
OPA 1370RKTMG01-PZ (Digital c/w Plug fan and Economiser)
Packaged Reverse Cycle R410A
Air Cooled Air Conditioner
GENERAL
This OPA 1370RKTMG Outdoor Unit must
be installed in accordance with all national
and local safety codes.
OPTION
1. TZT-100 Room Temperature Controller
(eld tted).
2. Viking Controller for Economiser with
enthalpy control (factory tted).
REFRIGERATION SYSTEM
General
The OPA 1370 has four independent
refrigeration circuits and four compressors
to provide the exibility and economy of
four stage operation, i.e. utilising one to
four circuits as conditions vary, plus the
advantage of staggered starting.
Each refrigeration system has been
charged with HFC-410A (R410A)
refrigerant; refer wiring diagram
specication table for amount. Tapping
points are provided to measure discharge
and suction operating pressures.
Compressors
The compressors are directional scroll
type. One of the four compressors is digital
scroll type. This has a variable capacity
ability that enables closer control of room
temperature.
The compressor lubricant is polyol ester
oil (POE). Note, this oil absorbs moisture
quickly if exposed to open air. On
commissioning, the compressors must be
checked for correct rotation (refer Start
Up Procedure). A time delay prevents
simultaneous starting of the compressors.
ECONOMISER
The economiser fresh air intake cowl with
water separator is supplied separately and
is best tted after the OPA is mounted on
it's platform. Fitting instructions are supplied
with the cowl.
Controls may be supplied by others. If the
outdoor air temperature or heat content
preferably, is below that of the return air
the fresh air damper opens and the return
air damper closes to provide the rst stage
of cooling. A spill air facility in the building
may be necessary for when the return air
damper is closed. The fresh air damper
should return to minimum setting and the
return air damper open before compressors
are allowed to operate to provide further
cooling.
INSTALLATION
Positioning
Refer to dimension diagrams for minimum
clearances. If multiple units are to be
placed side-by-side then allow at least 2 m
between coil faces.
Mounting
The unit should be fastened to a rm at
horizontal base using the holes supplied in
the mounting channels.
When the unit is being installed on a roof
it is recommended that the unit is installed
on a substantial structure with anti-vibration
mounts or pads.
Flexible duct connections are recommended
between the supply and return ducts and
the unit.
Condensate Drain
The condensate drain should be 'U' trapped
outside the unit. The trap should have a
vertical height of at least 100 mm. The drain
should have a slope of at least 1 in 50 and
must not be piped to a level above the unit
drain pipe.
OPEN
DRAIN
VENT PIPE
FOR LONG
CONDENSATE
DRAIN RUNS
100 mm
APPROX.
100 mm
MINIMUM
200 mm
APPROX.
'U' TRAP
Electrical Requirements
Electrical work must be done by a qualied
electrician. The outdoor unit must be wired
directly from a distribution board by means
of a circuit breaker or H.R.C. fuse, and a
mains isolator provided - preferably close to
the unit.
Note: DO NOT USE REWIRABLE FUSES.
The OPA 1370 is provided with a 24V AC
control circuit for a thermostat, on/off switch
and/or time clock.
Standard units are suitable for use with
thermostats with either manual Heat/Cool
selection or automatic changeover subject to
the contact ratings of the thermostats.
The system is set up for the compressors to
be controlled variably by:
1. TZT-100 Controller (via RS485 modbus),
2. 0-10V dc command via BMS modbus, or
3. 0-10V dc command via a client supplied
external controller.
If option 1 is chosen, then disconnect or
remove the Signal Input for Controller 0-10V.
If a TZT-100 Controller is used then variable
capacity control is automatically included
and no additional wiring is required.
A 24 hour power supply to the control circuit
is required, otherwise the warranty is void.
SETTING SUPPLY AIR FLOW
Consult OPA 1370 Technical Data pamphlet
at www.temperzone.biz for details of airow/
duct static pressure, if required.
MINIMUM
SLOPE
20 mm PER m
(1 IN 50)
Installation &
Maintenance
If the indoor air returning to the unit is
regularly expected to be above 50%RH,
then the coil face velocity should be limited
to be 2.5 m/s or less (refer Air Handling
graph in Technical Data pamphlet).
High humidity levels can occur in tropical or
subtropical conditions, and/or when heavily
moisture laden fresh air is introduced.
Select a fan speed that avoids water carryover problems.
INDOOR FAN SPEED
The fan speed is continuously variable
via the 0-10V DC control signal applied
between terminals 'FAN GND' and '0–10V'.
Once the maximum design air ow has
been set, a variable fan speed can be
controlled as follows by applying an external
variable 0–10V DC control voltage to
'0–10V' terminal. Connect 0V reference to
'FAN GND'.
CHECK TESTS
1. Check that all the shipping bolts on the
back of the compressor frame have been
removed and that the compressor is
secure on its mounts.
2. Check by hand that all fan motors can
turn freely.
3. Check that the air lters have been
correctly installed, if tted.
4. Check air diffuser dampers are open if
appropriate.
5. Check that the thermostat, or external
24V controller, is correctly wired to
the unit and is set at the desired
temperature.
6. Check the tightness of all electrical
connections.
7. Leave the thermostat, or external 24V
controller, in the off position and close
the mains isolating switch. (A four hour
delay period is required to allow the
crankcase heater to drive any liquid
refrigerant out of the compressor oil.)
8. Check the supply voltage between each
phase and neutral.
START UP PROCEDURE
After the four hour delay for the crankcase
heater has expired, use the supplied
Commissioning Sheet (Form NS 228) to
record results when completing the following
‘Start-up’ procedure. A UC6 Service
Interface tool is supplied to read, pressures,
superheat and its set-point, compressor
amps etc.
1. Select a sensible Fan speed (or Auto
Fan mode), operating cycle (cool or
heat), and room temperature set point,
depending on the time of year, such that
the compressor will start and run at a
high capacity.
2. Turn ON the thermostat / external
controller. Wait for the compressor to

start. Measure the current for each
phase feeding into the compressor’s.
Compare against the compressor amps
specied on the unit’s wiring diagram.
3. Compressors tted are directional. Check
for correct rotation. If rotation is incorrect
the compressor will not pump, be noisy,
and will draw minimal current. To correct
motor rotation, change the phasing at
the main power terminal. If changing the
phasing, check the indoor air fan then
runs in the correct direction also.
4. Measure the current draw of each fan
motor. Check all readings against the
specied values in the wiring diagram.
5. Use the UC6 Service Interface tool to
check operating pressures and status.
If the UC6 Service Interface is not
available, t gauges and measure the
suction and discharge pressures of both
refrigeration circuits.
6. Check that the outdoor air fan motors are
running smoothly and drawing less than
the full load amps specied.
7. Check the indoor unit's fan belt tension
after 20 mins of operation and adjust if
necessary (refer Commissioning Sheet).
8. Test the operation of the reversing valve
by running the unit in both the heating
and cooling mode.
9. Check the supply air ow at each outlet.
10. Touch up any outdoor unit paintwork
damage to prevent corrosion.
UNIT CONTROLLER (UC6)
The Unit Controller provides system
protection functions such as coil frost
protection, de-icing, high head pressure
and low suction pressure cut-out. It
also protects against rapid cycling of the
compressor and loss of refrigerant. The UC
regulates the superheat of the refrigeration
system by controlling the position of an
Electronic Expansion Valve (EEV). Various
methods of head pressure control (or
limiting) are employed in temperzone units
including in this particular unit, variation
of compressor speed. The particular
method used varies from model to model,
but is handled by the Unit Controller.
In combination, these features deliver
optimised performance across a wide
operating temperature range.
Refer to UC6 Controller label on the unit for
operation & fault diagnostics information.
Many operating status conditions can be
determined, without gauges, simply by using
the UC6 Service Interface graphical display
supplied with the unit.
MAINTENANCE
Monthly
1. Check air lters, if tted, and vacuum or
wash clean as necessary.
2. Check condensate drain for free
drainage.
3. Check compressor compartment for oil
stains indicating refrigerant leaks.
Six Monthly
1. Check the tightness of electrical
connections.
2. Check the tightness of all fans and motor
mountings.
3. Check suction and discharge operating
pressures. (Using the UC6 Service
Interface avoids tting and removing
gauges with consequential refrigerant loss.)
5. Check condensate drain for free drainage.
Yearly
1. Check all refrigerant piping for chang
and vibration.
2. Check the operation of electric heaters,
if tted.
3. Check air supply at all diffusers.
4. Check for excessive noise and vibration
and correct as necessary.
5. Check for insulation and duct damage
and repair as necessary.
6. Remove lint and dust accumulation from
outdoor coil ns.
7. Touch up any paintwork damage to
prevent corrosion.
NOTE
The manufacturer reserves the right to
make changes in specications at any time
without notice or obligation. Certied data is
available on request.
DIMENSIONS (mm)
OPA 1370RKTMG01-PZ – Horizontal Supply & Return Air
1000 MIN. CLEARANCE
FILTER
ACCESS PANEL
FAN
ACCESS
DOOR
W
RETURN
AIR
DRAIN
11/2" BSP
MALE
MOUNTING
CENTRES
SUPPLY
AIR
2260
UV
ELECTRICAL
ACCESS
DOOR
2430 OA
1000 MIN. CLEARANCE
ELECTRICAL
ACCESS
DOOR
ZYX
OUTDOOR
AIR FLOW
OUTDOOR
AIR FLOW
1000 MIN. CLEARANCE
2000 MIN. CLEARANCE
OPA 1370RKTMG-PZ
Not to Scale
POINT LOADS (kg)
U V W X Y Z
430 347 262 406 419 433
Net Weight 2297 kg
Note : A 2 m clearance
is required above the
exhaust air fans
690
ECONOMISER
WEATHER
HOOD
2320
OVERALL
184
2150 CENTRES
4668 OA
2150 CENTRES
184
1710
380
100
250
617
617
230
225

OPA 1370RKTMG-P – Wiring Diagram Part 3, of 3
Crankcase Heater Note
24 Hour power required (on L1)
for control curcuit and crankcase
heaters
Important Notes:
TFC Dip Switch Settings
SW1 SW2 SW3 SW4
Off Off Off Off
Important Note
Compressors fitted are directional. If
rotation incorrect, compressor/s will
not pump, be noisy, and draw
minimal current. To correct rotation,
reverse two phases.
Sensors (S) / Transducers (T)
132
134
1370RKTM
kW
OPA
37.7
kW
30.1
kW
3.55
3.54
kW/kW
kW/kW
A/Ph
15
A/Ph
15
A/Ph
15
A/Ph
65/73/73
22A x 42A32A x 4
A
A
AAA
N/A
MFD
20 x 4
4 x 4
1.9 x 415P.O.E4A10A x 2
96/105/105
4.5 x4
16A
16A
A
A
A
A/Ph
A/Ph
10A
200A
10.7
2297
A
A
A
Kg
Kg
C
Rev:
291-000-581
Drawing No:
Cooling -kWElectrical Input
Heating - Reverse Cycle
Capacities - Nett to AS/NZS 3823
C
Cooling -
E.E.R. (Cooling)
Heating - Reverse Cycle
A.E.E.R (Cooling)
Supply required 3Ph 380-415V ~ 50Hz
Electrical
Compressor 1 (3Ph) run amps rating conditions
Compressor 2 (3Ph) run amps rating conditions
Compressors type : Scroll
CM
Client Wiring
Compressor Overload settings
Compressor Circuit Breakers
Compressor 4 (3Ph) run amps rating conditions
Compressor 3 (3Ph) run amps rating conditions
CMOL
CMCB
Compressor Oil Type
Indoor Fan Motor (3Ph) kW
IFM
BB1
Indoor Fan Motor Circuit Breaker
Indoor Fan Motor (3Ph) Full Load amps
IFCB
Indoor Fan Motor Overload settings
Outdoor Fan Motor (1Ph) Full Load amps
Outdoor Fan Motor Capacitor
IFOL
L1
Outdoor Fan Motor 3 & 4 Circuit Breaker
Outdoor Fan Motor 1 & 2 Circuit Breaker
Running Amps (total)
OFCB
OFCB
Max Running Amps
L2
24 Volt Circuit Breaker
Control Circuit Breaker
Single Phase Socket Circuit Breaker
CCB
24VCB
SPSCB
L3
24 VOLT CIRCUIT BREAKER
Weight-Nett
Refrigerant Charge - per system
Main Isolator Switch
MIS
24VCB
N
BB2
Client External Protection and Isolator switch
BB BUS BAR
C12ER COMPRESSOR 1&2 ENABLE RELAY
C34ER COMPRESSOR 3&4 ENABLE RELAY
CAP CAPACITOR
CBL COMPRESSOR CABLE
CCB CONTROL CIRCUIT BREAKER
24V
24V
TB5
Fit links as shown
CCH CRANKCASE HEATER
CMC COMPRESSOR CONTACTOR
CMCB COMPRESSOR CIRCUIT BREAKER
24V
COMM
COMP2
COMP1
connected to UC6
ONLY if using TZT-100
CMM COMPRESSOR MOTOR
CMOL COMPRESSOR OVERLOAD
24V
24V
COMP3
"T/ST terminals OR a
BMS which
CR COMPRESSOR RELAY
DMF DAMPER MOTOR FRESH AIR
24V
COMP4
the UC6 via mod bus
communicates with
DMR DAMPER MOTOR RETURN AIR
24V
HEAT1
EEV ELECTRONIC EXPANSION VALVE
ETH EARTH STUD
24V
HEAT2
HR HEAT RELAY
IBB INSULATED BUS BAR
IFC INDOOR FAN CONTACTOR
IFM
24V
IFCB INDOOR FAN CIRCUIT BREAKER
IFM INDOOR FAN MOTOR
IFOL INDOOR FAN OVERLOAD
IFR INDOOR FAN RELAY
MIS MAIN ISOLATOR SWITCH
MV MODULATING VALVE
OFCB OUTDOOR FAN CIRCUIT BREAKER
OFM OUTDOOR FAN MOTOR
PRC PHASE ROTATION CONTROLLER
PLR PHASE LOSS RELAY
RV REVERSING VALVE
SPSCB SINGLE PHASE SOCKET CIRCUIT BREAKER
SPS SINGLE PHASE SOCKET
TERMINAL JOINER
UNIT CONTROLLER 6 (201-000-485)
TFC TRIAC FAN CONTROLLER
TJ
TR TRANSFORMER
UC6
Title:
Wiring Schematic
OPA 1370RKTMG-PZ UC6
27-12-2017
Date:
A.K.B
Drawn:
Apprvd:
02/19 Pamphlet No. 3986
1)
2)
Client Wiring
APPROVED
DATE
01-02-19 A.W.G.
SCALE - ASK
DO NOT
ECN
BLUE
T
T
High Pressure
High Pressure
HP1
HP2
S
De-ice Temp
TS1
BLUE
S
S YELLOW
De-ice Temp
Ambient Temp
TS2
OAT
BLUE
BLUE
Colour
S GREY
S GREY
T
DT1
T
DT2
Type
Name
3)
N4188
DESCRIPTION
C
REV
© temperzone limited 2019