Teledyne NV-100 User Manual

HASTINGS VACUUM GAUGES
MODEL NV-100
TELEDYNE BROWN ENGINEERING
HASTINGS INSTRUMENTS
P.O.BOX 1436
HAMPTON, VIRGINIA 23661 U.S.A.
TELEPHONE (804)723-6531
TWX (710)882-0085
EASYLINK: 62300280
© May 1994
103A - PAGE 1
Hastings Instruments reserves the right to change or modify the design of its equipment without any obligation to provide notification of change or intent to change.
103A - PAGE 2
GENERAL
The Hastings Model NV-100 Vacuum Gauge is a complete self contained instrument with all circuits mounted on the rear of the meter case. A remote type DV-100 gauge tube is used as the pressure sensor. The instrument measures pressures over the range of 0.1 to 100 Torr utilizing the well known Hastings directly heated thermopile. Unlike other Hastings gauges, this instrument operates in a constant temperature mode rather than constant applied voltage. The changes in power to create a constant temperature rise above ambient are measured by the indicating meter as a function of pressure. Corrections for gasses of differing thermal conductivities are necessary as in all thermal conductivity type vacuum gauges.
INSTALLATION
The instrument is factory calibrated and ready for use when received. All that is necessary to place the gauge in operation is to install the gauge tube into the system, plug in the gauge tube cable, and connect the power cord to the AC line. Gauge tubes should be installed with the open end pointing downward so as to be self draining. On dusty or dirty systems, a Hastings particle drop-out (protective) trap is recommended (see Product Bulletin #352).
OPERATION
The gauge is in operation once connected to the gauge tube and power. An initial check of the mechanical meter zero may be necessary upon receipt. To do this, unplug the power cord and set (if necessary) the meter mechanical zero adjustment the front of the meter to read "ATM". On the rear of the instrument are two calibration adjustments, they should be correct as received. An occasional check of the ATM adjustment may be desirable. Also, anytime a new gauge tube is replaced it is desirable to reset the ATM adjustment.
To do this, expose the tube to atmospheric pressure after the gauge is fully warmed up (about 30 minutes) and adjust the trim potentiometer marked ATM until the needle reads ATM. Use of a trim potentiometer tuning tool will facilitate this adjustment.
NOTE: When turned off, the meter needle rests at the right side of the meter (ATM mark).
When no tube is plugged in, the instrument reads off the scale below zero. If a broken gauge tube is plugged in it will read off scale above ATM. Replace with a new gauge tube.
The circuit has a protective shut-down circuit. This shuts down the electronics whenever a gauge tube is not plugged into the socket. This is to prevent burning out gauge tubes by application of excessive power surges when plugging in or unplugging gauge tubes. A delay circuit applies power gently when connected. Pins 1 and 2 of the gauge tube activate the circuit and act as the interlock switch. Thus the instrument will not operate unless the correct gauge tube is used. Troubleshooting the circuit on a bench cannot be accomplished unless these two pins are jumpered at the gauge tube socket, or a DV-100 gauge tube is plugged into the socket.
TROUBLE SHOOTING
If troubles develop, always try a new gauge tube before suspecting other problems. To check gauge tubes for continuity of thermocouples, first make sure that the gauge tube is at atmospheric pressure, then using an ohmmeter check for continuity between pins 3,5 and 7. Approximately 10 ohms resistance is read between all combinations of these three pins on a good tube. If open, replace the tube. Never check while under vacuum as the ohmmeter may burn out the gauge tube. Pins 1 and 2 should show zero ohms. Trouble shooting the electronics is difficult because this is a closed loop feed-back circuit. If circuit problems develop, it is best to return it to the factory for repair.
103A - PAGE 3
Loading...
+ 6 hidden pages