TemperZone OPA 116RKTYH, OPA 161RKTYH Installation & Maintenance

OPA 116RKTYH (c/w EC motor)
Packaged Reverse Cycle R410A Air Cooled Air Conditioner
Installation & Maintenance
in the wiring schematic. 24V AC or DC power from the external (BMS) controller should be provided to the '24V' and '0V' input terminals of the Signal Isolator board.
A voltage below 2V DC applied across
the '0V' and the '0-10V' input terminals (labelled 'From BMS Controller' in the wiring schematic) of the Signal Isolator will stop the indoor fan. A control voltage of slightly more than 2V will cause the fan to run at the 'Min. rpm' speed. A 10V DC signal will run the fan at the 'Max. rpm' speed. Control voltages between these two limits can be used to achieve any desired speed between 'Min.' and 'Max.' rpm.
Do not use switch combinations
marked with 'DO NOT USE' in the Speed Selection table.
If the air returning to the indoor unit is regu­larly expected to be above 50%RH, then the coil face velocity should be limited to be
2.5 m/s or less (refer Air Handling graph in Technical Data pamphlet).
High humidity levels can occur in tropical or subtropical conditions, and/or when heavily moisture laden fresh air is introduced. Select a fan speed that avoids water carry-over
problems.
CHECK TESTS
1. Leave the remote switch in the off position and close the mains isolating switch.
A four hour delay period is required to
allow the crankcase heater to drive any liquid refrigerant out of the compres­sor oil. Bypass the crankcase heater thermostat (CCHT) for this period only.
2. Check that all fan motors are free run­ning.
3. Check that the thermostat is correctly wired to the unit and is set at the desired temperature.
4. Check that the air filters, if any, have been correctly installed.
5. Check any supply air diffuser dampers are open.
START UP PROCEDURE
Use the supplied Commissioning Sheet to help you complete the following procedure:
1. Switch on the unit after the four hour delay period for the crankcase heater has expired. Ensure the crankcase heater thermostat has been reconnected.
2. Check for correct rotation of the compressor. If rotation is incorrect the compressor will not pump, be noisy, and
REFRIGERATION SYSTEM
General
The refrigeration system has been charged with R410A refrigerant; refer wiring diagram specification table for amount. Tapping points are provided to measure discharge and suction operating pressures. Beware of high system pressures; use correct guages.
Compressor
The compressor is directional scroll type. The compressor lubricant is polyol ester oil (POE). Note, this oil absorbs moisture quick­ly if exposed to open air. On commissioning, the compressor must be checked for correct rotation (refer Start Up Procedure).
ELECTRICAL REQUIREMENTS
Electrical work must be done by a qualified electrician. The outdoor unit must be wired directly from a distribution board by means of a circuit breaker or H.R.C. fuse, and a mains isolator provided - preferably close to the unit. Note: DO NOT USE REWIRABLE FUSES.
Standard units are suitable for use with thermostats with either manual Heat/Cool selection or automatic changeover subject to the contact ratings of the thermostats.
Refer to separate pamphlet for approved thermostats, or contact the manufacturer's nearest sales office.
A 24 hour power supply to the crankcase heaters is required, otherwise the warranty is void.
INDOOR FAN SPEED
The indoor fan speed can be 'Stepped' or 'Continuously Variable'. The choice is made using Switch 1 of 'DIP1' on the EC Motor Controller. Switches 1 to 5 on 'DIP2' determine the minimum and maximum fan speeds.
The same 'Minimum rpm' and 'Maximum rpm' settings apply to 'Stepped' and 'Continuously Variable'.
The default settings for DIP1 and DIP2 are highlighted on the Wiring Schematic.
1. Stepped (DIP1 switch 1 = OFF) Connecting the 24V AC power from the
unit’s 'HOT 24V' terminal to one (and only one at a time) of the 'LOW 24V' / 'MED 24V' / 'HIGH 24V' terminals, selects the 'LOW' (Min. rpm), 'HIGH' (Max. rpm), or 'MED' (mid-way between) fan speed. The transitions between speeds are smooth.
2. Continuously Variable (DIP1 switch 1=ON) When using this method a temperzone
Analog Signal Isolator (No. 201-000-129) must be fitted and connected as shown
GENERAL
This OPA 116 unit must be installed in ac­cordance with all national and local safety codes.
OPTION (Field Fitted)
1. SAT-2 Controller 230V kit
2. Electric heat kit.
INSTALLATION
Positioning
Refer to dimension diagram for minimum clearances. If multiple units are to be placed side-by-side then allow at least 2 m between coil faces.
Mounting
Fasten the unit down to a firm flat horizontal base using the four holes provided in the mounting rails.
When the unit is being installed on a roof it is recommended that the unit is installed on a substantial structure with vibration isolat­ing springs beneath the unit. These springs are not supplied with the unit.
Flexible duct connections are recommended between the supply and return ducts and the unit.
Condensate Drain
The condensate drain should be 'U' trapped outside the unit. The trap should have a vertical height of at least 50 mm. The drain should have a slope of at least 1 in 50 and must not be piped to a level above the unit drain pipe.
For long condensate pipe runs, fit a vent pipe near the drain trap. The top of the vent pipe must be at least 100 mm above the OPA unit's drain tray.
Air Filteration
Air filters are not supplied. If filters are to be installed upstream on the return air side of the unit, they should be sized twice the area of the return air spigot.
OPEN DRAIN
MINIMUM SLOPE 20 mm PER m (1 IN 50)
50 mm MINIMUM
100 mm
APPROX.
'U' TRAP
100 mm
APPROX.
VENT PIPE FOR LONG CONDENSATE DRAIN RUNS
UNIT
Dimensions (mm)
OPA 116RKTYH
PROJECTION
Not to Scale
SUPPLY
AIR
RETURN
AIR
1154
MOUNTING CENTRES
1110
OVERALL
1200
OVERALL
OUTDOOR
AIR FLOW
1000 MIN. CLEARANCE
500 MIN. CLEARANCE
X
YZ
W
OUTDOOR
AIR FLOW
ELECTRICAL ACCESS PANEL
60
225
140
285
35
105
ACCESS
PANEL
80
2000 MIN. CLEARANCE
135
915
OVERALL
160
OPTIONAL
FILTER BOX
1055
860
675
MOUNTING CENTRES
12 DIA. HOLES
DRAIN 15 BSPF
12
ELECTRICAL HOLES 25 DIA.
187
POINTLOads(kg) WEIGHT
W X Y Z (kg)
25 57 42 69 193
will draw minimal current. To correct motor rotation, change the phasing at the main power terminal.
3. Check the supply voltage.
4. Measure the current draw on the compressor motor and on each fan motor. Check all readings against the specified values - particularly the indoor fan amps if the unit is installed in a free blow application.
5. Fit R410A compatible gauges and measure the suction and discharge pressures.
6. Test the operation of the high pressure safety control by switching off the outdoor air fan.
7. Test the operation of the reversing valve by running the unit in both the heating and cooling mode.
8. Check that the motors are running smoothly.
9. Check the supply air flow at each outlet.
10. Touch up any outdoor unit paintwork damage to prevent corrosion.
OUTDOOR UNIT CONTROLLER (OUC)
The Outdoor Unit Controller (OUC) includes a temperature sensing head pressure control which enables the system to com­pensate for outdoor ambient temperatures
below 20°C on cooling cycle, and above 15°C on heating cycle. The OUC also has features which protect against icing or overheating of coils, rapid cycling of the compressor and loss of refrigerant charge.
If the outdoor unit fans take some time to begin rotating when the system is powered on, or they don't appear to be rotating appropriately while the compressor is running, consult the OUC label on the electrical box. If necessary, refer to temperzone for further diagnostic information.
MAINTENANCE
Weekly For First Four Weeks
1. Check indoor air filters (if fitted) and vacuum or wash clean as necessary.
2. Check condensate drain for free drainage.
3. Check compressor compartment for oil stains indicating refrigerant leaks.
4. Check tightness of electrical connections.
Six Monthly
1. Check the tightness of all fan and motor mountings.
2. Check tightness of electrical connections.
3. Check suction and discharge operating pressures.
4. Replace indoor unit air filters (if fitted).
5. Check condensate drain for free drainage.
Yearly
1. Check all refrigerant piping for chafing and vibration.
2. Check the operation of electric heaters, if fitted.
3. Check air supply at all diffusers.
4. Check for excessive noise and vibration and correct as necessary.
5. Check for insulation and duct damage and repair as necessary.
6. Remove lint and dust accumulation from outdoor coil fins.
7. Touch up any outdoor unit paintwork damage to prevent corrosion.
NOTE
The manufacturer reserves the right to change specifications at any time without notice or obligation. Certified dimensions available on request.
© temperzone limited 201111/11 Pamphlet No. 3719
Loading...