(Always read these instructions before using the equipment.)
Do not attempt to install, ope rate, maint ain or inspect the servo amplif ier and servo m otor until you hav e read
through this I nstruction M anual, Insta llation guid e, Servo motor Instructio n Manual and appen ded docum ents
carefully and can us e th e equ i pment correctl y. D o no t us e t he s er vo amplifier an d servo motor un ti l you have a
full knowledge of the equipment, safety information and instructions.
In this Instruction Manual, the safety instruction levels are classified into "WARNING" and "CAUTION".
Indicates that incorrect handling may cause hazardous conditions,
WARNING
CAUTION
Note that the CAUTION level may lead to a serious consequence according to conditions. Please follow the
instructions of both levels because they are important to personnel safety.
What must not be done and what must be done are indicated by the following diagrammatic symbols:
resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions,
resulting in medium or slight injury to personnel or may cause physical
damage.
: Indicates what must not be done. For example, "No Fire" is indicated by
: Indicates what must be done. For example, grounding is indicated by
In this Instructi on Manual, ins tructions at a lo wer level t han the abo ve, instruc tions for other func tions, an d so
on are classified into "POINT".
After reading this Instruction Manual, always keep it accessible to the operator.
.
.
A - 1
1. To prevent electric shock, note the following:
WARNING
Before wiring or inspection, switch power off and wait for more than 10 minutes. Then, confirm the voltage
is safe with voltage tester. Otherwise, you may get an electric shock.
Connect the serv o a mpl i fie r and se rvo mot o r to grou nd .
Any person who is involved in wiring and inspection should be fully competent to do the work.
Do not attempt to wire the servo amplifier and servo motor until they have been installed. Otherwise, you
may get an electric shock.
Operate the switches with dry hand to prevent an electric shock.
The cables should not be damaged , stressed, loaded, or pinched. Othe rwi se, you may get an ele ctric shoc k.
During power- on or o perat ion, do not op en t he front c over of th e serv o am plifi er. You m ay ge t an e lectric
shock.
Do not operate the servo amplifier with the front cover removed. High-voltage terminals and charging area
are exposed and you may get an electric shock.
Except for wiring or periodic inspection, do not remove the front cover even of the servo amplifier if the
power is off. The servo amplifier is charged and you may get an electric shock.
2. To prevent fire, note the following:
CAUTION
Do not install the servo amplifier, servo motor and regenerative brake resistor on or near combustibles.
Otherwise a fire may cause.
When the servo amplifier has become faulty, switch off the main servo amplifier power side. Continuous
flow of a large current may cause a fire.
When a regenerative brake resistor is used, use an alarm signal to switch main power off. Otherwise, a
regenerative brake transistor fault or the like may overheat the regenerative brake resistor, causing a fire.
3. To prevent injury, note the follow
CAUTION
Only the voltage specified in the Instruction Manual should be applied to each terminal. Otherwise, a burst,
damage, etc. may occur.
Connect the terminals correctly to prevent a burst, damage, etc.
Ensure that polarity ( , ) is correct. Otherwise, a burst, damage, etc. may occur.
Take safety measures, e.g. provide covers, to prevent accidental contact of hands and parts (cables, etc.)
with the servo amplifier heat sink, regenerative brake resistor, servo motor, etc.since they may be hot
while power is on or for some time after power-off. Their temperatures may be high and you may get burnt
or a parts may damaged.
During operation, never touch the rotating parts of the servo motor. Doing so can cause injury.
A - 2
4. Additional instructions
The following instructions should also be fully noted. Incorrect handling may cause a fault, injury, electric
shock, etc.
(1) Transportation and installation
CAUTION
Transport the products correctly according to their weights.
Stacking in excess of the specified number of products is not allowed.
Do not carry the servo motor by the cables, shaft or encoder.
Do not hold the front cover to transport the servo amplifier. The servo amplifier may drop.
Install the servo amplifier in a load-bearing place in accordance with the Instruction Manual.
Do not climb or stand on servo equipment. Do not put heavy objects on equipment.
The servo amplifier and servo motor must be installed in the specified direction.
Leave specified clearances between the servo amplifier and control enclosure walls or other equipment.
Do not install or operate the servo amplifier and servo motor which has been damaged or has any parts
missing.
Provide adequate protection to prevent screws and other conductive matter, oil and other combustible
matter from entering the servo amplifier.
Do not drop or strike servo amplifier or servo motor. Isolate from all impact loads.
When you keep or use it, please fulfill the following environmental conditions.
Environment
During
Ambient
temperature
Ambient
humidity
AmbienceIndoors (no direct sunlight) Free from corrosive gas, flammable gas, oil mist, dust and dirt
AltitudeMax. 1000m (3280 ft) above sea level
(Note)
Vibration
Note. Except the servo motor with reduction gear.
operation
In storage
During
operation
In storage90%RH or less (non-condensing)
[ ]0 to 55 (non-freezing)0 to 40 (non-freezing)
] 32 to 131 (non-freezing)32 to 104 (non-freezing)
[
[ ]20 to 65 (non-freezing)15 to 70 (non-freezing)
[
]4 to 149 (non-freezing)5 to 158 (non-freezing)
90%RH or less (non-condensing)80%RH or less (non-condensing)
[m/s2]5.9 or less
2
]19.4 or less
[ft/s
Servo amplifierServo motor
Conditions
HC-KFS Series
HC-MFS Series
HC-UFS13 to 73
HC-SFS52 to 152
HC-SFS53 to 153
HC-RFS Series
HC-UFS 72
HC-SFS121 201
HC-SFS202
HC-SFS203
HC-UFS202 to 502
HC-SFS301
HC-SFS502 to 702
HA-LFS11K2 to 22K2
HC-KFS Series
HC-MFS Series
HC-UFS 13 to 73
HC-SFS52 to 152
HC-SFS53 to 153
HC-RFS Series
HC-UFS 72
HC-SFS121 201
HC-SFS202
HC-SFS203
HC-UFS202 to 502
HC-SFS301
HC-SFS502 to 702
HA-LFS11K2 to 22K2
HC-SFS81
HC-SFS81
152
352
353
152
352
353
X
Y : 49
Y : 24.5
X
X : 24.5
Y : 49
X : 24.5
Y : 29.4
X : 11.7
Y : 29.4
X
Y : 161
Y : 80
X
X : 80
Y : 161
X : 80
Y : 96
X : 38
Y : 96
A - 3
CAUTION
Securely attach the servo motor to the machine. If attach insecurely, the servo motor may come off during
operation.
The servo motor with reduction gear must be installed in the specified direction to prevent oil leakage.
Take safet y m easur es , e .g. provide cover s, to prevent ac ci de nt al ac c ess to the rotating p ar ts of the s ervo
motor during operation.
Never hit the servo motor or shaft, especially when coupling the servo motor to the machine. The encoder
may become faulty.
Do not subject the servo motor shaft to more than the permissible load. Otherwise, the shaft may break.
When the equipment has been stored for an extended period of time, consult Mitsubishi.
(2) Wiring
CAUTION
Wire the equipment correctly and securely. Otherwise, the servo motor may misoperate.
Do not install a power capacitor, surge absorb er or radio nois e filter (FR-BI F option) bet ween the servo
motor and servo amplifier.
Connect the output terminals (U, V, W) correctly. Otherwise, the servo motor will operate improperly.
Do not connect AC power directly to the servo motor. Otherwise, a fault may occur.
The surge abs orb ing d iod e ins ta lled on t he DC ou tput sign al r ela y of th e s erv o am plifie r m ust be wir ed in
the specified direction. Otherwise, the forced stop (EM1) and other protective circuits may not operate.
Servo
Amplifier
(24VDC)
Control
output
signal
COM
RA
Servo
Amplifier
(24VDC)
Control
output
signal
COM
RA
(3) Test run adjustment
CAUTION
Before operat ion, check the par ameter setti ngs. Im proper sett ings m ay cause som e mac hines to p erform
unexpected operation.
The parameter settings must not be changed excessively. Operation will be insatiable.
A - 4
(4) Usage
CAUTION
Provide a forced stop circuit to ensure that operation can be stopped and power switched off immediately.
Any person who is involved in disassembly and repair should be fully competent to do the work.
Before resetting an alarm, make sure that the run signal of the servo amplifier is off to prevent an
accident. A sudden restart is made if an alarm is reset with the run signal on.
Do not modify the equipment.
Use a noise filter, etc. to minim i ze the inf lue nce of electr om agne tic int erfer enc e, wh ich m ay b e ca use d b y
electronic equipment used near the servo amplifier.
Use the servo amplifier with the specified servo motor.
The electromagnetic brake on the servo motor is designed to hold the motor shaft and should not be used
for ordinary braking.
For such reas ons as servic e life and mec hanical struc ture (e.g. wher e a ballscrew and the s ervo motor
are coupled via a tim ing belt) , the e lectrom agnet ic br ake m ay not ho ld the m otor shaf t. To ens ure saf ety,
install a stoppe r on the machin e si de.
(5) Corrective actions
CAUTION
When it is ass umed that a hazardous c ondition m ay take place a t the occur d ue to a po wer failure or a
product fault, use a servo motor with electromagnetic brake or an external brake mechanism for the
purpose of prev en ti on .
Configure the elec trom agnetic brake circ uit so th at it is activa ted not onl y by the inter face unit s ignals but
also by a forced stop (EM1).
Contacts must be open when
servo-off, when an alarm occurrence
and when an electromagnetic brake
interlock (MBR).
Servo motor
Electromagnetic brake
When any alarm has occurred, eliminate its cause, ensure safety, and deactivate the alarm before
restarting operation.
When power is restor ed after an inst antaneous power failu re, keep away from the machine because th e
machine may be restarted suddenly (design the machine so that it is secured against hazard if restarted).
Circuit must be
opened during
forced stop (EM1).
EM1RA
24VDC
A - 5
(6) Maintenance, inspection and parts replacement
CAUTION
With age, the electrolytic capacitor of the servo amplifier will deteriorate. To prevent a secondary accident
due to a fault, it is recommended to replace the electrolytic capacitor every 10 years when used in general
environment.
Please consult our sales representative.
(7) General instruction
To illustrate details, the equipment in the diagrams of this Instruction Manual may have been drawn
without covers and safet y guards. W hen the equipm ent is operate d, the covers and safet y guards must
be installed as specified. Operation must be performed in accordance with this Instruction Manual.
About processing of waste
When you discard servo amplifier, a battery (primary battery), and other option articles, please follow the law of
each country (area).
FOR MAXIMUM SAFETY
This product is not designed or manufactured to be used in equipment or systems in situations that can
affect or enda nge r hu man li fe .
When considering this product for operation in special applications such as machinery or systems used in
passenger transportation, medical, aerospace, atomic power, electric power, or submarine repeating
applications, please contact your nearest Mitsubishi sales representative.
Although this product was manufactured under conditions of strict quality control, you are strongly advised
to install safety devices to forestall serious accidents when it is used in facilities where a breakdown in the
product is likely to cause a serious accident.
EEP-ROM life
The number of write times to the EEP-ROM, which stores parameter settings, etc., is limited to 100,000. If
the total number of the following operations exceeds 100,000, the servo amplifier and/or converter unit may
fail when the EEP-ROM reaches the end of its useful life.
Write to the EEP-R OM du e to pa ra met er se t ting ch an ge s
A - 6
COMPLIANCE WITH EC DIRECTIVES
1. WHAT ARE EC DIRECTIVES?
The EC directives were issued to standardize the regulations of the EU countries and ensure smooth
distribution of safety-guaranteed products. In the EU countries, the machinery directive (effective in
January, 1995), EMC directive (effective in January, 1996) and low voltage directive (effective in January,
1997) of the EC directives require that products to be sold should meet their fundamental safety
requirements and carry the CE marks (CE mar king). CE marking applies to machines and equipment
into which servo amplifiers have been installed.
(1) EMC directive
The EMC directive applies not to the servo units alone but to servo-incorporated machines and
equipment. This requires the EMC filters to be used with the servo-incorporated machines and
equipment to comply with the EMC directive. For specific EMC directive conforming methods, refer to
the EMC Installation Guidelines (IB(NA)67310).
(2) Low voltage di re ctiv e
The low voltage directive applies also to servo units alone. Hence, they are designed to comply with
the low voltage directive.
This servo is certified by TUV, third-party assessment orga nization, to comply with the low voltage
directive.
(3) Machine directive
Not being machines, the servo amplifiers need not comply with this directive.
2. PRECAUTIONS FOR COMPLIANCE
(1) Servo amplifiers and servo motors used
Use the servo amplifiers and servo motors which comply with the standard model.
Servo amplifier:MR-J2S-10B to MR-J2S-22KB
MR-J2S-10B1 to MR-J2S-40B1
Servo motor:HC-KFS
HC-MFS
HC-SFS
HC-RFS
HC-UFS
HA-LFS
HC-LFS
(2) Configuration
Control box
Reinforced
(Note)
Reinforced
insulating
transformer
No-fuse
breaker
NFB
Magnetic
contactor
MC
insulating type
24VDC
power
supply
Servo
amplifier
Servo
motor
M
Note. The insulating transformer is not required for the 11kW or more servo amplifier.
(3) Environment
Operate the servo amplifier at or above the contamination level 2 set forth in IEC60664-1. For this
purpose, install the servo amplifier in a control box which is protected against water, oil, carbon, dust,
dirt, etc. (IP54).
A - 7
(4) Power supply
(a) Operate the servo amplifier 7kW or less to meet the requirements of the overvoltage category II set
forth in IEC60664-1. For this purpose, a reinforced insulating transformer conforming to the IEC
or EN standard should be used in the power input section.
Since the 11kW or more servo amplifier can be used under the conditions of the overvoltage
category III set forth in IE644, a reinforced insulating transformer is not required in the power
input section.
(b) When supplying interface power from external, use a 24VDC power supply which has been
insulation-reinforced in I/O.
(5) Grounding
(a) To prevent an electric shock, always connect the protective earth (PE) terminals (marked
servo amplifier to the protective earth (PE) of the control box.
(b) Do not connect two ground cables to the same protective earth (PE) terminal Always connect the
cables to the terminals one-to-one.
) of the
PE terminals
PE terminals
(c) If a leakage current breaker is used to prevent an electric shock, the protective earth (PE)
terminals of the servo amplifier must be connected to the corresponding earth terminals.
(6) Wiring
(a) The cables to be connected to the terminal block of the servo amplifier must have crimping
terminals provided with insulating tubes to prevent contact with adjacent terminals.
Crimping terminal
Insulating tube
Cable
(b) Use the servo motor side power connector which complies with the EN Standard. The EN Standard
compliant power connector sets are available from us as options.
(7) Auxiliary equipment and options
(a) The no-fuse breaker and magnetic contactor used should be the EN or IEC standard-compliant
products of the models described in Section 12.2.2.
(b) The sizes of the cables described in Section 12.2.1 meet the following requirements. To meet the
other requirements, follow Table 5 and Appendix C in EN60204-1.
Ambient tempera t ur e: 40 (104 ) [ ( )]
Sheath: PVC (polyvinyl chloride)
Installed on wall surface or open table tray
(c) Use the EMC filter for noise reduction.
(8) Performing EMC tests
When EMC tests are ru n on a machine/device in to which the servo amplifier has been installed, i t
must conform to the electromagnetic compatibility (immunity/emission) standards after it has
satisfied the operating environment/electrical equipment specificati ons.
For the other EMC directive guidelines on the servo amplifier, refer to the EMC Installation
Guidelines(IB(NA)67310).
A - 8
CONFORMANCE WITH UL/C-UL STANDAR D
(1) Servo amplifiers and servo motors used
Use the servo amplifiers and servo motors which comply with the standard model.
Servo amplifier:MR-J2S-10B to MR-J2S-22KB
MR-J2S-10B1 to MR-J2S-40B1
Servo motor:HC-KFS
HC-MFS
HC-SFS
HC-RFS
HC-UFS
HA-LFS
HC-LFS
(2) Installation
3
Install a fan of 100CFM (2.8m
cooling of at least equivalent capability.
(3) Short circuit rating
This servo amplifier conforms to the circuit whose peak current is limited to 5000A or less. Having
been subjected to the short-circuit tests of the UL in the alternating-current circuit, the servo
amplifier conforms to the above circuit.
/min) air flow 4 in (10.16 cm) above the servo amplifier or provide
(4) Capacitor discharge time
The capacitor disc har ge tim e is a s listed belo w. To ensu re safety , do no t touch th e ch arg ing sec tion for
10 minutes after power-off.
Servo amplifier
MR-J2S-10B(1) 20B(1)1
MR-J2S-40B(1) 60B2
MR-J2S-70B to 350B3
MR-J2S-500B 700B5
MR-J2S-11KB4
MR-J2S-15KB6
MR-J2S-22KB8
(5) Options and auxiliary equipment
Use UL/C-UL standard-compliant products.
(6) Attachment of a servo motor
For the flange size of the machine side where the servo motor is installed, refer to “CONFORMANCE
WITH UL/C-UL STANDARD” in the Servo Motor Instruction Manual.
(7) About wiring protection
For installation in United States, branch circuit protection must be provided, in accordance with the
National Electrical Code and any applicable local codes.
For installation in Canada, branch circuit protection must be provided, in accordance with the Canada
Electrical Code and any applicable provincial codes.
Discharge time
[min]
A - 9
<<About the manual s>>
This Instruction Manua l and the MEL SERVO Se rvo Moto r Ins truc tion M anua l are re quired if yo u use
the General-Purpose AC servo MR-J2S-B for the first time. Always purchase them and use the MRJ2S-B safely.
Also read the manual of the servo system controller.
Relevant manuals
Manual nameManual No.
MELSERVO-J2-Super Series To Use the AC Servo Safely
(Packed with the servo amplifier)
MELSERVO Servo Motor Instruction ManualSH(NA)3181
EMC Installation GuidelinesIB(NA)67310
1.2 Function block diagram ..........................................................................................................................1- 2
1.3 Servo amplifier standard specifications................................................................................................1- 5
1.4 Function list.............................................................................................................................................1- 6
1.5 Model code definition ..............................................................................................................................1- 7
1.6 Combination with servo motor...............................................................................................................1- 8
1.7.1 Parts identification...........................................................................................................................1- 9
1.7.2 Removal and reinstallation of the front cover ..............................................................................1-14
1.8 Servo system with auxiliary equipment...............................................................................................1-17
3.2.1 Connectors and signal arrangements.............................................................................................3- 6
3.2.2 Signal explanations ..........................................................................................................................3- 8
3.4.1 Common line ....................................................................................................................................3-10
3.4.2 Detailed description of the interfaces............................................................................................3-11
3.5 Power line circuit....................................................................................................................................3-14
3.10 Instructions for the 3M connector.......................................................................................................3-27
3.11 Control axis selection ...........................................................................................................................3-28
1
3.12 Power line circuit of the MR-J2S-11KB to MR-J2S-22KB...............................................................3-29
3.12.1 Connection example ......................................................................................................................3-29
4.4 Test operation mode................................................................................................................................4- 6
5.3 Analog monitor .......................................................................................................................................5-11
5.4 Replacement of MR-J2-
5.4.1 Main modifications made to the parameters ................................................................................5-14
5.4.2 Explanation of the modified parameters.......................................................................................5-15
6. GENERAL GAIN ADJUSTMENT6- 1 to 6-12
B by MR-J2S- B.......................................................................................5-14
6.1 Different adjustment methods ...............................................................................................................6- 1
6.1.1 Adjustment on a single servo amplifier.......................................................................................... 6- 1
6.1.2 Adjustment using MR Configurator (servo configuration software)...........................................6- 3
6.2 Auto tuning ..............................................................................................................................................6- 4
6.2.1 Auto tuning mode .............................................................................................................................6- 4
6.2.2 Auto tuning mode operation............................................................................................................6- 5
6.2.3 Adjustment procedure by auto tuning............................................................................................6- 6
6.2.4 Response level setting in auto tuning mode...................................................................................6- 7
9.1 Alarms and warning list.........................................................................................................................9- 1
9.2 Remedies for alarms................................................................................................................................9- 2
9.3 Remedies for warnings............................................................................................................................9- 8
13.4 Confirmation of absolute position detection data.............................................................................13- 4
3
AppendixApp- 1 to App- 2
App. Combination of servo amplifier and servo motor .........................................................................App- 1
4
Optional Servo Motor Instruction Manual CONTENTS
The rough table of contents of the optional MELSERVO Servo Motor Instruction Manual is in troduced
here for your reference. Note that the contents of the Servo Motor Instruction Manual are not included in
the Servo Amplifier Instruction Manual.
1. INTRODUCTION
2. INSTALLATION
3. CONNECTORS USED FOR SERVO MOTOR WIRING
4. INSPECTION
5. SPECIFICATIONS
6. CHARACTERISTICS
7. OUTLINE DIMENSION DRAWINGS
8. CALCULA TI ON ME TH O DS F OR DES I G NI N G
5
MEMO
6
1. FUNCTIONS AND CONFIGURATION
1. FUNCTIONS AND CONFIGURATION
1.1 Introduction
The Mitsubishi MELSERVO-J2-Super series general-purpose AC servo is ba sed on the MELSERVO-J2
series and has further higher performance and higher functions.
It is connected with a servo system controller or simila r device via a serial bus (SSCNE T) and the servo
amplifier reads position data directly to perform operation.
Data from a command unit controls the speed and rotation direction of the servo motor and executes
precision positioning.
A torque limit is imposed on the servo amplifier by the clamp circuit to protect the power transistor in the
main circuit from overcurrent due to sudden acceleration/deceleration or overload. The torque limit value
can be changed to any value with an external analog input or the parameter.
As this new series has the RS-232C serial communication function, a MR Configurator (servo
configuration software)-installed personal computer or the like can be used to perform parameter setting,
test operation, status display monitoring, gain adjustment, etc.
With real-time auto tuning, you can automatically adjust the servo gains according to the machine.
The MELSERVO-J2-Super series servo motor is equipped with an absolute position encoder which has
the resolution of 131072 pulses/rev to ensure more accurate control as compared to the MELSERVO-J2
series. Simply adding a battery to the servo amplifier makes up an abso lute position dete ction system.
This makes home position return unnecessary at power-on or alarm occurrence by setting a home position
once.
1 - 1
1. FUNCTIONS AND CONFIGURATION
1.2 Function block diagram
The function block diagram of this servo is shown below.
(1) MR-J2S-350B or less
Regenerative brake option
(Note 2)
Power
NFBMC
supply
3-phase
200 to
230VAC,
1-phase
230VAC or
1-phase
100to120VAC
Servo amplifier
L
1
2
L
3
L
CHARGE
lamp
(MR-J2S-200B or more)
11
L
21
L
Regenerative
brake
Position command
input
RADS
Regenerative
TR
Control
circuit
power
supply
Model position
control
P
C
Fan
Base amplifier
Model speed
control
D
(Note 1)
Voltage
detection
Current
detector
Overcurrent
protection
encoder
Virtual
motor
Dynamic
Virtual
brake
Current
detection
U
V
W
CN2
Servo motor
U
V
W
E1
E2
Encoder
M
Electromagnetic
brake
Model
position
Actual position
control
Model
speed
Actual speed
control
Model
torque
Current
control
I/F Control
CN1ACN1B
Controller
or
Servo amplifier
RS-232C
Servo amplifier
or
termination
connector
D/A
CN3
Analog monitor
(2 channels)
Personal computer
Note:1. The built-in regenerative brake resistor is not provided for the MR-J2S-10B(1).
2. For 1-phase 230VAC, connect the power supply to L
L
is not provided for a 1-phase 100to120VAC power supply.
3
and leave L3 open.
1,L2
1 - 2
MR-BAT
CON1
Optional battery
(for absolute position
detection system)
1. FUNCTIONS AND CONFIGURATION
(2) MR-J2S-50 0B , MR - J2S - 700B
Regenerative brake option
Power
supply
3-phase
200 to
230VAC
NFBMC
Servo amplifier
L
1
2
L
3
L
11
L
21
L
Regenerative
brake
Position command
input
RADS
CHARGE
lamp
Control
circuit
power
supply
Model position
control
Regenerative
TR
Fan
Base amplifier
Model speed
control
CPN
Voltage
detection
Current
detector
Overcurrent
protection
Virtual
encoder
Virtual
motor
Dynamic
brake
Current
detection
U
V
W
CN2
Servo motor
U
V
W
E1
E2
Encoder
M
Electromagnetic
brake
Model
position
Actual position
control
CN1ACN1B
Controller
or
Servo amplifier
Model
speed
Actual speed
control
I/F Control
Servo amplifier
or
termination
connector
Model
torque
Current
control
RS-232C
CN3
D/A
Analog monitor
(2 channels)
Personal computer
MR-BAT
CON1
Optional bat t ery
(for absolute position
detection system)
1 - 3
1. FUNCTIONS AND CONFIGURATION
(3) MR-J2S-11KB or more
Regenerative brake option
Power
supply
3-phase
200 to
230VAC,
1-phase
230VAC
NFBMC
Servo amplifier
DS
L
1
L
2
L
3
L
11
21
L
Regenerative
brake
Position command
input
Control
circuit
power
supply
Model position
control
PC
CHARGE
lamp
Fan
Base
amplifier
Model speed
NP1
Voltage
detection
control
Regenrative
TR
Overcurrent
protection
Virtual
motor
Current
detector
Current
detection
Virtual
encoder
U
V
W
CN2
Servo motor
U
V
M
W
Electro-
E1
magnetic
brake
E2
Encoder
Actual position
control
I/F Control
CN1ACN1B
Controller
or
Servo amplifier
Model
position
Servo amplifier
or
termination
connector
Model
speed
Actual speed
control
Model
torque
Current
control
RS-232C
CN3CN4
D/A
MR-BAT
CON1
Optional bat t ery
(for absolute position
detection system)
Analog monitor
(2 channels)
Personal
computer
1 - 4
1. FUNCTIONS AND CONFIGURATION
1.3 Servo amplifier standard specifications
Servo Amplifier
MR-J2S-
Item
Voltage/frequency
Permissible voltage
fluctuation
Power supply
Permissible fr eq uency
fluctuation
Power supply capacityRefer to Section 11.2
Inrush currentRefer to Section 11 .5
Control systemSine-wave PWM control, curr ent c ontr ol syste m
Dynamic brakeBuilt-in
The following table lists the functions of this servo. For details of the functi ons, refer to the reference field.
FunctionDescriptionReference
High-resolution encoderHigh-resolution encoder of 131072 pulses/rev is used as a servo motor encoder.
Absolute position detection
system
Adaptive vibration
suppression control
Low-pass filter
Machine analyzer function
Machine simulation
Gain search function
Slight vibration suppression
control
Auto tuning
Regenerative brake option
Brake unit
Return conv erter
Torque limitServo motor torque can be limited to any value.
Forced stop signal automatic
ON
Output signal (DO) forced
output
Test operati on modeJOG o peration positioning operation motor-less operation DO forced output Section 4.4
Analog monitor outputServo status is output in terms of voltage in real time.Parameter No. 22
MR Configurator
(Servo configuration software)
Merely setting a home position once makes home position return unnecessary
at every power-on.
Servo amplifier detects mechanical resonance and sets filter characteristics
automatically to suppress mechanical vibration.
Suppresses high-frequency resonance which occurs as servo system response is
increased.
Analyzes the frequency characteristic of the mechanical system by simply
connecting a MR Configurator (servo configuration software)-installed personal
computer and servo amplifier.
Can simulate machine motions on a personal computer screen on the basis of
the machine analyzer results. The MR Configurator (servo configuration
software) is required.
Personal computer changes gains automatically and searches for overshootfree gains in a short time. The MR Configurator (servo configuration software)
is required.
Suppresses vibration of
Automatically adjusts the gain to optimum value if load applied to the servo
motor shaft varies. Higher in performance than MELSERVO-J2 series servo
amplifier.
Used when the built-in regenerative brake resistor of the servo amplifier does
not have sufficient regenerative capability for the regenerative power
generated.
Used when the regenerative brake option cannot provide enough regenerative
power.
Can be used with the MR-J2S-500B to MR-J2S-22KB.
Used when the regenerative brake option cannot provide enough regenerative
power.
Can be used with the MR-J2S-500B to MR-J2S-22KB.
Forced stop (EM1) can be automatically switched on internally to invalidate it. Parameter No.23
Output signal can be forced on/off independently of the servo status.
Use this function for output signal wiring check, etc.
Using a personal computer, parameter setting, test operation, status display,
etc. can be performed.
1 pulse produced at a servo motor stop.Parameter No.24
Chapter 13
Section 7.3
Section 7.4
Chapter 6
Section 12.1.1
Section 12.1.2
Section 12.1.3
Parameters
No.10, 11
Section 4.4
(1) (e)
Section 12.1.8
1 - 6
1. FUNCTIONS AND CONFIGURATION
1.5 Model code definition
(1) Rating plate
(2) Model
MR–J2S–
Series
MITSUBISHI
MODEL
POWER
MR-J2S-60B
POWER :
INPUT :
OUTPUT :
SERIAL :
MITSUBISHI ELECTRIC CORPORATION
MADE IN JAPAN
600W
3.2A 3PH 1PH200-230V 50Hz
3PH 1PH200-230V 60Hz
5.5A 1PH 230V 50/60Hz
170V 0-360Hz 3.6A
A5
TC3 AAAAG52
B
AC SERVO
AC SERVO
PASSED
Model
Capacity
Applicable power supply
Rated output current
Serial number
MR–J2S–100B or less
MR–J2S–200B 350B
With no regenerative resistor
Symbol
Description
Indicates a servo amplifier
of 11 to 22kw that does not
–PX
use a regenerative resistor
as standard accessory.
Power Supply
Symbol
None
(Note1)
3-phase 200 to 230VAC
(Note2) 1-phase 230VAC
1-phase 100V to 120VAC
1
Power supply
MR-J2S-500B
Rating plate
Rating plate
MR-J2S-700B
Note:1. Not supplied to the servo amplifier
of MR-J2S-60B or more.
2. Not supplied to the servo amplifier
of MR-J2S-100B or more.
SSCNET compatible
Rated output
Symbol
Rated
output [kW]
Rating plate
MR-J2S-11KB 15KB
500
11k
15k
22k
Rated
output [kW]
3.5350
5
7700
11
15
22
Symbol
0.110
0.220
0.440
0.660
0.7570
1100
Rating plate
MR-J2S-22KB
2200
Rating plateRating plate
1 - 7
1. FUNCTIONS AND CONFIGURATION
1.6 Combination with servo motor
The following table li sts comb ina tio n s of se rvo ampl if iers and servo motors. The sa me comb in a tio n s ap ply
to the models with electromagnetic brakes and the models with reduction gears.
The servo amplifier is shown without the front cover. For removal of the
front cover, refer to Section 1.7.2.
Cooling fan
Name/Application
Axis select switch (CS1)
CS1
0
1
F
2
E
D
C
B
A
Used to set the axis number of
3
4
the servo amplifier.
5
6
7
9
8
Display
The two-digit, seven-s egment LED shows the servo
status and alar m number .
Battery holder
Contains the battery for absolute position data backup.
Battery connector (CON1)
Used to connect the battery for absolute position data
backup.
Monitor output terminal (CN4)
Used to output monitor values on two channels in the
form of analog signals.
Communication connector (CN3)
Used to connect a personal computer (RS-232C) .
Bus cable conne cto r ( C N 1A)
Used to connect the servo system controller or
preceding axis servo amplifier.
Bus cable connector ( C N1 B)
Used to connect the subsequent axis servo amplif ier
or termination connector (MR-A-TM).
Reference
Section3.11
Chapter4
Section13.3
Section13.3
Section3.2
Section12.1.5
Section3.2
Section12.1.5
Section3.2
Section3.2
Installation notch
(4 places)
Charge lamp
Lit to indicate that the main circuit is charged. While
this lamp is lit, do not reconnect the cables.
Control circ ui t t e rm i nal block (TE2)
Used to connect the control circuit power supply.
Encoder con n e ctor (CN2)
Connector for connection of the servo motor encoder.
I/O signal connector (C O N 2)
Used to connect digital I/O signals.
Rating plate
Main circuit terminal block (TE1)
Used to connect the input power supply, re ge ne rative
brake option and servo motor.
Note: 1. The HC-SFS, HC-RFS series have cannon connectors.
2. A 1-phase 230VAC power supply may be used with the servo amplifier of MR-J2S-70B or less. Connect the power supply to
L
and L2 terminals and leave L3 open.
1
P
Servo motor
C
1 - 17
1. FUNCTIONS AND CONFIGURATION
(b) For 1-phas e 10 0V t o 120V A C
1-phase 100VAC
power supply
No-fuse breaker
(NFB) or fuse
Magnetic
contactor
(MC)
Power
factor
improving
reactor
(FR-BAL)
Options and auxiliary equipment
No-fuse breaker
Magnetic contactor
MR Configurator
(Servo configuration software)
Servo amplifier
To CN2
L1
L
2
UV
CHARGE
W
Reference
Section 12.2.2
Section 12.2.2
Section 12.1.8
To CN1A
To CN1B
To CN3
Options and auxiliary equipment
Regenerative brake option
Reference
Section 12.1.1
CablesSection 12.2.1
Power factor improving reactor Section 12.2.3
Servo system
controller
or
preceding axis
servo amplifier
Subsequent axis
servo amplifier
CN1A
or
Termination
connector
MR Configurator
Personal
computer
(Servo configuration
software
MRZJW3-SETUP151E)
Control circuit terminal block
21
L
L
11
Regenerative brake
P
D
option
C
Note: The HC-SFS, HC-RFS series have cannon connectors.
Protective earth(PE) terminal
(Note)
Encoder cable
(Note)
Power supply lead
Servo motor
1 - 18
1. FUNCTIONS AND CONFIGURATION
(2) MR-J2S-200B MR-J2S-350B
3-phase 200V
to 230VAC
power supply
No-fuse
breaker
(NFB) or
fuse
Magnetic
contactor
(MC)
Power factor
improving
reactor
(FA-BAL)
Options and auxiliary equipment
No-fuse breaker
Magnetic contactor
MR Configurator
(Servo configuration software)
Servo amplifier
To CN2
L
11
L
21
Reference
Section 12.2.2
Section 12.2.2
Section 12.1.8
Options and auxiliary equipmentReference
Regenerative brake option
Section 12.1.1
CablesSection 12.2.1
Power factor improving reactor Section 12.2.3
Servo system
controller
or
Preceding axis
servo amplifier
To CN1A
Subsequent axis
servo amplifier
CN1A
or
To CN1B
Termination
connector
MR Configurator
To CN3
Personal
computer
(Servo
configuration
software
MRZJW3SETUP151E)
L1
L
L
U
2
3
V
PC
W
Regenerative brake option
1 - 19
1. FUNCTIONS AND CONFIGURATION
(3) MR-J2S-500B
3-phase 200V
to 230VAC
power supply
No-fuse
breaker
(NFB) or
fuse
Options and auxiliary equipment
No-fuse breaker
Magnetic contactor
MR Configurator
(Servo confi guration software)
Reference
Section 12.2.2
Section 12.2.2
Section 12.1.8
Options and auxiliary equipment
Regenerative brake option
Reference
Section 12.1.1
CablesSection 12.2.1
Power factor improving reactor Section 12.2.3
Magnetic
contactor
(MC)
Power
factor
improving
reactor
(FA-BAL)
(Note)
C
Regenerative brake
option
11
L
21
L
Servo system
controller
or
Preceding axis
Servo amplifier
To CN1A
1
L
L
2
L
3
To CN1B
servo amplifier
Subsequent axis
servo amplifier
CN1A
or
Termination
connector
MR
Configurator
(Servo
configuration
P
U
V
To CN3
Personal
computer
W
software
MRZJW3SETUP151E)
To CN2
Note. When using the regenerative brake option, remove the lead wires of the built-in regenerative brake resistor.
1 - 20
1. FUNCTIONS AND CONFIGURATION
f
(4) MR-J2S-700B
3-phase 200V
to 230VAC
power supply
No-fuse
breaker
(NFB) or
fuse
Magnetic
contactor
(MC)
Power
actor
improving
reactor
(FA-BAL)
Options and auxiliary equipment
No-fuse breaker
Magnetic contactor
MR Configurator
(Servo configuration software)
Servo amplifier
L
11
21
L
L
3
L
2
1
L
Reference
Section 12.2.2
Section 12.2.2
Section 12.1.8
To CN1A
To CN1B
To CN3
To CN2
U
V
W
Options and auxiliary equipmentReference
Regenerative brake option
Section 12.1.1
CablesSection 12.2.1
Power factor improving reactor Section 12.2.3
Servo system
controller
or
Preceding axis
servo amplifier
Subsequent axis
servo amplifier
CN1A
or
Termination
connector
MR
Configurator
(Servo
configuration
Personal
computer
software
MRZJW3-
SETUP151E)
C
P
(Note) Regenerative brake
option
Note. When using the regenerative brake option, remove the lead wires of the built-in regenerative brake resistor.
1 - 21
1. FUNCTIONS AND CONFIGURATION
(5) MR-J2S-11KB or more
Options and auxiliary equipment
No-fuse breaker
3-phase 200V to
230VAC power supply
No-fuse breaker(NFB)
or fuse
Magnetic contactor
MR Configurator
(Servo configuration software)
Reference
Section 12.2.2
Section 12.2.2
Section 12.1.8
Options and auxiliary equipmentReference
Regenerative brake option
Section 12.1.1
CablesSection 12.2.1
Power factor improving reactor Section 12.2.3
Power factor improving DC
reactor
Section 12.2.4
MR Configurator
Personal
computer
(Servo configuration
software
MRZJW3-SETUP151E)
Magnetic
contactor
(MC)
(Note 2)
Power factor
improving
reactor
(FR-BAL)
L
21
L
11
Analog monitor
To CN4
Servo sy st e m
To CN3
MITSUBISH I
controlle r or
Preceding axis
To CN1A
servo amplifier
Subsequent axis
servo amplifier
CN1A or
L
3
L
2
L
1
To CN1B
Forced st op etc.
Terminal
connector
To CON2
To CN2
C
Regenerative
brake option
P
(Note 2)
Power factor improving
DC reactor (FR-BEL)
Note1: There is no BW when the HA-LFS 11K2 is used.
Note2:
Use either the FR-BAL or FR-BEL power factor improving reactor.
(Note 1)
BU
1 - 22
BV
BW
VW
U
Servo motor
HA-LFS series
2. INSTALLATION
2. INSTALLATION
CAUTION
Stacking in excess of the limited number of products is not allowed.
Install the equipment to incombustibles. Installing them directly or close to
combustibles will led to a fire.
Install the equipment in a load-bearing place in accordance with this Instruction
Manual.
Do not get on or put heavy load on the equipment to prevent injury.
Use the equipment within the specified environmental condition range.
Provide an adequate protection to prevent screws, metallic detritus and other
conductive matter or oil and other combustible matter from entering the servo
amplifier.
Do not block the inta ke /e xhau st po rts o f th e se rv o ampl ifier. Otherwis e, a fa ul t may
occur.
Do not subject the servo amplifier to drop impact or shock loads as they are
precision equipment.
Do not install or operate a faulty servo amplifier.
When the product has been stored for an extended period of time, consult
Mitsubishi.
Indoors (no direct sunlight)
Free from corrosive gas, flammable gas, oil mist, dust and dirt
[m/s2] 5.9 [m/s2] or less
2
] 19.4 [ft/s2] or less
[ft/s
2 - 1
2. INSTALLATION
2.2 Installation direction and clearances
The equipment mus t be installe d in the specif ied direc tion. Other wise, a fau lt ma y
CAUTION
(1) Installation of one servo amplifier
10mm
(0.4 in.)
or more
occur.
Leave specified clearances between the servo amplifier and control box inside
walls or other equipment.
Control boxControl box
40mm
(1.6 in.)
or more
Servo amplifier
10mm
(0.4 in.)
or more
Wiring clearance
70mm
(2.8 in.)
Top
40mm
(1.6 in.)
or more
Bottom
2 - 2
2. INSTALLATION
(2) Installation of two or more servo amplifiers
Leave a large clearance between the top of the servo amplifier and the internal surface of the control
box, and install a fan to prevent the internal temperature of the control box from exceeding the
environmental conditions.
Control box
100mm
(4.0 in.)
or more
Servo
amplifier
10mm
(0.4 in.)
or more
30mm
(1.2 in.)
or more
40mm
(1.6 in.)
or more
30mm
(1.2 in.)
or more
(3) Others
When using heat generating equipment such as the regenerative brake option, install them with full
consideration of heat generation so that the servo amplifier is not affected.
Install the servo amplifier on a perpendicular wall in the correct vertical direction.
2.3 Keep out foreign materials
(1) When installin g the unit in a control box, prevent drill ch ips and wire fragmen ts from entering the
servo amplifier.
(2) Prevent oil, water, metallic dust, etc. from entering the servo amplifier through openings in the control
box or a fan installed on the ceiling.
(3) When insta lling the co ntrol box in a place whe re there are much toxic g as, dirt and dust, conduct an
air purge (force clean air into the contro l box from outside to make the internal pressure higher than
the external pressure) to prevent such materials from entering the control box.
2 - 3
2. INSTALLATION
2.4 Cable stress
(1) The way of clamping the cable must be fully examined so that flexing stress and cable's own weight
stress are not applied to the cable connection.
(2) For use in any application where the servo motor moves, fix the cables (encoder, power supply, brake)
supplied with the servo motor, and flex the optional encoder cable or the power supply and brake
wiring cables. Use the optional encoder cable within the flexing life range. Use the power supply and
brake wiring cables within the flexing li fe of the cabl es.
(3) Avoid any probability that the cable sheath might be cut by sharp chips, rubbed by a machine corner
or stamped by workers or vehicles.
(4) For installation on a machine where the servo motor will move, the flexing radius should be made as
large as possible. Refer to section 11.4 for the flexing life.
2 - 4
3. SIGNALS AND WIRING
3. SIGNALS AND WIRING
Any person who is involved in wiring should be fully competent to do the work.
Before starting wiring, make sure that the voltage is safe in the tester more than 10
minutes after power-off. Otherwise, you may get an electric shock.
WARNING
CAUTION
Ground the servo amplifier and the servo motor securely.
Do not attempt to wire the servo amplifier and servo motor until they have been
installed. Otherwise, you may get an electric shock.
The cables should not be damaged, stressed excessively, loaded heavily, or
pinched. Otherwise, you may get an electric shock.
Wire the equipment correctly and securely. Otherwise, the servo motor may
misoperate, resulting in injury.
Connect cables to correct terminals to prevent a burst, fault, etc.
Ensure that polarity ( , ) is correct. Otherwise, a burst, damage, etc. may occur.
The surge absorbing diode installed to the DC relay designed for control output
should be fitted in the specified direction. Otherwise, the signal is not output due to
a fault, disabling the forced stop(EM1) and other protective circuits.
Servo
Amplifier
COM
(24VDC)
Control
output
signal
RA
Servo amplifier
COM
(DC24V)
Control output
signal
RA
Use a noise filter, etc. to minimize the influence of electromagnetic interference,
which may be given to electronic equipment used near the servo amplifier.
Do not install a power capacitor, surge suppressor or radio noise filter (FR-BIF
option) with the power line of the servo motor.
When using the regenerative brake resistor, switch power off with the alarm signal.
Otherwise, a transistor fault or the like may overheat the regenerative brake
resistor, causing a fire.
Do not modify the equipment.
POINT
CN1A, CN1B, CN2 and CN3 have the same shape. Wrong connection of
the connectors will lead to a failure. Connect them correctly.
3 - 1
3. SIGNALS AND WIRING
3.1 Connection example of control signal system
POINT
Refer to Section 3.5 for the connection of the power supply system and to
Section 3.6 for connection with the servo motor.
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal (terminal marked ) of
the servo amplifier to the protective earth (PE) of the control box.
2. Connect the diode in the correct direction. If it is connected reversely, the servo am plifier will be
faulty and will not output signals, disabling the forced stop (EM1) and other protective circuits.
3. If the controller does not have an emergency stop function, always install a forced stop switch
(Normally closed).
4. When a personal computer is connected for use of the test operation mode, always use the
maintenance junction card (MR-J2CN3TM) to enable the use of the forced stop (EM1). (Refer to
section 12.1.6)
5. CN1A, CN1B, CN2 and CN 3 h ave the s am e shape. Wrong connection of the conn ector s will le ad t o
a fault.
6. The sum of currents that flow in the external relays should be 80mA max.
7. When starting operation, always turn on the forced stop (EM1). (Normally closed contacts) By
setting “0001” in parameter No.23, the forced stop (EM1) can be made invalid.
8. When connecting the personal computer together with analog monitor outputs 1, 2, use the
maintenance junction card (MR-J2CN3TM). (Refer to Section 12.1.3.)
9. Use MRZJW3-SETUP151E.
10. Use the bus cable at the overall distance of 30m(98.4ft) or less. In addition, to improve noise
immunity, it is recommended to use a cable clamp and data line filters (three or four filters
connected in series) near the connector outlet.
11. The wiring of the second and subsequent axes is omitted.
12. Up to eight axes (n
be connected on the same bus.
13. Always insert the termination connec tor (MR-A-T M) into CN 1B of the servo am plifier located at the
termination.
14. The bus cable used with the SSCNET dep ends on th e prec eding or su bsequent c ontr oller or ser vo
amplifier connected. Refer to the following table and choose the bus cable.
1 to 8) may be connected. The MR-J2S- B/MR-J2-03B5 servo amplifier may
MR-J2S- BMR-J2-03B5
QD75MMR-J2HBUS
Motion
controller
MR-J2S- B MR-J2-03B5
Maintenance junction card
Q172CPU(N)Q172J2BCBL M(-B)
Q173CPU(N)Q173J2B CBL M
A motionMR-J2HBUS
MR-J2HBUS
M
M-A
M
15. When the A1SD75M (AD75M) is used as the controller, encoder pulses may not be output
depending on the software ver sion of the controller. For details, r efer to the A1SD75M (AD75M)
Manual.
3 - 3
3. SIGNALS AND WIRING
3.1.2 MR-J2S-11KB or more
(Note 7)
MR Configurator
(Servo configuration
software)
Personal computer
Servo amplifier
(Note 4)
CN3
6
16
7
178LBR
18
Plate
LA
LAR
LB
LZ
LZR
SD
Encoder A-phase pulse
(differential line driver)
Encoder B-phase pulse
(differential line driver)
Encoder Z-phase pulse
(differential line driver)
(Note
13)
Servo system controller
(Note 8, 12)
Bus cable (Option)
Cable clamp
(Option)
15m(49.2ft)
or less
CN3
(Note 4)
CN1A
(Note 4)
CN1B
Setting : 0
MR-J2S-B
(2 axis)
CN1A
CN1B
Setting : 1
CN4
1
2
4
CON2
2
1
4
3
18
15 VDD
CS1
CS1
2m(6.56ft) or less
MO1
MO2
LG
EM1
SG
DB
MBR
COM
(Note 1)
(Note 9)
A
A
10k
10k
(Note 2, 5)
RA1
RA1
Always connect.
Analog monitor
Max. 1mA
Reading in
both directions
(Note 3, 6)
Forced stop
Dynamic brake
interlock
Magnetic brake
interlock
(Note 8, 12)
Bus cable
(Option)
(Note 11)
MR-A-TM
3 - 4
MR-J2S-B
(3 axis)
CN1A
CN1B
Setting : 2
MR-J2S-B
(n axis)
CN1A
CN1B
Setting: n-1
(Note 9)
CS1
(Note 9)
CS1
(Note 10)
n= 1 to 8
3. SIGNALS AND WIRING
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal (terminal marked ) of
the base unit to the protective earth (PE) of the control box.
2. Connect the diode in the c orrec t direc tion. If it is conn ected re vers el y, the int erf ace unit will be fau lt y
and will not output signals, disabling the forced stop and other protective circuits.
3. If the controller does not have an emergency stop (EM 1) f unc tio n, a l wa ys ins tal l a f orc ed s top switch
(Normally closed).
4. CN1A, CN1B, and CN3 h ave the same shape. Wr ong connection of the connectors will lead to a
fault.
5. The sum of currents that flow in the external relays should be 80mA max.
6. When starting operation, always turn on the forced stop (EM1). (Normally closed contacts) By
setting “0001” in DRU parameter No.23 of the drive unit, the forced stop (EM1) can be made invalid.
7. Use MRZJW3-SETUP151E.
8. Use the bus cable at the overall distance of 30m(98.4ft) or less. In addition, to improve noise
immunity, it is recommended to use a cable clamp and data line filters (three or four filters
connected in series) near the connector outlet.
9. The wiring of the second and subsequent axes is omitted.
10. Up to eight axes (n
be connected on the same bus.
11. Always insert the t ermination connec tor (MR-A-TM) into CN1B of the interface unit located at the
termination.
12. The bus cable used with the SSCNET dep ends on th e prec eding or su bsequent c ontr oller or ser vo
amplifier connected. Refer to the following table and choose the bus cable.
1 to 8) ma y be c onn ect ed. T he MR- J2 S- B/MR-J2-03B5 servo amplif ier m ay
MR-J2S- BMR-J2-03B5
QD75MMR-J2HBUS
Motion
controller
MR-J2S- B MR-J2-03B5
Maintenance junction card
Q172CPU(N)Q172J2BCBL M(-B)
Q173CPU(N)Q173J2B CBL M
A motionMR-J2HBUS M-A
MR-J2HBUS M
M
13. When the A1SD75M (AD75M) is used as the controller, encoder pulses may not be output
depending on the software ver sion of the controller. For details, r efer to the A1SD75M (AD75M)
Manual.
3 - 5
3. SIGNALS AND WIRING
3.2 I/O signals
3.2.1 Connectors and signal arrangements
POINT
The pin configurations of the connectors are as viewed from the cable
connector wiring section.
(1) MR-J2S-700B or less
CN1ACN1B
1
2
LGLG
RDRD*
3
4
TDTD*
5
6
LGLG
7
8
EMG
9
10
BT
CN2CN3
1
2
LG
LG
3
4
5
6
MD
7
8
MR
9
10
BAT
12
14
16
18
20
12
LG
14
16
MDR
18
P5
20
P5
11
13
15
17
EMG*
19
11
LG
13
15
17
MRR
19
P5
MITSUBISHI
MELSERVO-J2
The connector frames are
connected with the PE (earth)
terminal inside the servo amplifier.
1
2
LGLG
RDRD*
3
4
TDTD*
5
6
LGLG
7
8
EMG
9
10
BT
1
2
LG
RXD
3
4
SG
MO1
5
6
COM
LA
7
8
LB
9
10
VDD
12
14
16
18
20
12
TXD
14
MO2
16
LAR
18
LZRLZ
20
EM1
11
13
15
17
EMG*
19
11
LG
13
MBR
15
17
LBR
19
3 - 6
3. SIGNALS AND WIRING
(2) MR-J2S-11KB or more
CN3
CN1A
Same as the one of the
MR-J2S-700B or less.
CN1B
Same as the one of the
MR-J2S-700B or less.
CN2
1
2
LG
4
LG
12
LG
3
14
5
6
MD
8
10
7
MR
9
BAT
16
MDR
18
P5
20
P5
11
LG
13
15
17
MRR
19
P5
CN4
1
2
4
MITSUBISHI
CHARGE
The connector frames are
connected with the PE (earth)
terminal inside the servo amplifier.
MO1
MO2
LG
2
RXD
4
6
LA
8
LZ
10
2
EM1
4
DB
6
8
10
12
1
LG
3
5
7
LB
9
CON2
1
SG
3
MBR
5
7
9
11
13
12
TXD
14
16
LAR
18
LZR
20
15
VDD
17
19
21
23
25
11
LG
13
15
17
LBR
19
14
16
18
COM
20
22
24
26
3 - 7
3. SIGNALS AND WIRING
g
y
g
y
3.2.2 Signal expla na ti on s
For the I/O interfaces (symbols in I/O column in the table), refer to Section 3.4.2.
(1) Connector applications
ConnectorNameFunction/Application
CN1AConnector for bus cable from preceding axis.
CN1BConnector for bus cable to next axis
CN2Encoder connectorUsed for connection with the servo motor encoder.
CN3
(Note) CN4 Analog monitor output connector
(Note) CON2 IO signal connector
Note. These connectors are exclusive to the MR-J2S-11KB or more.
Communication connector
(I/O signal connector)
(2) I/O signals
(a) Input signal
Connector Pin
SignalSymbol
Forced stopEM1
No.
7kw
or less
11kw
or more
CN320CON2
Turnin
in which the servo is switched off and the d
operated to stop the servo motor.
2
Turn on EM1 in the forced stop status to reset the forced stop
status.
CN34CN41Used to output the data set in parameter No.22 to across
CN314CN42Used to output the data set in parameter No.22 to across
In the servo-off or alarm status, MBR turns off.
3
CON24When usin
When the dynamic brake is operated, DB turns off.
CN3
Outputs pulses per servo motor revolution set in parameter
6
No.38 in the differential line dri ver s
CN3
of the servo motor, the encoder B-phase pulse lags the
16
encoder A-phase pulse by a phase angle of
CN3
7
CN3
17
CN3
The zero-phase signal of the encoder is output in the
8
differential line driver system.
CN3
18
MO1-LG in terms of voltage. Resolution 10 bits
MO2-LG in terms of voltage. Resolution 10 bits
(c) Power supply
Connector Pin
SignalSymbol
Internal power output
for interface
Power input for digital
interface
Common for digital
interface
Control commonLG
ShieldSDPlatePlate Connect the external conductor of the shield cable.
VDD
COM
SG
No.
7kw
or less
11kw
or more
CN310CON2
CN35CON2
CN33CON21Common terminal to VDD and COM. Pins are connected internally.
CN3
1
11
Driver power output terminal for digital interface.
Used to output
15
Permissible current: 80mA
Driver power input terminal for digital interface.
Used to input 24VDC (200mA or more) for input interface.
18
Connect with VDD.
Separated from LG.
Common termin al to MO1 an d MO2.
CN4
4
Used for connection with the controller or preceding-axis
servo amplifier.
Used for connection with the next-axis servo amplifier or
for connection of the termination connector .
Used for connection w i th the personal computer.
Serves as an I/O signal connector when the personal
computer is not used.
Used to output analog monitor 1 (M01) and analog monitor
2 (M02).
Used to input a forced stop and output the dynamic brake
interlock(DR), the electromagnetic brake interlock
Function/ApplicationI/O Division
off EM1 puts the servo motor in a forced stop status,
Function/ApplicationI/O Division
this signal, set 1 in the parameter No. 2.
stem. In CCW rotation
Function/Application
24V 10% to across VDD-COM. Connect with COM.
3 - 8
namic brake is
/2.
DI-1
DO-1
DO-1
DO-2
DO-2
Analog
output
Analog
output
3. SIGNALS AND WIRING
3.3 Alarm occurrence timing chart
When an alarm has occurred, remove its cause, make sure that the operation
CAUTION
When an alarm occurs in the servo amplifier, t he base circuit is shut off and the servo motor is coated to a
stop. Switch off the main circuit power supply in the external sequence. To deactivate the alarm, power
the control circuit off, then on or give the error reset or CPU reset command from the servo system
controller. However, the alarm cannot be deactivated unless its cause is removed.
(Note)
Main circuit
Control circuit
Base circuit
Dynamic brake
Servo-on command
(from controll er)
Alarm
Reset command
(from controll er)
Note. Switch off the main circuit power as soon as an alarm occurs.
power
signal is not being input, ensure safety, and reset the alarm before restarting
operation.
ON
OFF
ON
OFF
Valid
Invalid
ON
OFF
ON
OFF
NO
1s
Alarm occurs.
Brake operation
YES
50ms or more60ms or more
Remove cause of trouble.
NO
Power off
Brake operation
YES
Power on
NO
(1) Overcurrent, overload 1 or overload 2
If operation is repeated by switching control circuit power off, then on to reset the overcurrent (32),
overload 1 (50) or overload 2 (51) alarm after its occurrence, without removing its cause, the servo
amplifier and servo motor may become faulty due to temperature rise. Securely remove the cause of
the alarm and also allow about 30 minutes for cooling before resuming operation.
(2) Regenerative alarm
If operation is repeated by switching control circuit power off, then on to reset the regenerative (30)
alarm after its occurrence, the external regenerative brake resistor will generate heat , resulting in an
accident.
(3) Instantane ou s pow e r fa il ur e
Undervoltage (10) occurs if power is restored after a 60m s or longer power failure of the con trol circu it
power supply or after a drop of the bus voltage to or below 200VDC. If the power failure persists
further, the control circuit power switches off. When the power failure is rese t in this state, the alarm
is reset and the servo amplifier returns to the initial state.
3 - 9
3. SIGNALS AND WIRING
e
3.4 Interfaces
3.4.1 Common line
The following diagram shows the power supply and its common line.
To conform to the EMC directive, refer to the EMC Installation Guide lines (IB(NA)67310).
Servo amplifier
24VDC
VDD
DI-1
COM
EM1
SG
<Isolated>
MBR
RA
Servo motor
M
Ground
LA .etc
LAR
.etc
LG
SD
MO1
MO2
LG
TXD
RXD
MR
MRR
LG
SD
Analog monitor output
RS-232C
Servo motor encoder
CN2
Differential lin
driver output
35mA max.
3 - 10
3. SIGNALS AND WIRING
3.4.2 Detailed description of the interfaces
This section gives the details of the I/O signal interfaces (refer to I/O Division in the table) indicated in
Sections 3.2.2.
Refer to this section and connect the interfaces with the external equipment.
(1) Digital input interface DI-1
Give a signal with a relay or open collector transistor.
Servo amplifier
24VDC
R: Approx. 4.7
For a transistor
Approx. 5mA
TR
V
1.0V
CES
CEO
100 A
I
VDD
COM
EM1
Switch
SG
(2) Digital output interface DO-1
A lamp, relay or photocoupler can be driven. Provide a diode (D) for an inductive load, or an inrush
current suppressing resister (R) for a lamp load. (Permissible current: 40mA or less, inrush current:
100mA or less)
(a) Inductive load
Servo amplifier
24VDC
VDD
COM
MBR
SG
Load
If the diode is not
connected as shown,
the servo amplifier
will be damaged.
3 - 11
3. SIGNALS AND WIRING
(b) Lamp load
Servo amplifier
24VDC
(3) Encoder pul se outp ut D O- 2
(Differential line driver system)
1) Interface
Max. output current: 35mA
Servo amplifierServo amplifier
LA
(LB, LZ)
Am26LS32 or equivalentHigh-speed photocoupler
VDD
COM
MBR
SG
LA
(LB, LZ)
R
100
LAR
(LBR, LZR)
LG
SD
2) Output pulse
150
Servo motor CCW rotation
LA
LAR
LB
LBR
LZ
LZR
OP
T
/2
LAR
(LBR, LZR)
SD
LZ signal varies 3/8T on its leading edge.
400 s or more
3 - 12
3. SIGNALS AND WIRING
(4) Analog output
Output voltage :
Max. output current :1mA
Resolution :10bit
Servo amplifier
10V
MO1
(MO2)
LG
SD
10k
Reading in one or
both directions
1mA meter
A
3 - 13
3. SIGNALS AND WIRING
3.5 Power line circuit
When the servo amplifier has become faulty, switch power off on the amplifier
power side. Continuous flow of a large current may cause a fire.
CAUTION
3.5.1 Connection example
Wire the power supply/main circuit as sho wn below so that po wer is shu t off and the servo -on com mand
turned off as soon as an alarm occurs, a servo forced stop is made valid, or a controller emergency stop is
made valid. A no-fuse breaker (NFB) must be used with the input cables of the power supply.
Switch power off at detection of an alarm. Otherwise, a regenerative brake
transistor fault or the like may o verheat the r egenerative b rake resist or, causing a
fire.
POINT
For the power line circuit of the MR-J2S-11KB to MR-J2S-22KB, refer to
Section 3.12 where the power line ci rcuit is shown together with th e servo
motor connection diagram.
(1) For 3-phase 200 to 230VAC power supply
(Note)
Alarm
RA1
NFBMC
Power supply
3-phase
200 to 230VAC
Forced stop
Controller
emergency stop
RA2
Forced
stop
OFF
Servo amplifier
L
1
2
L
3
L
11
L
L
21
VDD
COM
EM1
SG
ON
MC
MC
SK
Note: Configure up the power supply circuit which switches off the magnetic contactor after detection of
alarm occurrence on the controller side.
3 - 14
3. SIGNALS AND WIRING
(2) For 1-phase 100 to 120VAC or 1-phase 230VAC power supply
(Note 1)
Alarm
RA1
Controller
emergency stop
RA2
Forced
stop
OFF
ON
MC
MC
SK
Power supply
1-phase 100 to
120VAC or
1-phase 230VAC
NFBMC
Servo amplifier
L
1
2
L
(Note 2)
3
L
11
L
L
21
VDD
COM
Forced stop
EM1
SG
Note: 1. Configure up the power supply circuit whic h switches off the m agnetic contactor after det ection of
alarm occurrence on the controller side.
2. Not provided for 1-phase 100 to 120VAC.
3 - 15
3. SIGNALS AND WIRING
3.5.2 Terminals
The positions and signal arrangements of the terminal blocks change with the capacity of the servo
amplifier. Refer to Section 10.1.
Symbol
Connection Target
(Application)
Supply L1, L2 and L3 with the following power:
For 1-phase 230VAC, connect the power supply to L
Servo amplifier
Power supply
3-phase 200 to 230VAC,
L1, L2, L3Main circuit power supply
50/60Hz
1-phase 230VAC,
50/60Hz
1-phase 100 to 120VAC,
50/60Hz
U, V, WServo motor outputConnect to the servo motor power supply terminals (U, V, W).
Supply the following power to L11, L21.
Servo amplifier
Power supply
L11, L21Control circuit power supply
1-phase 200 to 230VAC,
50/60Hz
1-phase 100 to 120VAC,
50/60Hz
Description
and leave L3 open.
1/L2
MR-J2S-10B to
70B
L
1L2
L
1L2L3
MR-J2S-100B
to 700B
MR-J2S-10B1
to 40B1
L
1L2
MR-J2S-10B to 700BMR-J2S -10B 1 to 40B1
L
11L21
L
11L21
P, C, DRegenerative brake option
N
Return conv erter
Brake unit
Protective eart h (PE)
1) MR-J2S-350B or less
Wiring is factory-connected across P-D (servo amplifier built-in regenerative
brake resistor).
When using the regenerative brake option, always remove the wiring from
across P-D and connect the regenerative brake option across P-C.
2) MR-J2S-500B
MR-J2S-700B
Wiring is factory-connected across P-C (servo amplifier built-in regenerative
brake resistor).
When using the regenerative brake option, always remove the wiring from
across P-C and connect the regene rative brake option a cross P-C.
Refer to Section 12.1.1 for details.
When using the return converter or brak e unit, conn e ct it across P-N.
Do not connect it to the servo amplifier of MR-J2S-350B or less.
Refer to Sections 12.1.2 and 12.1.3 for details.
Connect this terminal to the protective earth (PE) terminals of the servo motor
and contro l box for ground ing.
3 - 16
3. SIGNALS AND WIRING
3.5.3 Power-on sequence
(1) Power-on procedure
1) Always wire the power supp ly as shown in above Section 3. 5.1 using the magnetic con tactor with
the main circuit power supply (3-phase 200V: L
external sequence to switch off the magnetic contactor as soon as an alarm occurs.
2) Switch on the control circuit power supply L
supply or before switching on the main circuit power supply. If the main circuit power supply is not
on, the display shows the corresponding warning. However, by switching on the main circuit power
supply, the warning disappears and the servo amplifier will operate properly.
3) The servo amplifier can accept the servo-on command within 3s the main circuit power supply is
switched on. (Refer to paragraph (2) in this section.)
(2) Timing chart
SON accepted
(3s)
Main circuit
Control circuit
Base circuit
Servo-on command
(from controller)
power
ON
OFF
ON
OFF
ON
OFF
1
, L2, L3, 1-phase 230V: L1, L2). Configure up an
11
, L21 simultaneously with the main circuit power
10ms60ms60ms
(3) Forced stop
CAUTION
Install an forc e d stop circ u it e xte rnally to ensure that oper a tion ca n be st o pped and
power shut off immediately.
If the controller does not have an emergency stop function, make up a circuit that switches off main
circuit power as soon as EM1 is turned off at a forced stop. When EM1 is turned off, the dynamic
brake is operated to stop the servo motor. At this time, the display shows the servo forced stop
warning (E6).
During ordinary operation, do not use forced stop (EM1) to alternate stop and run. The service life of
the servo amplifier may be shortened.
Servo amplifier
VDD
COM
Forced stop
EM1
SG
3 - 17
3. SIGNALS AND WIRING
3.6 Connection of servo amplifier and servo motor
3.6.1 Connection instructions
WARNING
Insulate the connections of the power supply terminals to prevent an electric
shock.
Connect the wires to the correct phase terminals (U, V, W) of the servo amplifier
CAUTION
and servo motor. Otherwise, the servo motor will operate improperly.
Do not connect AC power supply directly to the servo motor. Otherwise, a fault
may occur.
POINT
Do not apply the test lead bars or like of a tester directly to the pins of the
connectors supplied with the servo motor. Doing so will deform the pins,
causing poor contact.
The connection method differs according to the series and capacity of the servo motor and whether or not
the servo motor has the electromagnetic brake. Perform wiring in accordance with this section.
(1) For grounding, connect the earth cable of the servo motor to the protective earth (PE) terminal of the
servo amplifier and connect the ground cable of the servo amplifier to the earth via the protective
earth of the control box. Do not connect them directly to the protective earth of the control panel.
Control box
Servo
amplifier
PE terminal
Servo motor
(2) Do not share the 24VDC interface power supply between the interface and electromagnetic brake.
Always use the power supply designed exclusively for the electromagnetic brake.
3.6.2 Connection diagram
POINT
For the connection diagram of the MR-J2S-11KB to MR-J2S-22KB, refer
to Section 3.12 where the connection diagram is shown together with the
power line circuit.
The followin g table lists w iring me thods accord ing to the servo motor types. U se the conne ction diagram
which conforms to the servo motor used. For cables required for wiring, refer to Section 12.2.1. For
encoder cable connection, refer to Section 12.1.4. For the signal layouts of the connectors, refer to Section
3.6.3.
For the servo motor connector, refer to Chapter 3 of the Servo Motor Instruction Manual.
3 - 18
3. SIGNALS AND WIRING
Servo motorConnection diagram
HC-KFS053 (B) to 73 (B)
HC-MFS053 (B) to 73 (B)
HC-UFS13 (B) to 73 (B)
Servo amplifier
W
CN2
U
V
(Note 1)
24VDC
EM1
To be shut off when servo-off
or alarm occurrence
U (Red)
V (White)
W (Black)
(Green)
B1
B2
Servo motor
Motor
(Note 2)
Electromagnetic
brake
HC-SFS121 (B) to 301 (B)
HC-SFS202 (B) to 702 (B)
HC-SFS203 (B)
353 (B)
HC-UFS202 (B) to 502 (B)
HC-RFS353 (B)
503 (B)
Encoder cable
Encoder
Note:1. To prevent an electric shock, always connect the protective earth (PE) term i nal of the
servo amplifier to the protective earth (PE) of the control box.
2. This circuit applies to the servo motor with electromagnetic brake.
Servo amplifier
U
V
W
(Note 1)
24VDC
EM1
To be shut off when servo-off
Servo motor
U
V
Motor
W
B1
B2
Electromagnetic
brake
(Note 2)
or alarm occurrence
CN2
Encoder cable
Encoder
Note:1. To prevent an electric shock, always connect the protective earth (PE) term i nal of the
servo amplifier to the protective earth (PE) of the control box.
2. This circuit applies to the servo motor with electromagnetic brake.
Servo amplifier
U
V
W
U
V
W
Servo motor
Motor
HC-SFS81 (B)
HC-SFS52 (B) to 152 (B)
HC-SFS53 (B) to 153 (B)
HC-RFS103 (B) to 203 (B)
HC-UFS72 (B)
152 (B)
EM1
24VDC
B1
B2
Electromagnetic
brake
(Note 2)
(Note 1)
To be shut off when servo-off
or alarm occurrence
CN2
Encoder cable
Encoder
Note:1. To prevent an electric shock, always connect the protective earth (PE) term i nal of the
servo amplifier to the protective earth (PE) of the control box.
2. This circuit applies to the servo motor with electromagnetic brake.
3 - 19
3. SIGNALS AND WIRING
3.6.3 I/O terminals
(1) HC-KFS
Power supply
connector
5557-04R-210
HC-MFS HC-UFS3000r/min series
Power supply lead
4-AWG19 0.3m (0.98ft.)
Encoder cable 0.3m (0.98ft.)
With connector 1-1721 69-9
(AMP)
13
24
View b
a
b
Pin
Signal
1
U
2
V
3
W
4
Earth
Power supply connector (mol ex)
Without electromagnetic brake
5557-04R-210 (receptacle)
5556PBTL (Female termina l)
With electromagnetic brake
5557-06R-210 (receptacle)
5556PBTL (Female termina l)
Power supply
connector
5557-06R-210
1
25
36
View b
Encoder connector signal arrangement
123
MR
MRR BAT
456
MD
MDR
789
P5
LGSHD
View a
Signal
Pin
1
4
2
3
4
5
6
W
Earth
(Note)
(Note)
U
V
B1
B2
Note:For the motor with
electromagnetic brake,
supply electromagnetic
brake power (24VDC).
There is no polarity.
3 - 20
3. SIGNALS AND WIRING
t
(2) HC-SFS HC-RFS HC-UFS2000 r/min series
a
Encoder connector
b
Brake conn ector
c
Power supply conn ec to r
Servo motor
HC-SFS81(B)
HC-SFS52(B) to 152(B)
HC-SFS53(B) to 153(B)
HC-SFS121(B) to 301(B)
HC-SFS202(B) to 502 (B)
HC-SFS203(B)
Note:For the motor with
electromagnetic brake,
supply electromagnetic
brake power (24VDC).
There is no polarity.
Encoder connector sig nal arr ang em en t
MS3102A20-29P
Key
Signal
Pin
C
E
A
D
MD
B
MDR
MR
C
MRR
D
E
BAT
F
F
LG
G
L
K
J
M
TP
S
H
View a
B
A
N
R
F
G
H
J
CE05-2A32-17PD-B
KeyKey
F
E
G
D
View c
Pin
Signal
A
C
A
B
B
C
D
E
F
U
V
W
(Earth)
(Note)
B1
(Note)
B2
G
Note:For the motor with
electromagnetic brake,
supply electromagnetic
brake power (24VDC).
There is no polarity.
Electromagnetic brake connector signal arrangemen
MS3102A10SL-4P
Key
Signal
Pin
K
L
AB
M
SD
N
P
LG
R
P5
S
View b
T
Pin
Signal
U
V
W
(Earth)
Pin
A
B
A
Signal
(Note)
(Note)
D
CB
A
B
C
D
B1
B2
Note:For the motor with
electromagnetic brake,
supply electromagnetic
brake power (24VDC).
There is no polarity.
3 - 21
3. SIGNALS AND WIRING
3.7 Servo motor with electromagnetic brake
Configure the electromagnetic brake circuit so that it is activated not only by the
interface uni t sig nal s bu t also by a fo r ce d stop (E M1 ).
Contacts must be open when
servo-off, when an alarm occurrence
and when an electromagnetic brake
interlock (MBR).
CAUTION
The electromagnetic brake is provided for holding purpose and must not be used
for ordinary braking.
POINT
Refer to the Servo Motor Instruction Manual for specifications such as the
power supply capacity and operation delay time of the electromagnetic
brake.
Servo motor
Electromagnetic brake
Circuit must be
opened during
forced stop (EM1).
EM1RA
24VDC
Note the following when the servo motor equipped with electromagnetic brake is used for applications
requiring a brake to hold the motor shaft (vertical lift applications):
1) Do not share the 24VDC interface power supply between the interface and electromagnetic
brake. Always use the power supply designed exclusively for the electromagnetic brak e.
2) The brake will operate when the power (24VDC) switches off.
3) Switch off the servo-on command after the servo motor has stopped.
(1) Connection diagram
Servo amplifier
VDD
COM
MBR
RA
24VDC
RA
Forced
stop
B1
B2
Servo motor
(2) Setting
In parameter No.21 (electromagnetic brake sequence output), set the time delay (Tb) from
electromagnetic brake operation to base circuit shut-off at a servo off time as in the timing chart in (3)
in this section.
3 - 22
3. SIGNALS AND WIRING
(3) Timing charts
(a) Servo-on command (from controller) ON/OFF
Tb [ms] after the servo-on is switched off, the servo lock is released and the servo motor coasts. If
the electromagnetic brake is made valid in the servo lock status, the brake life may be shorter.
Therefore, when using the electromagnetic brake in a vertical lift application or the like, set delay
time (Tb) to about the same as the electromagnetic brake operati on delay ti me to prevent a drop.
Emergency stop command
(from controller)
or
Forced stop (EM1)
(10ms)
ON
OFF
Invalid (ON)
Valid (OFF)
Invalid (ON)
Valid (OFF)
Electromagnetic brake
Electromagnetic brake
Electromagnetic brake release
Electromagnetic brake
operation delay time
(180ms)
(180ms)
3 - 23
3. SIGNALS AND WIRING
A
(c) Alarm occurrence
Servo motor speed
Base circuit
Electromagnetic
brake interlock (MBR)
ON
OFF
Invalid(ON)
Valid(OFF)
Dynamic brake
Dynamic brake
Electromagnetic brake
Electromagnetic brake
(10ms)
Electromagnetic brake
operation delay time
Trouble (ALM)
No
Yes
(d) Both main and control circuit power supplies off
Dynamic brake
Dynamic brake
Electromagnetic brake
Electromagnetic brake
Electromagnetic brake
operation delay time
(Note 2)
Servo motor speed
Base circuit
Electromagnetic
brake interlock(MBR)
larm (ALM)
Main circuit
power
Control circuit
Note: Changes with the operating status.
ON
OFF
Invalid(ON)
Valid(OFF)
No
Yes
ON
OFF
(Note)
15 to 100ms
(10ms)
(10ms or less)
(e) Only main circuit power supply off (control circuit power supply remains on)
Dynamic brake
Dynamic brake
Electromagnetic brake
Electromagnetic brake
Servo motor speed
(10ms)
(Note 1)
15ms or more
Base circuit
Electromagnetic
brake interlock
(MBR)
Alarm
Main circuit power
supply
Note: 1. Changes with the operating status.
2. When the main circuit power supply is off in a motor stop status,
the main circuit off warning (E9) occurs and the alarm (ALM) does not turn off.
ON
OFF
Invalid(ON)
Valid(OFF)
No
Yes
ON
OFF
10ms or less
Electromagnetic brake
operation delay time
(Note 2)
3 - 24
3. SIGNALS AND WIRING
3.8 Grounding
Ground the servo amplifier and servo motor securely.
WARNING
The servo amplifier switches the power transistor on-off to supply power to the servo motor. Depending on
the wiring and ground cablerouting, the servo amplifier may be affected by the switching noise (due to
di/dt and dv/dt) of the transistor. To prevent such a fault, refer to the following diagram and always
ground.
To conform to the EMC Directive, refer to the EMC Installation Guidelines (IB(NA)67310).
To prevent an electric shock, always connect the protective earth (PE) terminal of
the servo amplifier with the protective earth (PE) of the control box.
Control box
(Note 1)
Power supply
3-phase
200 to 230VAC,
1-phase
230VAC or
1-phase
100 to 120VAC
NFB
MC
Servo amplifier
1
L
2
L
Line filter
(Note 2)
L
3
11
L
21
L
CN1A
Servo system
controller
CN2
U
V
W
Ensure to co n nect it to PE
terminal of the servo amplifier.
Do not connect it directly
to the protective earth of
the control panel.
Servo motor
Encoder
U
V
M
W
Outer
Protective earth(PE)
box
1
Note: 1. For 1-phase 230VAC, connect the power supply to L
There is no L
2. To reduce the influence of external noise, we recommend you to ground the bus cable near
the controller using a cable clamping fixture or to connect three or four data line filters in series.
Solid wire: After the sheath has been stripped, the cable can be used as it is. (Cable size: 0.2 to 2.5mm
Approx. 10mm
(0.39inch)
Twisted wire : U se the cable after strip ping the sheath and tw isting the c ore. At th is time , ta ke car e to
avoid a short caused by the loose wires of the core and the adjacent pole. Do not solder
the core as it m ay cause a contact fau lt. (Cable size: 0 .2 to 2.5mm
Insert the core of the cable into the opening and tighten the screw with a flat-blade screwdriver so that
the cable does not come off. (Tightening torque: 0.3 to 0.4N
m(2.7 to 3.5 lb in)) Before inserting the
cable into the opening, make sure that the screw of the terminal is fully loose.
When using a cable of 1.5mm
2
or less, two cables may be inserted into one opening.
2
)
Flat-blade screwdriver
Tip thickness 0.4 to 0.6mm
Overall width 2.5 to 3.5mm
To loosen.
To tighten.
Cable
Opening
Control circuit terminal block
Use of a flat-blade torque screwdriver is recommended to manage the screw tightening torque. The
following table indicates the recomme nded products of t he torque screwdriv er for tightening to rque
management and the flat-blade bit for torque screwdriver. When managing torque with a Phillips bit,
please consult us.
ProductModelMaker/Representative
Torque screwdriverN6L TDKNakamura Seisakusho
Bit for torque screwdriverB-30, flat-blade, H3.5 X 73LShiro Sangyo
3 - 26
3. SIGNALS AND WIRING
3.10 Instructions for the 3M connector
When fabricating an encoder cable or the like, securely connect the shielded external conductor of the
cable to the ground plate as shown in this section and fix it to the connector shell.
External conductorSheath
Strip the sheath.
Ground plate
External conductor
SheathCore
Pull back the external conductor to cover the sheath
Screw
Cable
Screw
3 - 27
3. SIGNALS AND WIRING
3.11 Control axis selection
POINT
The control axis number set to C S1 should be the same as the one set to
the servo system controller.
Use the axis select switch (CS1) to set the control axis number for the servo. If the same number s are set
to different control axes in a single communication system, the system will not operate properly. The
control axes may be set independently of the bus cable connection sequence.
Set the switch to "F" when executing the test operation mode using MR Configurator (servo configuration
software).
Axis select switch (CS1)
8
9
7
6
5
4
3
2
A
B
C
D
E
F
1
0
No.Description
0Axis 1
1Axis 2
2Axis 3
3Axis 4
4Axis 5
5Axis 6
6Axis 7
7Axis 8
8Not used
9Not used
ANot used
BNot used
CNot used
DNot used
ENot used
FTest operation mode or
when machine analyzer is used
(Refer to Section 6.1.2)
3 - 28
3. SIGNALS AND WIRING
3.12 Power line circuit of the MR-J2S-11KB to MR-J2S-22KB
When the servo amplifier has become faulty, switch power off on the amplifier
power side. Continuous flow of a large current may cause a fire.
CAUTION
3.12.1 Connection example
Wire the power supply/main circuit as shown below so that power is shut off and the servo-on signal
turned off as soon as an alarm occurs, a servo forced stop is m ade valid, a contro ller emergency stop, or a
servo motor thermal relay alarm is made valid. A no-fuse breaker (NFB) must be used with the input
cables of the power supply.
Switch power off at detection of an alarm. Otherwise, a regenerative brake
transistor fau lt or the l ike may ov erheat the r egenerat ive brake res istor, ca using a
fire.
POINT
The power-on sequence is the same as in Section 3.5.3.
3-phase
200 to
230VAC
Servo motor
thermal relay
RA3
NFBMC
Forced stop
(Note)
Alarm
RA1
Controller
emergency stop
RA2
Servo amplifier
1
L
L
2
L
3
11
L
CN2
L
21
VDD
COM
EM1
SG
Forced
stop
(Note 2)
Dynamic
break
U
V
W
MR-JHSCBL M
cable
24VDC
power supply
OFF
ON
MC
Servo motor
HA-LFS series
U
V
W
Encoder
RA3
M
Fan
OHS2OHS1
MC
SK
BU
BV
BW
Servo motor
thermal relay
(Note3)
Note: 1. Configure up the power supply circuit which switches off the magnetic contactor after detection of
alarm occurrence on the controller side.
2. When using the external dynamic break, refer to section 12. 1. 4.
3. There is no BW when the HA-LFS11K2 is used.
3 - 29
3. SIGNALS AND WIRING
3.12.2 Servo amplifier terminals
The positions and signal arrangements of the terminal blocks change with the capacity of the servo
amplifier. Refer to Section 10.1.
Symbol
L1, L2, L3Main circuit power suppl ySupply L1, L2 and L3 with three-phase 200 to 230VAC, 50/60Hz power.
U, V, WServo motor outputConnect to the servo motor power supply terminals (U, V, W).
L11, L21Control circuit power supply Supply L11 and L21 with single-phase 200 to 230VAC power.
P, CRegenerative brake option
N
Connection Target
(Application)
Return conv erter
Brake unit
The servo amplifier built-in regenerative brake resistor is not connected at the
time of shipme n t .
When using the regenerative brake option, wire it across P-C.
Refer to Section 12.1.1 for details.
When using the return converter or brak e unit, conn e ct it across P-N.
Refer to Sections 12.1.2 and 12.1.3 for details.
Description
P1, P
Protective eart h (PE)
Power factor improving DC
reactors
Connect this terminal to the protective earth (PE) terminals of the servo motor
and contro l box for ground ing.
-P are connected before shipment. When connecting a power factor improving
P
1
DC reactor, remove the short bar across P
-P. Refer to Section 12.2.4 for details.
1
3 - 30
3. SIGNALS AND WIRING
t
3.12.3 Servo motor terminals
Terminal box
Encoder connector
MS3102A20-29P
Terminal box inside (HA-LFS11K2)
Motor power supply
terminal block
(U, V, W) M6 screw
Encoder connector
signal arrangement
MS3102A20-29P
Power supplyU V WConnect to the motor output terminals (U, V, W) of the servo amplifier.
Supply power which satisfies the following specifications.
HA-LFS11K2
ItemDescription
Voltage/frequency
Power consumption [W]42(50Hz)/54(60Hz)
Rated voltage [V]0.12(50Hz)/0.25(60Hz)
HA-LFS15K2/22K2
ItemDescription
Voltage/frequency
Power consumption [W]32(50Hz)/40(60Hz)
Rated voltage [V]0. 30(50Hz)/0.25(60Hz)
Cooling fan
(Note)
BU
BV BW
M8
single-phase 200 to 220VAC, 50Hz
single-phase 200 to 230VAC, 60Hz
Three-phase 200 to 220VAC, 50Hz
Three-phase 200 to 230VAC, 60Hz
OHS1OHS2BW
Motor thermal relay OHS1 OHS2 OHS1-OHS2 are opened when heat is generated to an abnormal temperature.
Earth terminal
For grounding, connect to the earth of the control box via the earth terminal of the servo
amplifier.
Note. There is no BW when the HA-LFS11K2 is used.
3 - 32
4. OPERATION AND DISPLAY
4. OPERATION AND DISPLAY
4.1 When switching power on for the first time
Before starting operation, check the following:
(1) Wiring
(a) A correct power supply is connected to the power input ter minals (L
amplifier.
(b) The servo motor power supply terminals (U, V, W) of the servo amplifier match in phase with the
power input terminals (U, V, W) of the servo motor.
(c) The servo motor power supply terminals (U, V, W) of the servo amplifier are not shorted to the
power input terminals (L
(d) The earth terminal of the servo motor is connected to the PE terminal of the servo amplifier.
(e) Note the following when using the regenerative brake option, brake unit or power regeneration
converter:
1) For the MR-J2S-350B or less, the lead has been removed from across D-P of the control circui t
terminal block, and twisted cables are used for its wiring.
2) For the MR- J2S-500B
amplifier built-in regenerative brake resistor, and twisted cables are used for its wiring.
(f) 24VDC or higher voltages are not applied to the pins of connector CN3.
(g) SD and SG of connector CN3 are not shorted.
(h) The wiring cables are free from excessive force.
(i) CN1A should be connected with the bus cable connected to the servo system controller or preceding
axis servo amplifier, and CN1B should connected with the bus cable connected to the subsequent
axis servo amplifier or with the termination connector (MR-A-TM.)
1
, L2, L3) of the servo motor.
MR-J2S-700B, the lead has been removed from across P-C of the servo
1
, L2, L3, L11, L21) of the servo
(2) Axis number
The axis number setting of CS1 should be the same as that of the servo system controller. (Refer to
Section 3.11 . )
(3) Parameters
On the servo system controller screen or using the MR Configurator (servo configuration software),
make sure that correct values have been set in the parameters.
(4) Environment
Signal cables and power cables are not shorted by wire offcuts, metallic dust or the like.
(5) Machine
(a) The screws in the servo motor installation part and shaft-to-machine connection are tight.
(b) The servo motor and the machine connected with the servo motor can be operated.
4 - 1
4. OPERATION AND DISPLAY
4.2 Start up
Do not operate the switches with wet hands. You may get an electric shock.
Do not operate the controller with the front cover removed. High-voltage terminals
WARNING
CAUTION
and charging area exposed and you may get an electric shock.
During power-on or operation, do not open the front cover. You may get an electric
shock.
Before starting operation, check the parameters. Some machines may perform
unexpected operation.
Take safety measures, e.g. provide covers, to prevent accidental contact of hands
and parts (cables, etc.) with the servo amplifier heat sink, regenerative brake
resistor, servo motor, etc.since they may be hot while power is on or for some time
after power-off. Their temperatures may be high and you may get burnt or a parts
may damaged.
During operation, never touch the rotating parts of the servo motor. Doing so can
cause injury.
Connect the servo motor with a machine after confirming that the servo motor operates properly alone.
(1) Power on
When the main and control circuit power supplie s are switched on, "d1" (for the fir st axis) appears on
the servo amplifier display.
In the absolute position detection system, first power-on results in the absolute position lost (25) alarm
and the servo system cannot be switched on. This is not a failure and takes place due to the uncharged
capaci t or in the enc o de r.
The alarm can be deactivated by keeping power on for a few minutes in the alarm status and then
switching power off once and on again.
Also in the absolute position detection system, if power is switched on at the servo motor speed of
500r/min or higher, position mismatch may occur due to external force or the like. Power must
therefore be switched on when the servo motor is at a stop.
(2) Parameter setting
Set the parameters according to the structure and specifications of the machine. Refer to Chapter 5 for
the parameter definitions.
Parameter No.NameSettingDescription
7Rotation direction setting0
8Auto tuning 1Used.
9Servo response 5Slow response (initial value) is selected.
Increase in positioning address rotates the
motor in the CCW direction.
After setting the above parameters, switch power off once. Then switch power on again to make the set
parameter values valid.
4 - 2
4. OPERATION AND DISPLAY
(3) Servo-on
Switch the servo-on in the following procedure:
1) Switch on main circuit/control circuit power supply.
2) The controller transmits the servo-on command.
When placed in the servo-on status, the servo amplifier is ready to operate and the servo motor is
locked.
(4) Home position return
Always perform home position return before starting positioning operation.
(5) Stop
If any of the following situations occurs, the servo amplifier suspends the running of the servo motor
and brings it to a stop.
When the servo motor is equipped with an electromagnetic brake, refer to Section 3.7.
Operation/commandStopping condition
Servo off commandThe base circuit is shut off and the servo motor coasts.
Servo system controller
Servo amplifier
Emergency stop command
Alarm occurrence
Forced stop
(EM1) OFF
The base circuit is shut off and the dynamic brake
operates to bring the servo motor to stop. The controller
emergency stop warni ng (E7) occurs.
The base circuit is shut off and the dynamic brake
operates to bring the servo moto r to stop.
The base circuit is shut off and the dynamic brake
operates to bring the servo motor to stop. The servo
forced stop warning (E6) occurs.
4 - 3
4. OPERATION AND DISPLAY
4.3 Servo amplifier display
On the servo amplifier display (two-digit, seven-segment display), check the status of communication with
the servo system controller at power-on, check the axis number, and diagnose a fault at occurrence of an
alarm.
(1) Display sequence
Servo amplifier power ON
Waiting for servo system controller
power to switch ON
Servo system controller power ON
Initial data communication
with servo system controller
During emergency stop and forced stop
When alarm occurs,
alarm code appears.
Servo system controller power OFF
(Note)
Ready ON
(Note)
Servo ON
(Note)
Ordinary operation
Ready OFF/servo OFF
or
Emergency stop and forced stop
reset
Ready ON/servo OFF
Ready ON/servo ON
Servo system controller power ON
Note: The right-hand segments of b1, c1 and d1
indicate the axis number.
(Axis 1 in this example)
4 - 4
4. OPERATION AND DISPLAY
(2) Indication list
IndicationStatusDescription
AAInitializing
AbInitializing
ACInitializing
AdInitializingThe initial parameters from the servo system controller were received.
AEInitialize completionInitial data communication with the servo system controller was completed.
(Note 1)b#Ready OFFThe ready off signal from the servo system controller was received.
(Note 1)d#Servo ONThe ready off signal from the servo system controller was received.
(Note 1)C#Servo OFFThe ready off signal from the servo system controller was received.
(Note 2)**Alarm
88CPU errorInitial data communication with the servo system controller was completed.
(Note 3)b0.
(Note 1)b#.
d#.
c#.
(Note 3)
Test operati on mode
WarningThe alarm No./warning No. that occurred is displayed. (Refer to Section 9.1.)
The servo amplifier was switched on when power to the servo system
controller is off.
Power to the servo system controller was switched off during power-on of
the servo amplifier.
The axis No. set to the servo system controller does not match the axis No.
set with the axis setting switch (CS1) of the servo amplifier.
A servo amplifie r fault occurred or an error took place in communication
with the servo system controller. In t his ca se, the indication changes:
"Ab"
"AC" "Ad" "Ab"
The servo system controller is faulty.
Communication started between the servo system controller and servo
amplifier.
JOG operation, positioning operation, programmed operation, DO forced
output.
Motor-less operation
Note: 1. # denotes any of numerals 0 to 8 and what it means is listed below:
#Description
0Set to the test o peratio n mode.
1First axis
2Second axis
3Third axis
4Fourth axis
5Fifth axis
6Sixth axis
7Seventh axis
8Eighth axis
2. ** indicates the warning/alarm No.
3. Requires the MR Configurator (servo configuration software).
4 - 5
4. OPERATION AND DISPLAY
4.4 Test operation mode
The test operation mode is designed for servo operation confirmation and not for
CAUTION
By using a personal computer and the MR Configurator (servo configuration software MRZJW3SETUP121E), you can execute jog operation, positioning operation, motor-less operation and DO forced
output without connecting the motion controller.
(1) Test operation mode
(a) Jog operation
Jog operation can be performed without using the servo system controller. Use this operation with
the forced stop reset. This operation may be used independently of whether the servo is on or off
and whether the servo system controller is connected or not.
Exercise control on the jog operation screen of the MR Configurator (servo configuration software).
1) Operation pattern
machine operation confirmation. Do not use this mode with the machine. Always
use the servo motor alone.
If an operatio n fa ul t occur re d, u se th e fo rc ed stop (E M1 ) to make a st op .
ItemInitial valueSetting range
Speed [r/min]2000 to max. speed
Acceleration/deceleration time constant [ms]10001 to 20000
2) Operation method
OperationScreen control
Forward rotation startClick the "Forward" button.
Reverse rotation startClick the "Reverse" button.
StopClick the "Stop" button.
(b) Positioning operation
Positioning operation can be performed without using the servo system controller. Use this
operation with the forced stop reset. This operation may be used independently of whether the
servo is on or off and whether the servo system controller is connected or not.
Exercise control on the positioning operation screen of the MR Configurator (servo configuration
software).
1) Operation pattern
ItemInitial valueSetting range
Travel [pulse]1000000 to 9999999
Speed [r/min]2000 to max. speed
Acceleration/deceleration time constant [ms]10001 to 50000
2) Operation method
OperationScreen control
Forward rotation startClick the "Forward" button.
Reverse rotation startClick the "Reverse" button.
PauseClick the "Pause" button.
4 - 6
4. OPERATION AND DISPLAY
(c) Program operation
Positioning operation can be performed in two or more operation patterns combined, without using
the servo system controller. Use this operation with the forced stop reset. This operation may be
used independently of whether the servo is on or off and whether the servo system controller is
connected or not.
Exercise control on the programmed operation screen of the MR Configurator (servo configuration
software). For full information, refer to the MR Configurator (Servo Configuration Software)
Installation Guide.
OperationScreen Control
StartClick the "Start" button.
StopClick the "Reset" button.
(d) Motorless operation
POINT
Motor-less operation may be used with the MR Configurator (servo
configuration software). Usually, however, use mot or-less operation which
is available by making the servo system controller parameter setting.
Without connecting the servo motor, output signals or status displays can be provided in response
to the servo system controller commands as if the servo motor is actually running. This operation
may be used to check the servo system controller sequence. Use this operation with the forced stop
reset. Use this operation with the servo amplifier connected to the servo system controller.
Exercise control on the motor-less operation screen of the MR Configurator (servo configuration
software).
1) Load conditions
Load ItemCondition
Load torque0
Load inertia moment ratioSame as servo motor inertia moment
2) Alarms
The following alarms and warning do not occur. However, the other alarms and warning s occur
as when the servo motor is connected:
Output signals can be switched on/off forcibly independently of the servo status. Use this function
for output signal wiring check, etc.
Exercise control on the DO forced output screen of the MR Configurator (servo configuration
software).
4 - 7
4. OPERATION AND DISPLAY
(2) Configuration
Configuration should be as in Section 3.1. Always install a forced stop switch to enable a stop at
occurrence of an alarm.
(3) Operation procedure
(a) Jog operation, positioning operation, program operation, DO forced output.
1) Switch power off.
2) Set CS1 to “F”.
When CS1 is set to the axis number and operation is performed by the servo system controller,
the test operation mode screen is displayed on the personal computer, but no function is
performed.
3) Switch servo amplifier power on.
When initialization is over, the display shows the following screen:
Decimal poin t fli ck e r s .
4) Perform operation with the personal computer.
(b) Motor-less operation
1) Switch off the servo amplifier.
2) Perform motor-less operation with the personal computer.
The display shows the following screen:
Decimal poin t flickers.
4 - 8
5. PARAMETERS
5. PARAMETERS
CAUTION
Never adjust or change the parameter values extremely as it will make operation
instable.
POINT
When the servo amplifier is connected with the servo system controller, the
parameters are set to the values of the servo system controller. Switching
power off, then on makes the values set on the MR Configurator (servo
configuration software) invalid and the servo system controller values valid.
In the maker setting parameters, do not set any values other than the
initial values.
Setting may not be made to some parameters and ranges depending on the
model or version of the servo system controller. For details, refer to the
servo system controller user's manual.
5.1 Parameter write inhibit
POINT
When setting the parameter values from the servo system controller, the
parameter No. 40 setting need not be changed.
In this servo amplif ier, the parame ters a re cla ssified in to the basic pa ramete rs (No. 1 to 11) , adju stment
parameters ( No. 12 to 26) and expan sion par ameter s (No. 2 7 to 40) accord ing to their safety aspec ts and
frequencies of use. The values of the basic parameters may be set/changed by the customer, but those of
the adjustment and expansion parameters cannot. When in-depth adjustment such as gain adjustment is
required, change the parameter No. 40 value to make all parameters accessible. Parameter No. 40 is
made valid by switching power off, then on after setting its value.
The following table indicates the parameters which are enabled for reference and write by parameter No.
40 setting.
SettingOperationOperation from controller
0000(initial value)
000A
000C
000E
100E
Reference
Write
Reference
Write
ReferenceParameter No.1 to 40
Write
Reference
Write
ReferenceParameter No.1 to 40
Write
Parameter No.1 to 39Parameter No.1 to 11 40
Parameter No.1 to 39Parameter No.40
Parameter No.1 to 39
Parameter No.1 to 39Parameter No.1 to 40
Parameter No.1 to 39
Operation from MR Configurator
(servo configuration software)
Parameter No.1 to 11
Parameter No.40
40
5.2 Lists
POINT
For any parameter whose symbol is preceded by*, set the parameter value
and switch power off once, then switch it on again to make that parameter
setting valid. The parameter is set when communication between the
servo system controller and servo amplifier is established (b* is
displayed). After that, power the servo amplifier off once and then on
again.
Note:1. Factory settings of the servo amplifier. Connecti ng it with the servo sys t em cont rol l er and switching power on changes them to
the settings of the servo system controller.
2. Setting and changing cannot be made from the peripheral software of the motion controller.
3. The setting unit of 0.025rev applies for the servo amplifier of software version B1 or later. For the amplifier of software version
older than B1, the setting unit of 0.1rev is applied.
Customer
setting
5 - 2
5. PARAMETERS
)
(2) Details list
Classifi-
cation
No. SymbolName and Function
1*AMS Amplifier setting
2*REG0000Refer to
Basic parameters
30080
40000
5
Used to select the absolute position detection.
000
Absolute position detection selection
0: Invalid (Used in incremental system.
1: Valid (Used in absolute position
detection system.)
Regenerative brake resistor
Used to select the regenerative brake option used.
00
Regenerative selection brake option
00: Regenerative brake option is not used with
7kW or less servo amplifier (The built-in
regenerative brake resistor is used. However,
the MR-J2S-10B does not have a built-in
regenerative brake resistor and therefore
cannot use it.)
Supplied regenerative brake resistors or
regenerative brake option is used with 11kW
or more servo amp l i f i e r
01: FR-RC, FR-BU, FR-CV
05: MR-RB32
08: MR-RB30
09: MR-RB50
0B: MR-RB31
0C: MR-RB51
0E: When regenerative brake resistors or regenerative
brake option supplied to 11kW or more are cooled
by fans t o inc r ease capabil i t y
10: MR-RB032
11: MR-RB12
The MR-RB65, 66 and 67 are regenerative brake
options that have encased the GRZG400-2 ,
GRZG400-1 and GRZG400-0.8 , respectively.
When using any of these regenerative brake
options, make the same parameter setting as
when using the GRZG400-2 , GRZG400-1 or
GRZG400-0.8 (supplied regenerative brake
resistors or regenerative brake option is used
with 11kW or more servo amplifier).
Select the ext ernal dynamic brake.
0: Invalid
1: Valid
Select "1" when using the external dynamic
brake with the MR-J2S-11KB or more.
POINT
Wrong setting may cause the regenerative brake option to burn.
If the regenerative brake option selected is not for use with the
servo amplifier, parameter error (37) occurs.
For automatic setting by servo system controller
Automatically set from the servo system controller
Initial
Value
0000Refer to
1
Unit
Setting
Range
name
and
function
column.
name
and
function
column.
5 - 3
5. PARAMETERS
Classifi-
cation
No. SymbolName and Function
6*FBP0Refer to
7*POLRota tion dire ction se le ction
Feedback pulse numb er
Set the number of pulses per revolution in the controller side command
unit. Information on the motor such as th e f eedback pulse value, present
position, droop pulses and within-one-revolution position are derived
from the values converted in to the n umber of pul ses s et here.
SettingNum ber of feedback puls es
016384
18192
632768
7131072
255Depending on the number of motor resolution pulses.
POINT
If the number of pulses set exceeds the actual motor
resolution, the motor resolution is set automatically.
Used to select the rotation direction of the servo motor.
0: Forward rotation (CCW) with the increase of the positioning
address.
1: Reverse rotation (CW) with the increase of the positioning
address.
Initial
Value
0Refer to
Unit
Setting
Range
name
and
function
column.
name
and
function
column.
8ATUAuto tuning
Basic parameters
CCW
CW
Used to select the gain adjustment mode of auto tuning.
000
Gain adjustment mode selection
(For details, refer to Section 6.1.1.)
Set
Gain adjustment
value
0
1
3
4Simple manual
mode
Interpolation mode
Auto tuning mode 1
Auto tuning mode 2
Manual mode 1
Description
Fixes position control
gain 1
(parameter No. 13).
Ordinary auto tuning.
Fixes the load inertia
moment ratio set in
parameter No. 12.
Response level setting
can be changed.
adjustment.
0001Refer to
name
and
function
column.
2
Manual mode 2
Manual adjustment
of all gains.
5 - 4
5. PARAMETERS
Classifi-
cation
Basic parameters
No. SymbolName and Function
9RSPServo response
Used to select the response o f auto tuning.
000
Response level selection
Set
Response
value
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F300Hz
If the machine hunts or generates large gear
sound, decrease the set value.
To improve performance, e.g. shorten the
settling time, increase the set value.
level
Low
response
Middle
response
High
response
Machine resonance
frequency guideline
15Hz
20Hz
25Hz
30Hz
35Hz
45Hz
55Hz
70Hz
85Hz
105Hz
130Hz
160Hz
200Hz
240Hz
Initial
Value
7kW or
less
:0005
11kW or
more
:0002
Unit
Setting
Range
Refer to
name
and
function
column.
10TLPForward rotation torque limit
Assume that the rated torque is 100[%].
Used to limit the torque in the forward rotation driving mode and
reverse rotation regenerative mode.
In other than the test operation mode on the MR Configurator (servo
configuration software), the torque limit value on the servo system
controller side is made valid.
11TLNReverse rotation torque limit
Assume that the rated torque is 100[%].
Used to limit the torque in the forward rotation driving mode and
forward rotation regenerative mode.
In other than the test operation mode on the MR Configurator (servo
configuration software), the torque limit value on the servo system
controller side is made valid.
12GD2Ratio of load inertia to servo motor inertia (load inertia ratio)
Used to set the ratio of the load inertia (inertia moment) to the
inertia moment of the servo motor shaft. When auto tuning mode 1
and interpolation mode is selected, the result of auto tuning is
automatically used. (Refer to section 6.1.1)
13PG1Position loop gain 1
Used to set the gain of position loop 1. Increase the gain to improve
trackability performance in response to the position command.
Adjustment parame te rs
When auto turning mode 1,2 is selected, the result of auto turning is
automatically used.
300%0
300%0
7.0times0.0
7kW or
less:35
11kW or
more:19
rad/s4
to
500
to
500
to
300.0
to
2000
5 - 5
5. PARAMETERS
Classifi-
cation
Adjustment parame te rs
No. SymbolName and Function
14VG1Speed loop gain 1
Normally this parameter setting need not be changed. Higher setting
increases the response level but is liable to generate vibration and/o r
noise.
When auto tuning mode 1,2 and interpolation mode is selected, the
result of auto tuning is automatically used.
15PG2Position loop gain 2
Used to set the gain of the position loop.
Set this parameter to increase position response to load disturbance.
Higher setting increases the response level but is liable to generate
vibration and/or noise.
When auto tuning mode 1
2, manual mode and interpolation mode
is selected, the result of auto tuning is automatically used.
16VG2Speed loop gain 2
Set this parameter when vibration occurs on machines of low
rigidity or large backlash.
Higher setting increases the response level but is liable to generate
vibration and/or noise.
When auto tuning mode 1
2 and interpolation mode is selected, the
result of auto tuning is automatically used.
17VIC
Speed integral compensation
Used to set the constant of integral compensation.
When auto tuning mode 1
Used to select the machine resonance suppression filter.
(Refer to Section 7.2.)
0
Initial
Value
7kW or
Unit
rad/s20
less:177
11kW or
more:96
7kW or
rad/s1
less:35
11kW or
more:19
7kW or
rad/s20
less:817
11kW or
more:455
7kW or
ms1
less:48
11kW or
more:91
0Refer to
Setting
Range
to
5000
to
1000
to
20000
to
1000
name
and
function
column.
19FFC
Notch frequency selection
Setting
00
01
02
03
04
05
06
07
Frequency
Invalid
4500
2250
1500
1125
900
750
642.9
Setting
08
09
0A
0B
0C
0D
0E
0F
Frequency
562.5
500
450
409.1
375
346.2
321.4
300
Setting
10
11
12
13
14
15
16
17
Frequency
281.3
264.7
250
236.8
225
214.3
204.5
195.7
Setting
18
19
1A
1B
1C
1D
1E
1F
Frequency
187.5
180
173.1
166.7
160.1
155.2
150
145.2
Notch depth selection
SettingDepthGain
0
Deep
1
2
Shallow
3
40dB
14dB
to
8dB
4dB
Feed forward gain
Set the feed forward gain. When the setting is 100%, the droop
pulses during operation at constant speed are nearly zero. However,
sudden acceleration/deceleration will increase the overshoot. As a
guideline, when the feed forward gain setting is 100%, set 1s or more
as the acceleration/deceleration time constant up to the rated speed.
0%0
to
100
5 - 6
5. PARAMETERS
y
Classifi-
cation
No. SymbolName and Function
20INPIn-position range
Used to set the droop pulse range in which the in-position (INP) will
be output to the controller. Make setting in the feedback pulse unit
(parameter No. 6).
For example, when you want to set
ballscrew is direct coupled, the lead is 10mm, and the feedback
pulses are 8192 pulses/rev (parameter No. 6 : 1), set "8" as indicated
by the following expression:
10 10
10 10
21MBRElectromagnetic brake sequence output
Used to set a time delay (Tb) from when the electromagnetic brake
interlock signal (MBR) turns off until the base circuit is shut off.
22MODAnalog monitor output
Used to select the signal provided to the analog monitor
(MO1)
(Refer to Section 5.3.)
6
8192 8.192 8
3
analog monitor (MO2).
10 m in the conditions that the
00
Initial
Value
100pulse0
100ms0
0001Refer to
Unit
Setting
Range
to
50000
to
1000
name
and
function
column.
Adjustment parame te rs
23*OP1Optional function 1
Used to make the servo forced stop function invalid.
Servo forced stop selection
0: Valid (Use the forced stop (EM1).)
1: Invalid (Do not use the forced stop (EM1).)
Automatically switched on internall
0000Refer to
name
and
function
column.
5 - 7
5. PARAMETERS
)
)
Classifi-
cation
No. SymbolName and Function
24*OP2Optional function 2
Used to select slight vibration suppression control and motor-less
operation
00
Slight vibration suppression control selection
Made valid when auto tuning selection is
set to "0002" in parameter No.8.
Used to suppress vibration at a stop.
0: Invalid
1: Valid
Motor-less operation selection
0: Invalid
1: Makes motor-less operation valid.
When motor-less operation is made valid, signal output or
status display can be provided as if the servo motor is running
actually in response to the servo system controller command,
without the servo motor being connected.
Motor-less operation is performed as in the motor-less
operation using the MR Configurator (servo configuration
software
. (Refer to (d), (1) in Section 4.4.
25LPFLow-pass filter/adaptive vibration suppression control
Used to select the low-pass filter and adaptive vibration suppression
control. (Refer to Chapter 7.)
When you choose "vaid", the filter of th e handwidth
represented by the following expressi on is set automatically.
For 1kW or less
VG2 setting 10
2 (1 GD2 setting 0.1)
For 2kW or more
VG2 setting 5
2 (1 GD2 setting 0.1)
Adaptive vibration suppression control selection
0: Invalid
1: Valid
Machine resonance freq uency is always detected
and the filter is generated in response to resonance to
suppress machine vibration.
2: Held
The characteristics of the filter generated so far are
held, and detection of machine resonance is stopped.
Adaptive vibration suppression control sensitivity
selection
Used to select the sensitivity of machine resonance
detection.
0: Normal
1: Large sensitivity
[H
]
z
z
[H
]
26For manufacturer setting
0
Don't change this value by any means.
5 - 8
5. PARAMETERS
Classifi-
cation
No. SymbolName and Function
27MO1Analog monitor 1 offset
Used to set the offset voltage of the analog monitor1 (MO1) output.
28MO2Analog monitor 2 offset
Used to set the offset voltage of the analog monitor2 (MO2) output.
29For manufacturer setting
Don't change this value by any means.
30ZSPZero speed
Used to set the output range of the zero speed signal (ZSP).
31ERZError excessive alarm level
Used to set the output range of the error excessive alarm.
Note: The setting unit of 0.025rev applies for the servo amplifier of
software version B1 or later. For the amplifier of software version
older than B1, the setting unit of 0.1rev is applied.
32OP5Optional function 5
Used to select PI-PID control switch-over.
000
PI-PID control switch over selection
0: PI control is always valid.
1: Droop-based switching is valid in position
control mode (refer to parameter No. 34).
2: PID control is always valid.
Initial
Value
0mV999
0mV999
0001
50r/min0
80(Note)
0000Refer to
Unit
0.025
Setting
Range
to
999
to
999
to
10000
0
to
1000
name
and
function
column.
33*OP6Option function 6
Used to select the serial communication baudrate, serial
communication response delay time setting and encoder output
pulse setting.
Expansion parameters
34VPIPI-PID control switch-over position droop
35For manufacturer setting
36VDCSpeed differential compensation
37For manufacturer setting0010
0
Serial communication baudrate selection
0: 9600[bps]
1: 19200[bps]
2: 38400[bps]
3: 57600[bps]
Serial communication response delay time
0: Invalid
1: Valid , replay sent in 800 s or mor e
Encoder output pulse setting selection
(refer to parameter No.38)
0: Output pulse designation
1: Division ratio setting
Used to set the position droop value (number of pu lses) at which PI
control is switched over to PID control.
Set "0001" in parameter No. 32 to make this function valid.
Don't change this value by any means.
Used to set the differential compensation.
0000Refer to
name
and
function
column.
0pulse0
to
50000
0
9800
to
1000
5 - 9
5. PARAMETERS
Classifi-
cation
Expansion parameters
No. SymbolName and Function
38*ENR Encoder output pulses
Used to set the encoder pulses (A-phase, B-phase) output by the
servo amplifier.
Set the value 4 times greater than the A-p hase and B-phas e pulses.
You can use parameter No.33 to choose the output pulse setting or
output division ratio setting.
The number of A-phase and B-phase pulses actually output is 1/4
times greater than the preset number of pulses.
The maximum output frequency is 1.3Mpps (after multiplication by
4). Use this parameter within this range.
For output pulse designation
Set "0
" (initial value) in parameter No. 33.
Set the number of pulses per servo motor revolution.
Output pulse
At the setting of 5600, for example, the actually output A-phase
and B-phase pulses are as indicated be lo w:
A-phase and B-phase output pulses
For output division ratio setting
Set "1
The number of pulses per servo motor re volution is divided by the
set value.
Output pulse
At the setting of 8, for example, the actually output A-phase and
B-phase pulses are as indicate d belo w:
A-phase and B-phase output pulses4096[pulse]
39For manufacturer setting
Don't change this value by any means.
40*BLK0000Refer to
Parameter blocks
SettingOperationOperation from
(initial
value)
000C
100E
set value [pulses/rev]
5600
1400[pulse]
4
" in parameter No. 33.
Resolution per servo motor revol ution
Set value
13107241
8
Operation from
controller
Reference0000
Write
Reference000A
Write
ReferenceParameter No.1
Write
Reference000E
Write
ReferenceParameter No.1
Write
Parameter No.1
to 39
Parameter No.1
to 39
Parameter No.1
to 39
Parameter No.1
to 39
Parameter No.1
to 39
MR Configurator
(servo configuration)
Parameter No.1
to 11
40
Parameter No.40
to 40
Parameter No.1
to 11
40
Parameter No.1
to 40
to 40
Parameter No.40
[pulses/rev]
Initial
Value
4000pulse/rev1
0
Unit
Setting
Range
to
65535
name
and
function
column.
5 - 10
5. PARAMETERS
5.3 Analog monitor
The servo status can be output to two channels in terms of voltage. Use this function when using an
ammeter to monitor the servo status or synchronizing the torque/speed with the other servo.
(1) Setting
Change the following digits of parameter No.22:
Parameter No. 22
00
Analog monitor 2(MO2) output selection
(Signal output to across MO2-LG)
Analog monitor 1(MO1) output selection
(Signal output to across MO1-LG)
Parameters No.27 and 28 can be used to set the offset voltages to the analog output voltages. The
setting range is between
Parameter No.DescriptionSetting range [mV]
27Used to set the offset voltage for the analog monitor 1(MO) output.
28
Used to set the offset voltage for the analog monitor 2(MO2)
output.
999 and 999mV.
999 to 999
5 - 11
5. PARAMETERS
(2) Setting description
The servo amplifier is factory-set to output the servo motor speed to analog monitor (MO1) and the
torque to analog monitor (MO2). The setting can be changed as listed below by changing the
parameter No.22 (Analog monitor output) value:
Refer to (3) in this section for the measurement point.
B, you cannot use some parameter functions. Read this section carefully and set appropriate
B on the servo system controller peripheral software incompatible with the
values in the parameters.
5.4.1 Main modifications made to the parameters
The following table lists the parameters whose settings have been modified from the MR-J2to the MR-J 2S-
B. The peripheral software of the servo system controller may not be compatible with
B or added
some parame ters whose se ttings are diff erent or have been added . For det ails, refer to the serv o syste m
controller manual.
Parameter
No.
6FBPFeedback pulse numberThe encoder resolution of the
8ATUAuto tuningGain adjustment modes were
9RSPServo re sponse levelT he response level setting range
18NCHMachine resonance
20INPIn-position rangeThe setting unit became the
22MOD Analog monitor outputThe data that may be output by
25LPFLow-pass filter/adaptive
31ERZError excessive ala rm levelThe setting unit was changed in
33OP6Optional function 6The communication baudrate
38ENREncoder output pulsesThe encoder feedback pulses can
CodeNameMain modifications/additions
compatible motor changed to
131072 pulses/rev.
increased.
was increased to meet the
enhanced response.
The machine resonan ce
suppression filter 1
(Notch filter)
vibration suppression control
suppression filter (notch filter)
setting range was increased.
feedback pulse unit in
parameter No. 6.
analog monitor was added.
The low-pass filter and adaptive
vibration suppression control
functions were newly added.
response to the enhanced
resolution (131072 pulses/rev) of
the encoder.
with the personal computer was
changed to max. 57600bps.
be output from the servo
amplifier. These pulses can be
set.
(Note) Setting from peripheral
software of conventional servo
system controller
Setting cannot be made.
The resolution is 16384
pulses/rev.
Setting can be made but the
added modes cannot be
used.
Some response levels cannot
be set.
Some filter frequencies
cannot be set.
Setting can be made.
Setting can be made but the
bus voltage cannot be set.
Setting can be made.
Setting can be made but the
setting unit is [0.1 rev].
Setting cannot be made.
Setting cannot be made.
Note. As of November, 2003
5 - 14
5. PARAMETERS
5.4.2 Explanation of the modified parameters
(1) Feedback pulse number (parameter No. 6)
This parameter was newly added to the MR-J2 Scontroller is no t compatible with the MR-J2S-
B. If the peripheral software of the servo system
B, this parameter setting cannot be changed. When
the servo motor used is the HC-KFS or HC-MFS, the feedback pulse number is 8192 pulses/rev, and
when it is the HC-SFS, HC-RFS or HC-UFS, the feedback pulse number is 16384 puls es/rev.
(2) Auto tuning (parameter No. 8)
The set value s of this parameter were newly added to the MR-J2 Sthe servo system controller is not compatible with the MR-J2S-
B. If the peripheral software of
B, the parameter settings are as
indicated below. The auto tuning mode 2 and manual mode 1 cannot be used.
000
Gain adjustment mode selection
(For details, refer to Section 6.1.1.)
Set value Gain adjustment mode
Interpol ation mode
0
Auto tuning mode 1
1
Manual mode 2
2Manual adjustment of all gains.
Fixes position control gain 1
(parameter No. 13).
Ordinary auto tuning.
Description
(3) Servo response level (parameter No. 9)
The set values of this parameter were newly added to the MR-J2S-
B. In addition, the machine
resonance frequency guidelines corresponding to the set values were changed. If the peripheral
software of the servo system controller is not compatible with the MR-J2S-
The settings of this parameter were changed for the MR- J2Sservo system controller is not compatible with the MR-J2Sindicated below. The notch depth is
0
40dB.
00
Notch frequency selection
Set value Frequency
Invalid
0
1
2
3
4
5
6
7
Notch depth selection
Set valueDepthGain
0Deep40dB
4500
2250
1500
1125
B. If the peripheral software of the
B, the parameter settings are as
900
750
642.9
(5) In-position range (parameter No. 20)
The setting o f this parame ter was change d for the MR-J2 S-
B. The setting unit was changed from
the conventional input pulse unit to the feedback pulse unit. For deta ils, refer to Section 5.2.
(6) Analog moni to r ou tp ut ( p ara met e r No. 22 )
The setting o f this par ame ter was ch ang e d f o r th e M R- J2 S-
B. "Bus voltage" is a new choice, but you
cannot select it if the peripheral software of the servo system controller is not compatible with the MRJ2S-
B.
Also, the droop pulse output is the encoder resolution unit of the actual motor. For details, refer to
Section 5.3.
(7) Low-pass filter/adaptive vibration suppression control (parameter No. 25)
This parameter was newly added to the MR-J2 Scontroller is no t compatible with the MR-J2 S-
B. If the peripheral software of the servo system
B, this parameter setting cannot be changed. Hence,
the low-pass filter is "valid" an d the adaptive vibration suppre ssion control is "invalid". For de tails,
refer to Sections 7.3 and 7.4.
The setting o f this parame ter was change d for the MR-J2 S-
B. The setting unit was changed from
conventional [k pulse] to [0.1rev]. If the peripheral software of the servo system controller is not
compatible with the MR- J2S-
B, the unit is se t as [0.1rev] to the MR-J2S-B even when the on-
screen setting unit is [k pulse]. For details, refer to Section 5.2.
5 - 16
5. PARAMETERS
(9) Optional function 6 (parameter No. 33)
This parameter was newly added to the MR-J2 Scontroller is no t compatible with the MR-J2 Sthe serial communication baudrate is “9600 [bps]”, the serial commun ication response ready time is
“invalid”, and the encoder outpu t pulse setting selec tion is "o utpu t pulse setting ". For de tails, refer to
Section 5.2.
B. If the peripheral software of the servo system
B, this parameter setting cannot be changed. Hence,
5 - 17
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.