Taylor 772 Installation Manual

OPERATOR’S MANUAL
Model 702 & 772
Navy Soft Serve Freezers
Original Operating Instructions
051469- M
December, 1998 (Original Publication)
(Updated 12/6/13)
Taylor Distributor:
Address:
Phone:
Service:
Parts:
Date of Installation:
Information found on the data label:
Model Number:
Serial Number:
Electrical Specs: Voltage Cycle
Phase
Maximum F use Size: A
Minimum Wire Ampacity: A
E 1998 Carrier Commercial Refrigeration, Inc.
051469- M Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a violation of Copyright Law of the United States of America and other countries, could result in the awarding of Statutory Damages of up to $250,000 (17 USC 504) for infringement, and may result in further civil and criminal penalties. All rights reserved.
Taylor Company
a division of Carrier Commercial Refrigeration, Inc. 750 N. Blackhawk Blvd. Rockton, IL 61072
Table of Contents
Section 1 To th e Installer 1............................................
Installer Safety 1........................................................
Site Preparation 1.......................................................
Running Specifications 3.................................................
Section 2 Thermistor Control 5........................................
Section 3 Semi- Assembled Navy Units 8...............................
Disassembly 8..........................................................
Assembly 9............................................................
Semi- Assembled Model 702 Exploded View 11..............................
Section 4 To the Operator 13...........................................
Section 5 Safety 14....................................................
Section 6 Operator Parts Identification 16...............................
Model 702 16............................................................
Model 702 Door Assembly 17.............................................
Model 772 18............................................................
Model 772 Door Assembly 19.............................................
Section 7 Important: To the Operator 20.................................
Indicator Light “Mix Low” 20...............................................
Symbol Definitions 20....................................................
Control Switch 20........................................................
Reset Button 20.........................................................
Thermistor Control 21....................................................
Draw Rate 21............................................................
Optional Features 21.....................................................
Section 8 Operating Procedures 22.....................................
Assembly 22............................................................
Sanitizing 24............................................................
Priming 25..............................................................
Closing Procedure 26....................................................
Draining Product From the Freezing Cylinder 27.............................
Rinsing 27..............................................................
Cleaning 27.............................................................
Disassembly 27..........................................................
Brush Cleaning 28.......................................................
Section 9 Important: Operator Checklist 29..............................
During Cleaning and Sanitizing 29.........................................
Troubleshooting Bacterial Count 29........................................
Regular Maintenance Checks 29...........................................
Winter Storage 30........................................................
Section 10 Troubleshooting Guide 31....................................
Troubleshooting Thermistor Components 34................................
Table of Contents Models 702 & 772
Table of Contents - Page 2
Section 11 Parts Replacement Schedule 35...............................
Section 12 Service Parts Functions 36...................................
Section 13 Limited Warranty on Equipment 37............................
Section 14 Limited Warranty on Parts 39.................................
Section 15 Parts List 42.................................................
Wiring Diagrams 48......................................................
Section 16 Motor Characteristics 52......................................
702 - Motor Characteristics and Performance Data 52........................
702 - Controller Data 53..................................................
702 - Motor Characteristics and Performance Data 54........................
702 - Controller Data 55..................................................
702 - Motor Characteristics and Performance Data 56........................
702 - Controller Data 57..................................................
772 - Motor Characteristics and Performance Data 58........................
772 - Controller Data 59..................................................
772 - Motor Characteristics and Performance Data 60........................
772 - Controller Data 61..................................................
772 - Motor Characteristics and Performance Data 62........................
772 - Controller Data 63..................................................
Section 17 Navy Specifications 64.......................................
Note: Continuing research results in steady improvements; therefore, information in this manual is subject to change without notice.
Note: Only instructions originating from the factory or its authorized translation representative(s) are considered to be the original set of instructions.
E 1998 Carrier Commercial Refrigeration, Inc. (Original Publication)
(Updated December, 2013) 051469- M Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a violation of Copyright Law of the United States of America and other countries, could result in the awarding of Statutory Damages of up to $250,000 (17 USC 504) for infringement, and may result in further civil and criminal penalties. All rights reserved.
Taylor Company
a division of Carrier Commercial Refrigeration, Inc. 750 N. Blackhawk Blvd. Rockton, IL 61072
Models 702 & 772
Table of Contents
Section 1 To the Installer
The following information has been included in the manual as safety and regulatory guidelines. For complete installation instructions, please see the Installation Checklist.
Installer Safety
In all areas of the world, equipment should be installed in accordance with existing local codes. Please contact your local authorities if you have any questions.
Care should be taken to ensure that all basic safety practices are followed during the installation and servicing activities related to the installation and
service of Taylor® equipment.
S Only authorized Taylor service personnel
should perform installation, maintenance, and repairs on Taylor equipment.
S Authorized service personnel should consult
OSHA Standard 29CFRI910.147 or the applicable code of the local area for the industry standards on lockout/tagout procedures before beginning any installation or repairs.
S Authorized service personnel must ensure
that the proper protective equipment (PPE) is available and worn when required during installation and service.
S Authorized service personnel must remove
all metal jewelry, rings, and watches before working on electrical equipment.
The main power supply(s) to the unit must be disconnected prior to performing any installation, maintenance, or repairs. Failure to follow this instruction may result in personal injury or death from electrical shock or hazardous moving parts as well as poor performance or damage to the unit.
Site Preparation
Review the area where the unit will be installed. Make sure that all possible hazards to the installer, user, and the unit have been addressed.
For Indoor Use Only: This unit is designed to operate indoors, under normal ambient
temperatures of 70°-75°F(21°-24°C). The unit has
successfully performed in high ambient
temperatures of up to 104°F(40°C) at reduced
capacities.
This unit must NOT beinstalledinanarea where a water jet or hose can be used. NEVER use a water jet or hose to rinse or clean the unit. Failure to follow this instruction may result in electrocution.
This unit must be installed on a level surface to avoid the hazard of tipping. Extreme care should be taken in moving this unit for any reason. Two or more persons are required to safely move this unit. Failure to comply may result in personal injury or damage to the unit.
The authorized installer should inspect the unit for damage and promptly report any damage to the local authorized Taylor distributor.
This unit is made using USA sizes of hardware. All metric conversions are approximate and vary in size.
DO NOT install the machine in an area where a water jet could be used. Failure to follow this instruction may result in serious electrical shock.
131206
Models 702 & 772 To the Installer
1
Water Connections (Water Cooled Units On ly)
An adequate cold water supply must be provided with a hand shut- off valve. On the underside rear of the base pan, two 3/8” I.P.S. (for single head units) or two 1/2” I.P.S. (for double head units) water connections for inlet and outlet have been provided for easy hook- up. 1/2” inside diameter water lines should be connected to the machine. (Flexible lines are recommended, if local codes permit.) Depending on local water conditions, it may be advisable to install a water strainer to prevent foreign substances from clogging the automatic water valve. There will be only one water “in” and one water “out” connection for both single head and double head units. DO NOT install a hand shut- off valve on the water “out” line! Water should always flow in this order: first, through the automatic water valve; second, through the condenser; and third, through the outlet fitting to an
opentrapdrain.
A back flow prevention device is required
on the incoming water connection side. Please
refer to the applicable National, State, and local codes for determining the proper configuration.
Air Cooled Units
DO NOT obstruct the unit’s air intake and discharge openings:
Model 702 units require a minimum of 3” (76 mm) clearance on both sides, and 6” (152 mm) on the back. Model 772 units require a minimum of 3” (76 mm) clearance around all sides of the freezer. This is necessary to allow for adequate air flow across the condenser(s).
Failure to allow adequate clearance can reduce the refrigeration capacity of the freezer and possibly cause permanent damage to the compressor.
Electrical Connections
In the United States, this unit is intended to be installed in accordance with the current edition of the National Electrical Code (NEC), ANSI/NFP A 70 which governs the installation of the unit at the local governmental level.
The purpose of the NEC code is the practical safeguarding of persons and property from hazards arising from the use of electricity. This code contains provisions considered necessary for safety.
In all other areas of the world, the unit should be installed in accordance with the existing local codes. Please contact your local authorities.
Each unit requires one power supply for each data label on the unit. Check the data label(s) on the unit for branch circuit overcurrent protection or fuse, circuit ampacity, and other electrical specifications. Refer to the wiring diagram provided inside of the electrical box for proper power connections.
FOLLOW YOUR LOCAL ELECTRICAL CODES!
CAUTION: THIS UNIT MUST BE PROPERLY GROUNDED! FAILURE TO DO SO CAN RESULT IN SEVERE PERSONAL INJURY FROM ELECTRICAL SHOCK!
An equipotential grounding lug is provided with this unit. Some countries require the grounding lug be properly attached to the rear of the frame by the authorized installer. The installation location is marked by the equipotential bonding symbol (5021 of IEC 60417-1) on both the removable panel and the unit’s frame.
S Stationary appliances which are not
equipped with a power cord and a plug or another device to disconnect the appliance from the power source must have an all-pole disconnecting device with a contact gap of at least 3 mm installed in the external installation.
S Appliances that are permanently connected
to fixed wiring and for which leakage currents may exceed 10 mA, particularly when disconnected or not used for long periods, or during initial installation, shall have protective devices such as a GFI, to protect against the leakage of current, installed by the authorized personnel to the local codes.
To the Installer
2
Models 702 & 772
S Supply cords used with this unit shall be
oil-resistant, sheathed flexible cable not lighter than ordinary polychloroprene or other equivalent synthetic elastomer-sheathed cord (Code designation 60245 IEC 57) installed with the proper cord anchorage to relieve conductors from strain, including twisting, at the terminals and protect the insulation of the conductors from abrasion.
If the supply cord is damaged, it must be replaced by an authorized Taylor service technician in order to avoid a hazard.
Running Specifications
Expansion Valve Setting
404A/HP62: 20 to 22 PSI (138 to 152 kPa.) for normal products at temperatures of 18 to 20_F. ( - 7. 8 t o
-6.7_C.).
Low Side Pressure
Low side pressure = expansion valve setting.
Water Cooled: High side pressure for water cooled units is determined by the water valve. The water valve is factory set to maintain a high pressure of 235 PSI (1,620 kPa.). To adjust the high pressure, place the gauge on the high side access port. Turn the adjustment knob on the water valve clockwise to lower the high side pressure and counterclockwise to raise the pressure.
The high side pressure switch is factory set at 440 PSI (3,034kPa) for 404A/HP62. In the event of a water loss, this switch will sense a rise in pressure and deactivate the freezer.
Check Out
Once the unit is installed, it is advisable to check the following controls and mechanical operations of the freezer and to make any necessary adjustments. If applicable, repeat these checks for the second freezing cylinder on double head units.
Controls
To adjust the low side pressure, place the gauge on the low side suction port at the compressor. With the compressor running, turn the adjustment knob of the automatic expansion valve clockwise to raise low side pressure and counterclockwise to lower pressure.
High Side Pressure
Air Cooled: The following chart indicates normal
operating head pressures at various ambient temperatures:
Ambient Temperature
F. C. PSI
70_ 21.1_ 240 - 270
80_ 26.7_ 270 - 300
90_ 32.2_ 300 - 340
100_ 37.8_ 340 - 380
Note: This chart applies to units using 502 or 404A refrigerant.
Normal Operating
Head Pressures
(1,655 - 1,862 kPa.)
(1,862 - 2,069 kPa.)
(2,069 - 2,344 kPa.)
(2,344 - 2,620 kPa.)
Place the control switch in the “AUTO” position. The main refrigeration system will operate (compressor, beater motor , and the condenser fan). The dial light and the mix low indicator will be lit.
Figure 1
If the freezer is water cooled, the automatic water valve will begin to open and cold water will flow into the condenser. This will remove heat from the refrigerant. As the water flows into the open trap drain, it should be warm to the touch. Place the control switch in the “OFF” position.
Models 702 & 772 To the Installer
3
Beater Rotation
Beater rotation must be clockwise as viewed
looking into the freezing cylinder. Beater rotation must be clockwise as viewed looking
into the freezing cylinder. To correct rotation on a three- phase unit, interchange
any two incoming power supply lines at the freezer main terminal block only.
To correct rotation on a single- phase unit, exchange leads inside the beater motor. (Follow the diagram printedonthemotor.)
Electrical connections are made directly to the terminal block provided in the main control box located behind the upper left side panel for the Model 702, and behind the service panel for the Model 772.
Note: Electrical connections should be performed by a trained service technician.
Gear Alig n ment
To prevent costly parts damage and to prevent excessive mix leakage, the gear unit must be perfectly aligned. To check gear alignment, insert the drive shaft through the rear shell bearing and into the gear unit. Move the drive shaft in and out of the gear unit, using all positions of the hex end. If any binding of the drive shaft occurs, the gear unit could be out of alignment.
Inspect the bolts which mount the gear unit. make sure they are tightened down.
To prevent excessive mix leakage, check the rear shell bearing. The locking tab should be folded over the nut to prevent the nut from working loose.
To the Installer
4
Models 702 & 772
Section 2 Thermistor Control
Function
The thermistor control maintains temperature in the freezing cylinder by monitoring the resistance of the thermistor probe.
Specifications
Temperature Differential: cut in = 2_F. (1. 1 _C.)
above cut- out.
Coarse Adjustment Range: 10_ to 30_F. ( - 12_ to
-1_C.).
Fine Adjustment Range:4_F. (2 _C.) total.
Coarse Adjustment Potentiometer: 1/4 turn =
approximately 6_F. (3 _C.).
Input Voltage Supply: 24 VAC.
Thermistor Probe (Part # 038061- BLK)
The resistance value of the thermistor probe corresponds with the product temperature in the freezing cylinder. As the product becomes colder, the probe resistance increases. As the product becomes warmer, the probe resistance decreases.
Approximate probe resistance readings:
1. 10,000 ohms at room temperature (78_F. / 25_C.).
2. 46.012 ohms at product temperature (20_F. /
-6.6_C.).
Operation
The thermistor probe is positioned in the bulb- well located at the front of the freezing cylinder. The thermistor control becomes operational when powered by the 24 VAC transformer.
When the desired product is achieved (control set- point) the thermistor control relay opens and discontinues the power sent to the compressor relay coil.
When the product in the freezing cylinder reaches 2_F. (1_C.) above the control set- point, the thermistor relay closes, sending L1 power to the compressor relay coil. The refrigeration system will run until the control set- point is achieved.
Anticipator
The anticipator signals the thermistor control to activate the refrigeration system whenever product is drawn. As the draw valve is raised (freezer draw switch closes), continuity is created between the thermistor control anticipator terminals. The thermistor control relay will close within 1 second to start the refrigeration system.
Upon completing the draw, the thermistor control recognizes the loss of continuity between the anticipator terminals, but will continue refrigeration for at least 25 seconds. This allows for additional blending and freezing of the warmer mix which has entered the freezing cylinder. After approximately 25 seconds have elapsed, the thermistor control returns to normal operation and cycles off the refrigeration system when the set- point temperature is achieved.
Models 702 & 772 Thermistor Control
5
Setting Temperature
1. Position the thermistor fine adjustment at mid- range. This will limit the fine adjustment temperature range to 2_F. ( 1_C.).
ELECTRICAL SHOCK AREA! USE CAUTION!
2. Turn the coarse adjustment clockwise to the coldest setting.
3. With the freezer correctly primed, place the control switch in the “AUTO” position.
4. After the appropriate freezing time, test the product temperature. When a sample portion temperature is approximately 1_ above the desired temperature setting, slowly turn the coarse adjustment counterclockwise (warmer) until the refrigeration system cycles off.
5. Allow the refrigeration system to cycle through at least two “off” cycles. After the unit cycles off, draw a sample of product and check the temperature. Readjust the coarse adjustment as required, but make only small adjustments.
Note: The anticipator automatically activates the refrigeration system 0 - 1 second after the draw valve is opened. If several small samples are drawn, the temperature may drift lower. To accurately set the control, let the product temperature stabilize by allowing the thermistor control to cycle the f reezer on and off by the control set point instead of the anticipator.
1. Make sure power is being supplied to the freezer and that all operating switches are in the correct position.
2. Using a voltmeter, check the voltage supply to the thermistor control. The control requires 24 volts to operate.
3. Using an ohmmeter, check probe resistance. (Refer to the thermistor curve chart on page 7 for proper readings.)
If the thermistor relay which deactivates the compressor will not open, check the following items:
ELECTRICAL SHOCK AREA! USE CAUTION!
1. Make sure the thermistor relay opens when the freezer control switch is in the “OFF” position.
Service Tips
If a problem arises with the thermistor control assembly, identify and replace only the faulty component. For example, if the probe is defective, replace only the probe.
A varistor must be connected to the thermistor control’s 24 VAC terminals in order to protect the control from voltage spikes (varistor part number X31547).
Fill the bulb- well with automotive antifreeze before installing the thermistor probe, and be sure the probe is installed completely into the bottom of the bulb- well.
Note: Lower the probe to the point where the wires extend from the probe and a resistance is felt. This indicates the probe is installed completely in the bottom of the bulb- well.
If the thermistor relay which starts the compressor will not close, check the following items:
2. Make sure the thermistor probe is connected to the correct probe terminals.
3. Using an ohmmeter, check the thermistor probe for proper resistance. (Refer to the thermistor curve chart on page 7 for proper readings.)
4. Disconnect one wire to an anticipator terminal. If the thermistor relay opens after approximately 25 seconds, the problem is in the anticipator wiring circuit.
When problems such as erratic product quality occur, it is of utmost importance to determine if the thermistor components are defective before replacing them.
See page 34 for Troubleshooting Thermistor Components.
Thermistor Control
6
Models 702 & 772
Thermistor Curve Chart
F. C. KOHM F. C. KOHM F. C. KOHM
-10 - 23.3 118.201 22 -5.5 43.530 54 12.2 17.915
-9 - 22.7 114.394 23 -5.0 42.340 55 12.7 17.451
-8 - 22.2 110.709 24 -4.4 41.136 56 13.3 16.998
-7 - 21.6 107.143 25 -3.8 39.967 57 13.8 16.557
-6 - 21.1 103.692 26 -3.3 38.830 58 14.4 16.128
-5 - 20.5 100.352 27 -2.7 37.727 59 15.0 15.710
-4 - 20.0 97.120 28 -2.2 36.654 60 15.5 15.315
-3 - 19.4 94.085 29 -1.6 35.612 61 16.1 14.929
-2 - 18.8 91.144 30 -1.1 34.599 62 16.6 14.554
-1 - 18.3 88.296 31 -0.5 33.616 63 17.2 14.187
0 - 17.7 85.536 32 0 32.660 64 17.7 13.830
1 - 17.2 82.863 33 0.5 31.760 65 18.3 13.482
2 - 16.6 80.273 34 1.1 30.885 66 18.8 13.143
3 - 16.1 77.765 35 1.6 30.035 67 19.4 12.812
4 - 15.5 75.334 36 2.2 29.207 68 20.0 12.490
5 - 15.0 72.980 37 2.7 28.403 69 20.5 12.185
6 - 14.4 70.627 38 3.3 27.620 70 21.1 11.888
7 - 13.8 68.350 39 3.8 26.859 71 21.6 11.598
8 - 13.3 66.147 40 4.4 26.120 72 22.2 11.315
9 - 12.7 64.014 41 5.0 25.400 73 22.7 11.039
10 - 12.2 61.951 42 5.5 24.721 74 23.3 10.769
11 -11.6 59.953 43 6.1 24.059 75 23.8 10.507
12 -11.1 58.021 44 6.6 23.416 76 24.4 10.250
13 - 10.5 56.150 45 7.2 22.789 77 25.0 10.000
14 - 10.0 54.340 46 7.7 22.180 78 25.5 9.763
15 -9.4 52.854 47 8.3 21.586 79 26.1 9.532
16 -8.8 51.409 48 8.8 21.009 80 26.6 9.306
17 -8.3 50.003 49 9.4 20.447 81 27.2 9.085
18 -7.7 48.636 50 10.0 19.900 82 27.7 8.870
19 -7.2 47.306 51 10.5 19.384 83 28.3 8.659
20 -6.6 46.012 52 11.1 18.881 84 28.8 8.454
21 -6.1 44.754 53 11.6 18.392 85 29.4 8.254
When checking a thermistor probe, first determine the temperature at the probe and find it on this chart, along with the correct ohmmeter reading. If your ohmmeter reading varies from the correct reading, determine whether the difference is acceptable. If a probe is faulty, the difference will be great.
Models 702 & 772 Thermistor Control
7
Section 3 Semi- Assembled Navy Units
To disassemble and assemble the Model 702 unit for installation in a Navy submarine, perform the following steps. Use the illustrations on page 12 for the numerical references.
Disassembly
Step 1
Remove the rear panel, both lower side panels, and the control box cover.
Step 2
Remove the door assembly, the drip pan, the beater assembly, and the shaft from the front of the unit.
Step 3
Remove the decorative plate from the front of the unit, then the fasteners from the following: (1) 24V transformer , (2) draw switch, (3) thermistor board, and (4) hopper temperature control.
Step 4
Disconnect the mix low light wires, and remove the thermistor probe and mix hopper temperature probe from their respective bulb well locations.
Step 5
Using a drill (1/8” to 5/32” bit), remove all (8) hood rivets.
Step 6
Remove the upper side panels, (remove the rear screws, then the lower front screws, then swing the panel out and up to remove the upper front screws).
Step 7
Disconnect the beater motor wires from the right hand side of the beater motor start relay. Remove the high pressure cut out wire and blue wire from the beater motor relay overload. Disconnect the high pressure cutout wire to the #13 terminal on the compressor relay and disconnect the blue wire from the transformer (if applicable).
Step 8
Remove the main condenser fan motor wire and the orange with white stripe wire from the compressor relay #14 terminal and remove the splice caps from the white wires in the control box (save the white jumper wire). Remove the fan motor ground wire.
Step 9
Remove the splice cap from the Danfoss system white with black stripe wire and white wire. Disconnect and remove the control channel wires, the black and gray wire from mix level sensor, the white with red stripe wire from the compressor relay coil, and the orange wire from the beater motor relay coil.
Step 10
For 115 volt units, disconnect the capacitor relay box assembly wires from the compressor relay, (or on 460 volt units the transformer wires from the beater motor relay), in the control box. Disconnect the compressor wires at the compressor.
Step 11
Disconnect the purple mix low probe wire and remove the control box from the unit.
Step 12
Remove the belts from the pulleys.
Step 13
Remove the two allen screws that secure the gearbox to the rear shell support. Remove the two screws that secure the drip tray guide, and the two screws that secure the auxiliary compressor bracket to the rear shell support.
Step 14
Remove the two carriage bolts and nuts that secure the front of the shell to the front panel.
Step 15
Disconnect all 5 sets of refrigeration junction fittings (2 on auxiliary, and 3 on main system). Use two wrenches and do not allow copper tubing to twist.
Remove discharge line coupling from the bracket on right side.
Step 16
Fasten the Danfoss dryer/capillary tube assembly to the shell assembly to protect the capillary tube from damage.
Step 17
Remove the shell and hood assembly in one piece.
Step 18
Remove the rear corner trim from the frame.
Semi- Assembled Navy Units
8
Models 702 & 772
Step 19
Remove the front panel from the frame.
Step 20
Remove the condenser mounting screws (from the top of the bracket), remove the fan blade through the right side, and then remove the condenser, shroud, and receiver assembly.
Step 21
Remove the main compressor.
Step 22
Remove the fasteners that connect the top of the frame to the bottom of the frame. Remove the top half of the frame that includes the Danfoss compressor and condenser.
Assembly
Step 10
Slide the condenser, shroud and receiver assembly into place, then install the fan blade before bolting the condenser in. (Note: The fan blade should be positioned 1/3 within the shroud and 2/3 out.) Be sure the fan blade turns freely.
Attach the cap tube to the clips on the side of the condenser.
Step 11
Connect the compressor discharge coupling to the bracket on the right side of the shell. Connect all of the refrigerant couplings. Use two wrenches, and do not allow the copper tubing to twist. Perform leak check on both refrigeration systems.
Step 12
Install the belts on the pulleys.
Step 1
Mount the compressor to the base pan.
Step 2
Mount and fasten the upper frame with the auxiliary system to the lower frame. Fasten the auxiliary compressor support to the rear shell support.
Step 3
Install the front panel assembly and connect the drip tray guide to the rear shell support.
Step 4
Install the rear corner trim.
Step 5
Install the shell and hood assembly. Connect the dryer and cap tube assembly to the Danfoss condenser assembly. (Be very careful with the cap tube.)
Step 6
Install the two carriage bolts through the front panel assembly, and place the nuts on the bolts to secure the shell.
Step 7
Connect the gearbox to the rear shell support with two allen head screws.
Step 13
Install the control box assembly with two screws.
Step 14
Connect the beater motor wires to the right hand side of the beater motor start relay. Connect the capacitor relay box wires to the compressor relay (if applicable) or the black wires from the transformer to L1 and L2 on the beater motor relay. Reconnect the compressor wires at the compressor.
Step 15
Connect one high pressure cut out wire to the #95 terminal on the beater motor overload, and connect the blue wire from the control channel to the #96 terminal on the beater motor overload. Connect the other high pressure cutout wire to the #13 terminal on the compressor relay along with the blue wire from the transformer (if applicable).
Step 16
Connect one fan wire and orange with white stripe wire to the compressor relay #14 terminal, and splice the other fan wire and all white wires, in the control box, into two bundles using a white jumper wire. Connect the fan motor ground wire to the back of the box.
Step 8
Tighten the nuts on the carriage bolts, then tighten the screws that secure the gearbox.
Step 9
Using silicone, seal around the nose cone that protrudes through the front panel assembly.
Models 702 & 772 Semi- Assembled Navy Units
Step 17
Splice theDanfoss system white with black stripe wire. Connect the control channel wires: the black and gray wire to the mix level sensor, the white with red stripe wire to the compressor relay coil, and the orange wire to the beater motor relay coil.
9
Step 18
Connect the purple mix low probe wire.
Note: Double check all of the wire connections with the wiring diagram.
Step 22
Connect the mix low light wires, and replace the thermistor probe, and mix hopper temperature probe into their respective bulb well locations.
Step 19
Connect the power cord, supplied by the end user, and replace the control box cover.
Step 20
Replace the upper side panels and fasten the hood with rivets supplied (p/n: 022517).
Step 21
Replace all the panels.
Note: Be sure the thermistor probe bulb well has plenty of antifreeze before replacing the thermistor probe.
Step 23
Fasten all the components in the control channel area and install the decorative plate.
Step 24
Install the beater shaft, beater assembly and blade, door assembly, and the drip pan in the front of the unit.
Semi- Assembled Navy Units
10
Models 702 & 772
Semi- Assembled Model 702 Exploded View
Models 702 & 772 Semi- Assembled Navy Units
11
Semi- Assembled Navy Units
12
Models 702 & 772
Section 4 To the Operator
The freezer you have purchased has been carefully engineered and manufactured to give you dependable operation. The Taylor freezer, when properly operated and cared for, will produce a consistent quality product. Like all mechanical products, this machine will require cleaning and maintenance. A minimum amount of care and attention is necessary if the operating procedures outlined in this manual are followed closely.
This Operator’s Manual should be read before operating or performing any maintenance on your equipment.
Your Taylor freezer will NOT eventually compensate and correct for any errors during the set- up or filling operations. Thus, the initial assembly and priming procedures are of extreme importance. It is strongly recommended that all personnel responsible for the equipment’s operation review these procedures in order to be properly trained and to make sure that there is no confusion.
In the event that you should require technical assistance, please contact your local authorized Taylor Distributor.
Note: Your Taylor warranty is valid only if the parts are authorized T aylor parts, purchased from the local authorized Taylor Distributor, and only if all required service work is provided by an authorized Taylor service technician. Taylor reserves the right to deny warranty claims on units or parts if non- Taylor approved parts or incorrect refrigerant were installed in the unit, system modifications were performed beyond factory recommendations, or it is determined that the failure was caused by abuse, misuse, neglect, or failure to follow all operating instructions. For full details of your Taylor Warranty, please see the Limited Warranty section in this manual.
Note: Constant research results in steady improvements; therefore, information in this manual is subject to change without notice.
If the crossed out wheeled bin symbol is affixed to this product, it signifies that this product is compliant with the EU Directive as well as other similar legislation in effect after August 13, 2005. Therefore, it must be collected separately after its use is completed, and cannot be disposed as unsorted municipal waste.
The user is responsible for returning the product to the appropriate collection facility, as specified by your local code.
For additional information regarding applicable local laws, please contact the municipal facility and/or local distributor.
Compressor Warranty Disclaimer
The refrigeration compressor(s) on this unit are warranted for the term stated in the Limited Warranty section in this manual. However, due to the Montreal Protocol and the U.S. Clean Air Act Amendments of 1990, many new refrigerants are being tested and developed, thus seeking their way into the service industry. Some of these new refrigerants are being advertised as drop- in replacements for numerous applications. It should be noted that in the event of ordinary service to this unit’s refrigeration system,
only the refrigerant specified on the affixed data label should be used. The unauthorized use of
alternate refrigerants will void your Taylor compressor warranty. It is the unit owner’s responsibility to make this fact known to any technician he employs.
It should also be noted that Taylor does not warrant the refrigerant used in its equipment. For example, if the refrigerant is lost during the course of ordinary service to this machine, Taylor has no obligation to either supply or provide its replacement either at billable or unbillable terms. Taylor does have the obligation to recommend a suitable replacement if the original refrigerant is banned, obsoleted, or no longer available during the five year warranty of the compressor.
The Taylor Company will continue to monitor the industry and test new alternates as they are being developed. Should a new alternate prove, through our testing, that it would be accepted as a drop- in replacement, then the above disclaimer would become null and void. T o find out the current status of an alternate refrigerant as it relates to your compressor warranty, call the local Taylor Distributor or the Taylor Factory. Be prepared to provide the Model/Serial Number of the unit in question.
The freezer you have purchased uses refrigerants 404a and 134a. These “ozone friendly” refrigerants comply with the U.S. Clean Air Act of 1990.
131206
Models 702 & 772 To the Operator
13
Section 5 Safety
We, at Taylor Company, are concerned about the safety of the operator at all times when they are coming in contact with the unit and its parts. Taylor makes every effort to design and manufacture built- in safety features to protect both operators and service technicians.
Installing and servicing refrigeration equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service refrigeration equipment. When working on refrigeration equipment, observe precautions noted in the literature, tags and labels attached to the unit, and other safety precautions that may apply. Follow all safety code requirements. Wear safety glasses and work gloves.
IMPORTANT - Failure to adhere to the following safety precautions may result in severe personal injury or death. Failure to comply with these warnings may also damage the unit and/or its components. Such damage may result in component replacement and service repair expenses.
DO NOT operate the unit without reading
this entire Operator Manual first. Failure to follow all of these operating instructions may result in damage to the unit, poor performance, health hazards, personal injury, or death.
This unit is to be used only by trained personnel. It is not intended for use by children or people with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge. Where limited equipment operation is allowed for public use, such as a self- serve application, supervision or instruction concerning the use of the appliance by a person responsible for their safety is required. Children should be supervised to ensure that they do not play with the appliance.
S All repairs should be performed by an
authorized Taylor service technician.
S The main power supplies to the unit must be
disconnected prior to performing installation, repairs, or maintenance.
S DO NOT operate the unit unless it is
properly grounded.
S DO NOT operate the unit with larger fuses
than specified on the unit’s data label.
S Units that are permanently connected to
fixed wiring and for which leakage currents may exceed 10 mA, particularly when disconnected or not used for long periods, or during initial installation, shall have protective devices such as a GFI, to protect against the leakage of current, installed by the authorized personnel to the local codes.
S Stationary units which are not equipped with
a power cord and a plug or another device to disconnect the appliance from the power source must have an all-pole disconnecting device with a contact gap of at least 3 mm installed in the external installation.
S Supply cords used with this unit shall be
oil-resistant, sheathed flexible cable not lighter than ordinary polychloroprene or other equivalent synthetic elastomer-sheathed cord (Code designation 60245 IEC 57) installed with the proper cord anchorage to relieve conductors from strain, including twisting, at the terminals and protect the insulation of the conductors from abrasion.
If the supply cord is damaged, it must be replaced by an authorized Taylor service technician in order to avoid a hazard.
Failure to follow these instructions may result in electrocution. Contact your local authorized Taylor Distributor for service.
DO NOT use a water jet to clean or rinse the unit. Failure to follow these instructions may result in serious electrical shock.
Safety
14
Models 702 & 772
S DO NOT allow untrained personnel to
operate this unit.
S DO NOT operate the unit unless all service
panels and access doors are restrained with screws.
S DO NOT remove any internal operating
parts (including, but not limited to, freezer door, beater, or scraper blades), unless all control switches are in the OFF position.
Failure to follow these instructions may result in severe personal injury, especially to fingers or hands, from hazardous moving parts.
This unit has many sharp edges that can
cause severe injuries.
S DO NOT put objects or fingers in the door
spout. This may contaminate the product and cause severe personal injury from blade contact.
S USE EXTREME CAUTION when removing
the beater assembly. The scraper blades are very sharp.
This unit must be placed on a level surface. Extreme care should be taken when moving the unit for any reason. Two or more persons are required to safely move this unit. Failure to comply may result in personal injury or damage to the unit.
Access to the service area of the unit must be restricted to persons having knowledge and practical experience with the unit, in particular as far as safety and hygiene are concerned.
Cleaning and sanitizing schedules are governed by your state or local regulatory agencies and must be followed accordingly. Please refer to the cleaning section of this Operator Manual for the proper procedure to clean this unit.
This unit is designed to maintain product
temperature under 41°F(5°C). Any product being added to this unit must be below 41°F(5°C). Failure to
follow this instruction may result in health hazards and poor freezer performance.
DO NOT run the unit without product. Failure to follow this instruction can result in damage to the unit.
DO NOT obstruct air intake and discharge openings: Counter Model: 3” (76 mm) minimum air space on
both sides, 6” (152 mm) on the back, and 4- 1/4” (108 mm) on the bottom.
Console Model: 3” (76 mm) minimum air space on sides and rear, and 7- 1/2” (191 mm) minimum on bottom. Failure to follow this instruction may cause poor freezer performance and damage to the machine.
NOISE LEVEL: Airborne noise emission does not exceed 78 dB(A) when measured at a distance of 1.0 meter from the surface of the machine and at a height of 1.6 meters from the floor.
131206
Models 702 & 772 Safety
15
Section 6 Operator Parts Identification
Model 702
Item Description Part No.
*Cover A.- Hopper
(115V- 60- 1 only)
1
Cover A.- Hopper- Std. (460- 60 - 3) X38458
1a Knob - Hopper Cover 025429
2 Tube- Feed- SS- 5/32 Hole 028967- 2
3 Panel- Rear 702 Navy 050929
4 Panel- Side 702 Right 050928
5 Pan- Drip 13- 1/4 Long 039027
X39291
Operator Parts Identification
Item Description Part No.
6 Panel- Side 5472 HT Upper 042317
7 Shield- Splash 15” L x 5- 13/32 022763
8 Tray-Drip14-7/8Lx5-1/8SG 013690
9 Panel A. - Front X50930
10 Stud- Nose Cone 022822
11 Panel A.- Side Left X50940
12 Gasket- Hopper (460- 60- 3) 038375
*Insulated hopper cover that requires no gasket.
16
Models 702 & 772
Model 702 Door Assembly
Item Description Part No.
1 Seal- Drive Shaft 032560
2 Shaft- Beater 033498
3 Beater A.- 4 Qt.- 1 Pin Support X49490
4 Bearing- Front 013116
5 Gasket- Door 5.177 ID x 5.9380 016672
6 Decal- Lift Plate Front 015200
7 Valv e A.- D raw X13624- SP
Models 702 & 772 Operator Parts Identification
Item Description Part No.
8 O- Ring - 1- 1/16 OD x .139 W 020571
9 Cap- Design- 1.188” ID 6 Point 013139- 6
10 Nut- Stud 021508
11 Door A.- 1 Spout- 4 Qt. X30269- SER
12 Blade- Scraper- Plastic 046237
13 Clip- Scraper Blade 8.75 Inch 046238
17
Loading...
+ 48 hidden pages