcase Heater Note
24 Hour power required (on L1)
for control curcuit and crankcase
heaters
Important Notes:
TFC Dip Switch Settings
SW1 SW2 SW3 SW4
Off Off Off Off
Important Note
Compressors fitted are directional. If
rotation incorrect, compressor/s will
not pump, be noisy, and draw
minimal current. To correct rotation,
reverse two phases.
Sensors (S) / Transducers (T)
ST1 Suction Temp S
ST2 Suction Temp S
Discharge Temp
Discharge Temp
SP1 Suction Pressure
SP2 Suction Pressure
Spec data updated.
132
134
1370RKTM
kW
OPA
37.7
kW
30.1
kW
3.55
3.54
kW/kW
kW/kW
A/Ph
15
A/Ph
15
A/Ph
15
A/Ph
65/73/73
22A x 42A32A x 4
A
A
AAA
N/A
MFD
20 x 4
4 x 4
1.9 x 415P.O.E4A10A x 2
96/105/105
4.5 x4
16A
16A
A
A
A
A/Ph
A/Ph
10A
200A
10.7
2297
A
A
A
Kg
Kg
C
Rev:
291-000-581
Drawing No:
Cooling -kWElectrical Input
Heating - Reverse Cycle
Capacities - Nett to AS/NZS 3823
C
Cooling -
E.E.R. (Cooling)
Heating - Reverse Cycle
A.E.E.R (Cooling)
Supply required 3Ph 380-415V ~ 50Hz
Electrical
Compressor 1 (3Ph) run amps rating conditions
Compressor 2 (3Ph) run amps rating conditions
Compressors type : Scroll
CM
Client Wiring
Compressor Overload settings
Compressor Circuit Breakers
Compressor 4 (3Ph) run amps rating conditions
Compressor 3 (3Ph) run amps rating conditions
CMOL
CMCB
Compressor Oil Type
Indoor Fan Motor (3Ph) kW
IFM
BB1
Indoor Fan Motor Circuit Breaker
Indoor Fan Motor (3Ph) Full Load amps
IFCB
Indoor Fan Motor Overload settings
Outdoor Fan Motor (1Ph) Full Load amps
Outdoor Fan Motor Capacitor
IFOL
L1
Outdoor Fan Motor 3 & 4 Circuit Breaker
Outdoor Fan Motor 1 & 2 Circuit Breaker
Running Amps (total)
OFCB
OFCB
Max Running Amps
L2
24 Volt Circuit Breaker
Control Circuit Breaker
Single Phase Socket Circuit Breaker
CCB
24VCB
SPSCB
L3
24 VOLT CIRCUIT BREAKER
Weight-Nett
Refrigerant Charge - per system
Main Isolator Switch
MIS
24VCB
N
BB2
Client External Protection and Isolator switch
BB BUS BAR
C12ER COMPRESSOR 1&2 ENABLE RELAY
C34ER COMPRESSOR 3&4 ENABLE RELAY
CAP CAPACITOR
CBL COMPRESSOR CABLE
CCB CONTROL CIRCUIT BREAKER
24V
24V
TB5
Fit links as shown
CCH CRANKCASE HEATER
CMC COMPRESSOR CONTACTOR
CMCB COMPRESSOR CIRCUIT BREAKER
24V
COMM
COMP2
COMP1
connected to UC6
ONLY if using TZT-100
CMM COMPRESSOR MOTOR
CMOL COMPRESSOR OVERLOAD
24V
24V
COMP3
"T/ST terminals OR a
BMS which
CR COMPRESSOR RELAY
DMF DAMPER MOTOR FRESH AIR
24V
COMP4
the UC6 via mod bus
communicates with
DMR DAMPER MOTOR RETURN AIR
24V
HEAT1
EEV ELECTRONIC EXPANSION VALVE
ETH EARTH STUD
24V
HEAT2
HR HEAT RELAY
IBB INSULATED BUS BAR
IFC INDOOR FAN CONTACTOR
IFM
24V
IFCB INDOOR FAN CIRCUIT BREAKER
IFM INDOOR FAN MOTOR
IFOL INDOOR FAN OVERLOAD
IFR INDOOR FAN RELAY
MIS MAIN ISOLATOR SWITCH
MV MODULATING VALVE
OFCB OUTDOOR FAN CIRCUIT BREAKER
OFM OUTDOOR FAN MOTOR
PRC PHASE ROTATION CONTROLLER
PLR PHASE LOSS RELAY
RV REVERSING VALVE
SPSCB SINGLE PHASE SOCKET CIRCUIT BREAKER
SPS SINGLE PHASE SOCKET
TERMINAL JOINER
UNIT CONTROLLER 6 (201-000-485)
TFC TRIAC FAN CONTROLLER
TJ
TR TRANSFORMER
UC6
Title:
Wiring Schematic
OPA 1370RKTMG-PZ UC6
27-12-2017
Date:
A.K.B
Drawn:
Apprvd:
02/19 Pamphlet No. 3986
1)
2)
Client Wiring
APPROVED
DATE
01-02-19 A.W.G.
SCALE - ASK
DO NOT
ECN
BLUE
T
T
High Pressure
High Pressure
HP1
HP2
S
De-ice Temp
TS1
BLUE
S
S YELLOW
De-ice Temp
Ambient Temp
TS2
OAT
BLUE
BLUE
Colour
S GREY
S GREY
T
DT1
T
DT2
Type
Name
3)
N4188
DESCRIPTION
C
REV
© temperzone limited 2019
Loading...