This chapter contains important safety
instructions that you must follow during
operation and storage. Read the following before
any operation to insure your safety and to keep
the instrument in the best possible condition.
These safety symbols may appear in this manual or on the
instrument.
Warning: Identifies conditions or practices that
could result in injury or loss of life.
Caution: Identifies conditions or practices that
could result in damage to the T3PS or to other
properties.
Do not dispose electronic equipment as unsorted
municipal waste. Please use a separate collection
facility or contact the supplier from which this
instrument was purchased.
Do not place any heavy object on the T3PS.
Avoid severe impact or rough handling that
leads to damaging the T3PS.
Do not discharge static electricity to the T3PS.
Use only mating connectors, not bare wires, for
the terminals.
Do not block the cooling fan opening.
Do not disassemble the T3PS unless you are
qualified.
AC Input voltage range: 85Vac-265Vac
Input Power 2000 VA (Max)
Frequency: 47Hz to 63Hz
To avoid electrical shock connect the protective
grounding conductor of the AC power cord to
an earth ground.
Do not dispose this instrument as unsorted
municipal waste. Please use a separate collection
facility or contact the supplier from which this
instrument was purchased. Please make sure
discarded electrical waste is properly recycled to
reduce environmental impact.
When using the power supply in the United Kingdom, make sure
the power cord meets the following safety instructions.
As the colours of the wires in main leads may not correspond with
the coloured marking identified in your plug/appliance, proceed
as follows:
The wire which is coloured Green & Yellow must be connected to
the Earth terminal marked with either the letter E, the earth symbol
or coloured Green/Green & Yellow.
The wire which is coloured Blue must be connected to the terminal
which is marked with the letter N or coloured Blue or Black.
The wire which is coloured Brown must be connected to the
terminal marked with the letter L or P or coloured Brown or Red.
If in doubt, consult the instructions provided with the equipment
or contact the supplier.
This cable/appliance should be protected by a suitably rated and
approved HBC mains fuse: refer to the rating information on the
equipment and/or user instructions for details. As a guide, a cable
of 0.75mm2should be protected by a 3A or 5A fuse. Larger
conductors would normally require 13A types, depending on the
connection method used.
Any exposed wiring from a cable, plug or connection that is
engaged in a live socket is extremely hazardous. If a cable or plug is
deemed hazardous, turn off the mains power and remove the cable,
any fuses and fuse assemblies. All hazardous wiring must be
immediately destroyed and replaced in accordance to the above
standard.
This chapter describes the power supply,
including its main features and front / rear panel
introduction. After going through the overview,
please read the theory of operation to become
familiar with the operating modes, protection
modes and other safety considerations.
Series lineup ......................................................................................11
Main Features ...................................................................................11
USB A port for data transfer,
loading test scripts etc.
Air inlet for cooling the inside of
the T3PS series.
Voltage
Used to set the voltage value or
select a parameter number in the
Function settings.
The display area shows setting values, output
values and parameter settings. The function LEDs
below show the current status and mode of the
power supply. See page 16 for details.
Current
Used to set the current value or
change the value of a Function
parameter.
maintain a constant voltage, the power supply will
), the load
resistance. This means that the voltage output will
current mode (CC) a constant current will be
supplied to the load. When in constant current
mode the voltage output can vary, whilst the
current remains constant. When the load
resistance increases to the point where the set
current limit (I
) can no longer be sustained the
SET
power supply switches to CV mode. The point
where the power supply switches modes is the
crossover point.
When the power supply is operating in CV mode,
a constant voltage will be supplied to the load,
whilst the current will vary as the load varies. At
the point that the load resistance is too low to
switch to CC mode and maintain the set current
limit.
The conditions that determine whether the power
supply operates in CC or CV mode depends on
the set current (I
), the set voltage (V
SET
SET
resistance (RL) and the critical resistance (RC). The
critical resistance is determined by V
SET/ISET
. The
power supply will operate in CV mode when the
load resistance is greater than the critical
Conversely the power supply will operate in CC
mode when the load resistance is less than the
critical resistance. In CC mode the current output
is equal to I
V
Bleed resistors are designed to dissipate the power
mode. This gives the T3PS power supply the
ability to limit the current/voltage draw of the
power supply. Slew rate settings are divided into
High Speed Priority and Slew Rate Priority. High
speed priority mode will use the fastest slew rate
for the instrument.
for user adjustable slew rates for CC or CV mode.
The rising and falling slew rate can be set
independently.
High Speed
Priority
mode
Slew rate =
Enabled
The T3PS DC power supplies employ a bleed
resistor in parallel with the output terminals.
T3PS
Bleed
resistor
Load
from the power supply filter capacitors when
power is turned off and the load is disconnected.
Without a bleed resistor, power may remain
charged on the filter capacitors for some time and
In addition, bleed resistors also allow for smoother
power supply to simulate power sources that have
voltage regulation of the power supply as the
bleed resistor acts as a minimum voltage load.
The bleed resistance can be turned on or off using
the configuration settings.
On the T3PS, the internal resistance of the power
supply can be user-defined in software. (Internal
Resistance Setting, see the Normal Function
Settings on page 82.) When the internal resistance
is set it can be seen as a resistance in series with
the positive output terminal. This allows the
The T3PS power supplies have a number of protection features.
minimum
be set by
When one of the protection alarms is tripped, the ALM icon on the
display will be lit and the type of alarm that has been tripped will
be shown on the display. When an alarm has been tripped the
output will be automatically turned off. For details on how to clear
an alarm or to set the protection modes, please see page 44.
Over voltage protection (OVP) prevents a high
voltage from damaging the load. This alarm can
be set by the user.
Over current protection prevents high current
from damaging the load. This alarm can be set by
the user.
Under voltage limit. This function sets a
voltage setting level for the output. It can
the user.
Over temperature protection for slave and master
board. OHP is a hardware protection function.
Only when the unit has cooled can the over
temperature protection alarms be cleared.
Master board over temperature protection.
Slave board over temperature protection.
Sense alarm. This alarm will detect if the sense
wires have been connected to the wrong polarity.
Hardware over voltage protection. This is a
hardware OVP that is fixed at approximately
120% of the rated voltage output.
current can exceed the indicated value. For pulsed
low AC input is detected.
Fan failure. This alarm function is activated when
the fan RPMs drop to an abnormally low level.
Force Shutdown is not activated as a result of the
T3PS series detecting an error. It is a function that
is used to turn the output off through the
application of a signal from the rear-panel analog
control connector when an abnormal condition
occurs.
Alarms are output via the analog control
connector. The alarm output is an isolated opencollector photo coupler output.
The following situations should be taken into consideration when
using the power supply.
When the power supply switch is first turned on,
an inrush current is generated. Ensure there is
enough power available for the power supply
when first turned on, especially if a number of
units are turned on at the same time.
When the load has current peaks or is pulsed, it is
possible for the maximum current to exceed the
mean current value. The T3PS power supply
ammeter only indicates mean current values,
which means for pulsed current loads, the actual
loads, the current limit must be increased, or a
power supply with a greater capacity must be
chosen. As shown below, a pulsed load may
exceed the current limit and the indicated current
When the power supply is connected to a
regenerative load such as a transformer or
inverter, reverse current will feed back to the
power supply. The T3PS power supply cannot
absorb reverse current. For loads that create
reverse current, connect a r
power supply to bypass the reverse current. This
description only applies when the bleed resist
is off.
such as a battery, reverse current may flow back to
the power supply. To prevent damage to the
power supply, use a reverse-current-protection
diode in series between the power supply and
load.
Diode
T3PS
The output terminals of the T3PS power supplies are isolated with
respect to the protective grounding terminal. The insulation
capacity of the load, the load cables and other connected devices
must be taken into consideration when connected to the protective
ground or when floating.
As the output terminals are floating, the load and
all load cables must have an insulation capacity
that is greater than the isolation voltage of the
power supply.
If the positive or negative terminal is connected to
the protective ground terminal, the insulation
capacity needed for the load and load cables is
greatly reduced. The insulation capacity only
needs to be greater than the maximum output
voltage of the power supply with respect to
ground.
The T3PS power supplies use a universal power
input that can be used with 100 and 240 Vac
systems. To connect or replace the power cord
(user supplied, specification below), use the
procedure below:
1. Turn off the power switch and unplug the
power from the socket.
2. Unscrew the power cord protective sheath.
3. Remove the 2 screws holding the power cord
cover and remove.
1. Connect the power cord to the
universal power input.
2. Press the POWER switch on.
3. The power supply will show the Power On
settings (Pon) at start up. If no Power On
settings are configured, the T3PS will recover
the state right before the power was last turned
OFF. If used for the first time, the default
settings will appear on the display.
For default configuration settings, see page 140.
To turn the T3PS power supply off, press the
power switch again (0 position). It may take a
few seconds for the power supply to fully turn
off.
the wire gauge of the cables should be considered.
.
It is essential that the current capacity of the load
cables is adequate. The rating of the cables must
equal or exceed the maximum current rated
output of the instrument.
200.59
180.7511
18113
161.518
142.524
12434
10645
81064
61688
425120
232145
150190
0070240
00095290
0000120340
The maximum temperature rise can only be 60
degrees above the ambient temperature. The
ambient temperature must be less than 30 degrees
To minimize noise pickup or radiation, the load
wires and remote sense wires should be twistedpairs of the shortest possible length. Shielding of
the sense leads may be necessary in high noise
environments. Where shielding is used, connect
the shield to the chassis via the rear panel ground
screw. Even if noise is not a concern, the load and
rminals to the load,
remote sense wires should be twisted-pairs to
reduce coupling, which might impact the stability
of the power supply. The sense leads should be
separated from the power leads.
Before connecting the output te
first consider whether voltage sense will be used,
the gauge of the cable wiring and the withstand
voltage of the cables and load.
The output terminals is:
Two solid bars equipped with M8 sized bolt and
nuts for low voltage models.
1. Turn the power switch off.
2. Remove the output terminal cover.
3. If necessary, connect the chassis
ground terminal to either the
positive or negative terminal. See
the grounding chapter for details.
4. Choose a suitable wire gauge and
crimping terminal for the load
cables.
3. Tighten the screws to secure the cover over the
terminals.
Reverse the procedure to remove the terminal
covers.
The T3PS power supplies use a novel method of
configuring parameter values only using the
voltage or current knobs. The knobs are used to
quickly edit parameter values at 0.01, 0.1 or 1 unit
steps at a time.
When the user manual says to set a value or
parameter, use the steps below.
Use the Voltage knob to set a voltage of 10.05
volts.
1. Repeatedly press the Voltage knob
until the least significant digit is
Voltage
highlighted. This will allow the
voltage to be edited in 0.01 volt
steps.
3. Rotate the Voltage knob to change
the F setting to F-88 (Factory Set
Value).
Voltage
4. Use the Current knob to set the
Current
F-88 setting to 1 (Return to factory
default settings).
5. Press the Voltage knob to confirm.
Voltage
ConF will be displayed when it is
configuring.
6. Press the Function key again to
Function
exit. The Function key light will
turn off.
The F-89 configuration setting allows you to view
the T3PS version number, build date, keyboard
version, analog-control version, kernel build, test
command version and test command build date.
1. Press the Function key. The
Function
Function key will light up.
2. The display should show F-01 on the top and
the configuration setting for F-01 on the
bottom.
This section describes the basic operations required to operate the
power supply.
Setting OVP/OCP/UVL44
C.V. priority 47
C.C. priority 49
52
Save/Recall s53/53
Voltage Sense54
Before operating the power supply, please see the Getting Started
chapter, page 10.
The OVP level and OCP level has a selectable
range that is based on the output voltage and
output current, respectively. The OVP and OCP
level is set to the highest level by default. The
actual selectable OVP and OCP range depends on
the T3PS model.
When one of the protection measures are on, ALM
indicator is lit red on the front panel and the type
of alarm is also shown on the display. The
ALM_CLR button can be used to clear any
protection functions that have been tripped. By
default, the output will turn off when the OVP or
OCP protection levels are tripped.
The UVL will prevent you from setting a voltage
that is less than the UVL setting. The UVL setting
range is from 0%-105% of the rated output voltage.
When setting the power supply to constant voltage mode, a current
on the
limit must also be set to determine the crossover point. When the
current exceeds the crossover point, the mode switches to C.C.
mode. For details about C.V. operation, see page 21. C.C. and C.V.
mode have two selectable slew rates: High Speed Priority and Slew
Rate Priority. High Speed Priority will use the fastest slew rate for
the instrument while Slew Rate Priority will use a user-configured
slew rate.
Before setting the power supply to C.V. mode,
ensure:
The output is off.
The load is connected.
1. Press the Function key. The
Function
Function key will light up.
2. The display will show the function (F-01)
voltage display and the setting for the function
in the current display.
Function
number
Function
setting
3. Rotate the Voltage knob to change
the F setting to F-03 (V-I Mode
Slew Rate Select).
10. Press the Output key. The
Output ON LED becomes
lit.
When setting the power supply to constant current mode, a voltage
limit must also be set to determine the crossover point. When the
voltage exceeds the crossover point, the mode switches to C.V.
mode. For details about C.C. operation, see page 21. C.C. and C.V.
mode have two selectable slew rates: High Speed Priority and Slew
Rate Priority. High Speed Priority will use the fastest slew rate for
the instrument while Slew Rate Priority will use a user-configured
slew rate.
The panel lock feature prevents settings from being changed
accidentally. When activated, the Lock/Local key will become
illuminated and all keys and knobs except the Lock/Local key and
Output key (if active) will be disabled.
If the instrument is remotely controlled via the USB/LAN interface,
the panel lock is automatically enabled.
When using local sense, the sensing terminals are connected to the
local sense terminals (via the local sense connections) and thus do
not compensate for any possible voltage drop that is seen on the
load cables. Local sense is only recommended when the voltage
drop is of no consequence or for load-current applications. By
default, the sense plug is already configured to local sensing.
T3PSLoad
Output
Output
S-
LS-
LS+
S+
Input
Input
Page 54
Remote sense is used to compensate for the voltage drop seen
across load cables due to the resistance inherent in the load cables.
The remote sense terminals are connected to the load terminals of
the DUT to determine the voltage drop across the load cables.
Remote sense can compensate up to 1 volt (T3PS062001P), 2 volts
(T3PS40381P), 3 volts (T3PS60251P). Load cables should be chosen
with a voltage drop less than the compensation voltage.
Although you can use remote sense to compensate up to 3V for a
single line, it is recommended that the voltage drop is minimized to
a maximum of 1V to prevent excessive output power consumption
from the power supply and poor dynamic response to load changes.
This section describes the basic operations required to operate the
power supply in series or parallel. Operating the T3PS series in
parallel increases the total current output of the power supply units.
When used in series, the total output voltage of the power supplies
can be increased.
When the units are used in parallel or in series, a number of
precautions and limitations apply. Please read the following
sections before operating the power supplies in parallel or series.
When connecting the T3PS power supplies in
parallel, up to 4 units can be used in parallel and
all units must be of the same model with similar
output settings.
To use the power supplies in parallel, units must
be used in a aster-slave configuration. In the
master-
power supplies. In order for the master unit to
control the slave units, the master unit must use
the analog control connector to control the slave
units.
When using the Analog Control Connector, the
connector must be wired correctly between the
master and each of the slave units. For the
complete connector pin assignment, see page 98.
The parallel calibration function can be used to
offset cables losses.
External Voltage and Resistance Control
Voltage/Resistance controlled remote control
can only be used with the master unit.
The full scale current (in parallel) is equivalent
to the maximum external voltage or resistance.
Internal Resistance
For 2 units in parallel, the internal resistance is
actually half of the setting value.
For 3 units in parallel, the internal resistance is
actually a third of the setting value.
For 4 units in parallel, the internal resistance is
actually a fourth of the setting value.
See function setting F-08 for internal resistance
settings, page 84.
Bleeder Control
The Master unit is used to control the bleeder
settings. The bleeder resistors in all the slave
units are always turned off when in parallel
mode.
Model1 unit 2 units 3 units 4 units
T3PS062001P6V6V6V6V
To operate the power supplies in parallel with the
analog connectors, connect the analog connectors
on the master and slave units as shown in the
diagrams below.
The F-16 function setting can be used to calibrate
the output of T3PS units connected in parallel.
If you feel the accuracy is not good enough when
you measure the accuracy in parallel mode, the
parallel calibration can be used to get better
measurement accuracy.
1. Short all the terminals together. This is best
accomplished by connecting the master and all
the slave units in parallel and then shorting the
output terminals.
Master
Output
Output
Ground
Slave #1, 2, 3
Output
Output
Ground
Short
2. Connect the slave units to the
master unit using the analog
control connectors as described
previously.
3. Configure F-93 (Master/Slave)
setting for each master/slave unit,
as described previously.
4. Cycle the power on the units (reset the power).
When connecting T3PS power supplies in series,
up to 2 units can be used in series and all units
must be of the same model. When operated in
series, the power supplies can be used to increase
the voltage output or setup the power supplies to
output both positive and negative polarities.
Unlike with the parallel operation, the series
operation does not require any special
configuration as each power supply is operated
and controlled individually.
When the units are used in series, a number of
precautions and limitations apply. Please read this
overview before operating the power supplies in
series.
Ext-V
Ext-R
VMON
IMON
Ext-V
Ext-R
VMON
IMON
Master
Load
Slave
Display
Master and slave units display both the current
and the voltage. The total voltage is the sum of
the units.
The OVP and OCP protections are tripped
independently on the master and slave.
Remote monitoring
Voltage monitoring (VMON) and current
monitoring (IMON) should be performed on
both units.
The VMON voltage represents the voltage of
that particular unit.
Remote Sense
Please see the voltage sense chapter for details,
page 54.
External Voltage and Resistance Control
Voltage/Resistance controlled remote control
should be used on both units separately.
The full scale voltage (in series) is equivalent to
the maximum external voltage or resistance.
Slew Rate
The slave rate should be set for both units.
Internal Resistance
The internal resistance should be set for both
units.
Bleeder Control
The bleeder resistor setting should be set
equally on both units.
or measure with T3PS
series, make sure that each unit is separated and
floating from each other.
When T3PS
and the load or one of the output terminals is
grounded, no point on the output shall be more
than 600VDC above or below chassis ground.
If using the T3PS in series, please be aware that each unit acts
independently and thus there are no special communication buses
for serial connections.
1. Ensure the power is off on both power supplies.
2. Connect the master and slave unit in series as
shown above to either increase the voltage
output or to create a positive and negative
output. Remember that how the units are
grounded depends on the configuration of the
series connection.
3. Use diodes across the output terminals to
prevent reverse voltage at startup or if one of
the units unexpectedly shuts down. Ensure the
diodes are rated to withstand the voltage and
current output of the power supply.
Before using the power supplies in series, the
master and slave units need to be configured.
1. Configure the OVP, OCP and UVL
settings for each unit.
2. For each unit, hold the Function key while
turning the power on to enter the power on
configuration settings.
VoltageCurr ent
VOLTAGECURRENT
VSR LAN RMT ERR DLY ALM ISR M1 M 2 M3 RU N
Lock/Local PROT Function Test Set
:LongPush
Unlock ALM_CLR M1 M 2 M3
CC
CV
A
V
Shift
Output
3. Make sure each unit is set to
Independent (F-93 = 0). When
using the power supplies in series,
each unit is operated individually,
and thus no unit is considered the
master or slave.
F-93
0
4. Cycle the power on the units (reset the power).
Only operate the power supplies in series if the
units are configured correctly.
unit will only show the voltage and current of
their own unit.
2. Operation of both units is the
as for a single unit. Each unit will
only draw as much power as is
programmed. Please see the basic
operation chapter for details.
3. Press the Output key on
each unit to begin. The
output LED will become lit.
Configuration of the T3PS power supplies is divided into five
different configuration settings: Normal Function, USB, LAN,
UART, System Configuration Settings, Power ON Configuration,
Trigger Input/Output Configuration Settings and Special Function
Settings. Power ON Configuration differs from the other settings in
that the settings used with Power ON Configuration settings can
only be set during power up. The other configuration settings can
be changed when the unit is already on. This prevents some
important configuration parameters from being changed
inadvertently. Power On Configuration settings are numbered F-90
to F-98 and the other configuration settings are numbered F-00 to F61, F-70 to F-78, F-88 to F-89 and F100 to F122. The Special Function
Settings are used for calibration, firmware updated and other
special functions; these functions are not supported for end-user
use.
Please use the configuration settings listed below when applying
the configuration settings.
Sets the falling voltage slew rate. Only applicable if
Sets the falling current slew rate. Only applicable if
for CV or CC mode. The voltage or current slew
rate can only be edited if CC/CV Slew Rate
Priority is selected. The ISR indicator will be lit for
CC Slew Rate Priority and the VSR indicator will
be lit for CV Slew Rate Priority.
Note: CC and CV Slew Rate Priority mode are
disabled when voltage/current output is set to
external control.
F-030 = CV high speed priority
1 = CC high speed priority
2 = CV slew rate priority
3 = CC slew rate priority
Sets the rising voltage slew rate. Only applicable if
V-I Mode is set to CV Slew Rate Priority.
F-040.001-max. V/msec
V-I Mode is set to CV Slew Rate Priority.
F-050.001-max. V/msec
Sets the rising current slew rate. Only applicable if
V-I Mode is set to CC Slew Rate Priority.
F-060.001-max. A/msec
V-I Mode is set to CC Slew Rate Priority.
F-070.001-max. A/msec
Bleeder control turns ON/OFF the bleeder resistor.
Sets the OCP delay time. This parameter will delay
F-080.000 -
(Where X.XXX = Rating Voltage /
Rating Current)
Bleeder resistors discharge the filter capacitors
after power is turned off as a safety measure.
F-090 = OFF, 1 = ON, 2 = AUTO
Turns the buzzer sound on or off. The buzzer is
associated with alarm sounds and keypad entry
sounds.
F-100 = OFF, 1 = ON
the amount of time it takes to trigger the over
current protection. This function can be useful to
prevent current overshoot from triggering OCP.
F-120.1-2.0 sec
Turns the current setting limit (I-limit) on or off.
Turning this function on will prevent you from
accidentally setting the current limit above the set
OCP level.
F-130 = OFF, 1 = ON
Turns the voltage setting limit (V-limit) on or off.
Turning this function on will prevent you from
accidentally setting the voltage limit above the
OVP level.
F-140 = OFF 1 = ON
Displays which memory setting is recalled (M1,
M2 or M3) when recalling a setup.
Sets the SCPI emulation mode. The emulation
modes allow you to emulate the remote commands
of legacy equipment that is used in a test
environment. Parameter 2, 3 and 4 are only
supported as use stand alone.
F-26
Displays the MAC address in 6 parts. This setting
is not configurable.
This is used primarily for multi-unit remote
control, see page 126.
F-750 = SCPI, 1 = Emulation mode
UART Address: this is used to set the address of a
unit when using multi-unit remote control, see
page 126 for details.
F-760-30
Sets the master/slave/display-information
parameters of a unit when using Multi-Drop
remote control, see page 126 for details.
F-770 = Disable, 1 = Master, 2 = Slave,
3 = Display Information
Displays the Multi-Drop status on the master unit
for each slave unit belonging to the Multi-Drop
bus, see page 126 for details.
F-78Displayed parameter: AA-S
AA: 00-
S: 0-1 (Off-line/On-line status).
Returns the T3PS to the factory default settings.
See page 140 for a list of the default settings.
F-880 = None, 1 = Factory Default.
Displays the T3PS version number, build date,
keyboard CPLD, analog board CPLD, analog
board FPGA, kernel build date, test command
version and test command build date.
0-XX = Version (1/2)
1-XX = Version (2/2)
F-89
2-XX = Build year (1/2)
3-XX = Build year (2/2)
4-XX = Build month
5-XX = Build day
6-XX = Keyboard CPLD (1/2)
7-XX = Keyboard CPLD (2/2)
8-XX = Analog board CPLD (1/2)
9-XX = Analog board CPLD (2/2)
A-XX = Analog board FPGA (1/2)
B-XX = Analog board FPGA (2/2)
C-XX = Kernel build year (1/2)
D-XX = Kernel build year (2/2)
E-XX = Kernel build month
F-XX = Kernel build day
G-XX = Test command version (1/2)
H-XX = Test command version (2/2)
I-XX = Test command build year (1/2)
J-XX = Test command build year (2/2)
K-XX = Test command build month
L-XX = Test command build day
M-XX = Reserved (1/2)
N-XX = Reserved (2/2)
O-XX = Option module (1/2)
P-XX = Option module (2/2)
Sets the constant voltage (CV) control mode
between local and external voltage/resistance
control. For external voltage control, see page 101
(External Voltage Control of Voltage Output) and
page 106 (External Resistance Control of Voltage
Output).
F-900= Control by local
1 = Control by external voltage
2 = Control by external resistor rising
3 = Control by external resistorfalling
4 = Control by isolated board
between local and external voltage/resistance
control. For details on external voltage control, see
page 104 (External Voltage Control of Current
Output) and 108 (External Resistance Control of
Current Output).
F-910 = Control by local
1 = Control by external voltage
2 = Control by external resistor -
rising
3 = Control by external resistor-
falling
4 = Control by isolated board
Sets the power supply to turn the output on or off
at power up.
F-920 = Safe Mode (Always OFF),
1 = Force Mode (Always ON),
time Power OFF)
Sets the power supply as master or slave. See the
parallel/series operation for details, page 60.
F-930 = Independent
1 = Master with 1 slave in parallel
2 = Master with 2 slaves in
parallel
3 = Master with 3 slaves in
parallel
4 = Slave (parallel)
Sets the external logic as active high or low for
analog control pin 19.
function is accessed. Please see your distributor for
received.
1 = M1
F106
Trigger output pulse width. A setting of 0 will
output the active level.
F1200-60ms. 0 = output active level
Sets the active level of the output trigger if the
trigger output pulse width (F120) = 0.
F121
Sets the trigger source.
F1220 = None
2 = M2
3 = M3
0 = LOW
1 = HIGH
1 = Switching the output on/ off
2 = Changing a setting
3 = Recalling a memory
The special function setting is used to access
calibration, firmware updates and other special
functions. The special function setting has a
password that is used to access the special function
menu. The password used determines which
The Analog Control chapter describes how to
control the voltage or current output using an
external voltage or resistance, monitor the
voltage or current output as well as remotely
turning off the output or shutting down the
power supply.
Analog Control Connector Overview..........................................98
External Voltage Control of Voltage Output ...........................101
External Voltage Control of Current Output ...........................104
External Resistance Control of Voltage Output ......................106
External Resistance Control of Current Output ......................108
External Control of Output .........................................................111
External control of Shutdown .....................................................113
External Voltage and Current Monitoring ................................115
External Operation and Status Monitoring...............................117
The T3PS power supply series have a number of analog control
options. The Analog Control connectors are used to control output
voltage and current using external voltage or resistance. The power
supply output can also be controlled using external switches.
connector that can be used with the ARC (analog
remote control) kit for wiring connections. The
connector is used for al
pins used determine what remote control mode is
used.