SPS Speaker/Strobe6.0˝5.0˝ 4.7˝ (including lens and speaker) SPSC Speaker/Strobe6.8˝4.7˝ (including lens and speaker)
SPSV Speaker/Strobe6.0˝5.0˝ 4.8˝ (including lens and speaker) SPSCV Speaker/Strobe6.8˝4.8˝ (including lens and speaker)
Weatherproof back box **6.5˝5.5˝2.9˝*Weatherproof back box **7.2˝2.9˝*
Surface Mount Skirt6.5˝5.0˝2.7˝*Surface Mount Skirt7.2˝2.7˝*
*Depth above finished surface of wall or ceiling. **Weatherproff back box dimensions do not include the two mounting tabs.
Mounting Box Options
2-Wire Indoor ProductsK Series Products
Plastic
1
4 × 4 × 2
The indoor SP and SPV Series are suitable for dry and damp environments. The “K” Series models are suitable for use in both indoor and outdoor applications.
NOTICE: This manual shall be left with the owner/user of this equipment.
The “K” models are suitable for outdoor use in wet environments with outdoor back box supplied with the product.
GENERAL DESCRIPTION
The SpectrAlert Advance series of notification appliances offers a wide range
of speaker/strobe products for wall and ceiling applications, indoors and outdoors. The strobe portion is designed to be used in 12 or 24 volt, DC or FWR
(full wave rectified) systems. The speaker portion can be operated with distribution amplifiers having an output voltage of either 25 or 70.7 volts.
With its low total harmonic distortion, the SpectrAlert Advance SP series offers high fidelity sound output. The SpectrAlert Advance SPV series offers
greater sound output at every tap setting for applications with high ambient
noise levels. The speakers operate at any one of four input power levels. These
products are electrically backward compatible with the previous generation of
SpectrAlert notification appliances. All SpectrAlert Advance products are suitable for use in synchronized systems. The System Sensor MDL module may
be used to provide synchronization for the strobes. Wall and ceiling products
may be used interchangeably (wall products may be used on the ceiling and
ceiling products may be used on the wall.) K Series products are designed to
be used over a wider range of temperatures and are suitable for use in wet
locations.
SS-140-001 1 I56-3109-001R
/8 or deeper
PWBB - red wall plastic weatherproof back box
PWBBW - white wall plastic weatherproof back box
PWBBCW - white ceiling plastic weatherproof back box
FIRE ALARM SYSTEM CONSIDERATIONS
All wiring must be installed in compliance with the National Electrical Code
(NEC) and applicable local codes. System Sensor recommends installing fire
alarm speakers in compliance with NFPA 72, ANSI/UL1480 and NEC 760.
LOOP DESIGN AND WIRING
The system designer must make sure that the total current drawn by the devices on the loop does not exceed the current capability of the panel supply,
and that the last device on the circuit is operated within its rated voltage.
The current draw information for making these calculations can be found in
the tables within this manual. For convenience and accuracy, use the voltage
drop calculator on the System Sensor website (www.systemsensor.com) or
CD-ROM.
When calculating the voltage available to the last device, it is necessary to
consider the voltage drop due to the resistance of the wire. The thicker the
wire, the smaller the voltage drop. Wire resistance tables can be obtained
from electrical handbooks. Note that if Class A wiring is installed, the wire
length may be up to twice as long as it would be for circuits that are not fault
tolerant.
NOTE: For 24 volt applications, the total number of strobes on a single NAC
must not exceed 40, with a maximum loop resistance of 120 ohms. For 12 volt
applications, the total number of strobes must not exceed 12, with a maximum loop resistance of 30 ohms.
NOTE: Supply power for strobe must be continuous for proper operation.
CAUTION
FIGURE 1. WIRING DIAGRAM:
INPUT FROM
AMPLIFIER
INPUT FROM
POWER
SUPPLY
OUTPUT TO
NEXT SPEAKER
OR EOL
OUTPUT TO
NEXT STROBE
OR EOL
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
SHORTING SPRINGS
A0388-00
ELECTRICAL WIRING
1. Connect the speaker as shown in Figure 1.
NOTE: Do not loop electrical wiring under terminal screws. Wires con-
necting the device to the control panel must be broken at the device
terminal connection in order to maintain electrical supervision.
2. There are two rotary switches on the back of the product The first switch
is used to select either 25 or 70.7 volts input for the speaker portion. The
second switch is used to select the input power of 1/4, 1/2, 1 or 2 watts.
See diagram.
SHORTING SPRING
NOTE: Shorting springs are provided between terminals 2 and 3 and between
terminals 5 and 6 of the mounting plate to enable wiring checks after the
system has been wired, but prior to installation of the final product. These
springs will automatically disengage when the product is installed, to enable
supervision of the final system.
FIGURE 2. SHORTING SPRING
TABLE 1. SOUND LEVELS FOR EACH TRANSFORMER POWER TAP:
UL Reverberant (dBA @ 10 ft.)SPS, SPSCSPSV, SPSCV
2W8589
1W8286
1
/2W7983
1
/4W7680
Signal levels exceeding 130% rated signal voltage can damage the speaker.
Consequently, an incorrect tap connection may cause speaker damage. This
means that if a 25V tap is selected when a 70.7V amplifier is being used,
speaker damage may result. Therefore, be sure to select the proper taps for the
amplifier voltage/input power level combination being used.
TABLE 2. STROBE CURRENT DRAW MEASUREMENTS:
Strobe Current Draw
Candela
8-17.5 Volts16-33 Volts
DCFWRDCFWR
Standard Candela Range151231286671
15/751421487781
30NA NA9496
75NANA158153
95NANA181176
110NANA202195
115NANA210205
High Candela Range135NANA228207
150NANA246220
177NANA281251
185NANA286258
FIGURE 3. SPEAKER WATTAGE AND VOLTAGE SETTINGS:
SS-140-001 2 I56-3109-001R
A0391-00
C0419-00
CANDELA SELECTION
Adjust the slide switch on the rear of the product to position the desired candela setting in the small window on the front of the unit. All products meet
the light output profiles specified in the appropriate UL Standards. Use Table 2
to determine the current draw for each candela setting. For K series products
used outdoors at low temperatures, listed candela ratings must be reduced in
accordance with Table 3.
NOTE: SpectrAlert products set at 15 and 15/75 candela automatically work
on either 12V or 24V power supplies. The products are not listed for 12V operating voltages when set to any other candela settings.
TABLE 3. CANDELA DERATING:
Listed Candela Rating
Candela rating at -40°F (K Series Outdoor Applications Only)
15
15/75
30
Do not use
below 32°F
7544
9570
110110
115115
135135
150150
177177
185185
MOUNTING
Mounting Indoor Wall or Ceiling Products
1. Attach mounting plate to junction box as shown in Figures 4 and 5. The
mounting plate is compatible 4˝ x 4˝ x 21/8˝ junction boxes. If using a back
box skirt or trim ring, attach the mounting plate to the skirt or trim ring and
then attach the entire assembly to the junction box (see Figures 4, 6 and 8).
CAUTION
2. Connect field wiring to terminals, as shown in Figure 1.
3. If the product is not to be installed at this point, use the paint cover to
prevent contamination of the mounting plate.
4. To attach product to mounting plate, remove the paint cover, then hook
tabs on the product housing into the grooves on mounting plate.
5. Then, swing product into position to engage the pins on the product with
the terminals on the mounting plate. Make sure that the tabs on the back
of the product housing fully engage with the mounting plate.
6. Secure product by tightening the single mounting screw in the front of the product housing. For tamper resistance, the standard captivated
mounting screw may be replaced with the enclosed Torx screw.
FIGURE 4: WALL MOUNT PRODUCT WITH TRIM RING:
A0389-00
FIGURE 5: CEILING MOUNT PRODUCT:
A0390-00
FIGURE 6: WALL MOUNT PRODUCT WITH BACK BOX SKIRT:
FIGURE 8: CEILING MOUNT PRODUCT WITH BACK BOX SKIRT:
A0393-00
K Series Mounting
1. K Series products may be used indoors or outdoors. They must be installed using the proper SpectrAlert Advance weatherproof back box. Do
not attempt to use boxes other than those specified for use with the
product.
2. The plastic weatherproof back box is equipped with removable side
flanges for mounting. The back box may be secured directly to the wall
or ceiling using the flanges or by using the knockout plugs. Knockout
plugs are provided to mount directly to the wall or ceiling or to a 1900
weatherproof electrical box
3. Threaded holes are provided in the sides of the box for 3/4 inch conduit
adapters. Knockout plugs in the back of the box can be used for 1/2 or
3
/4 inch rear entry. Unused holes must be sealed. Plugs and O-Rings are
provided with the box for this purpose.
4. It is the responsibility of the installer to make sure that all openings and
connections are sealed properly. Outdoor installations that are protected
from direct exposure to rain are still subject to condensation or leakage
through hidden areas, such as a soffit.
5. Water may pool on the back box due to condensation or direct exposure
to rain or snow. Use watertight fittings for all wiring connections, including the knockout plugs on the back of the box. When using the plastic
plugs to fill unused threaded holes, make sure the O-rings supplied are
properly positioned on the plug.
6. Attach the mounting plate to the weatherproof back box using the four
non-painted screws.
7. Follow steps 2-5 of the indoor mounting instructions to wire and attach
the product. The product must be mounted to the weather proof back
box using the painted screws (wall product has 4 screws, ceiling product
has 3 screws)
FIGURE 7. OUTDOOR CEILING MOUNT PRODUCT WITH PLASTIC
WEATHERPROOF BACK BOX:
SS-140-001 3 I56-3109-001R
A0392-00
A0420-00
The ‘hold-in-place’ snaps are not intended to secure the product to the back
box. The product must be secured to the back box using the screws provided
FIGURE 9. WALL MOUNT WEATHERPROOF PRODUCT WITH
PLASTIC BACK BOX:
A0395-00
WARNING
Please refer to insert for the Limitations of Fire Alarm Systems
If either of the voltage select or power select shunts is not plugged into one of the appropriate option positions, the speaker will not sound and there will be no trouble indication
at the panel. Always make sure that the individual speakers are tested after installation
per NFPA regulations.
The speaker may not be heard. The loudness of the speaker meets (or exceeds) the
current Underwriters Laboratories’ standards. However, the speaker may not attract the
attention of a sound sleeper or one who has recently used drugs or has been drinking
alcoholic beverages. The speaker may not be heard if it is placed on a different floor from
the person in hazard or if placed too far away to be heard over the ambient noise. Traffic,
air conditioners, machinery, or music appliances may prevent even alert persons from
hearing the alarm. The speaker may not be heard by persons who are hearing impaired.
System Sensor warrants its enclosed product to be free from defects in materials and
workmanship under normal use and service for a period of three years from date of
manufacture. System Sensor makes no other express warranty for this air duct smoke
detector. No agent, representative, dealer, or employee of the Company has the authority
to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the replacement of any part of the product which
is found to be defective in materials or workmanship under normal use and service
during the three year period commencing with the date of manufacture. After phoning
System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization
number, send defective units postage prepaid to: System Sensor, Returns Department, RA
SpectrAlert Speaker/Strobes have been tested and found to comply with the limits for a
Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed
to provide reasonable protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates, uses, and can radiate
The signal strobe may not be seen. The electronic visual warning signal uses an extremely reliable xenon flash tube. It flashes at least once every second. The strobe must
not be installed in direct sunlight or areas of high light intensity (over 60 foot candles)
where the visual flash might be disregarded or not seen. The strobe may not be seen by
the visually impaired.
The signal strobe may cause seizures. Individuals who have positive photoic response to
visual stimuli with seizures, such as persons with epilepsy, should avoid prolonged exposure to environments in which strobe signals, including this strobe, are activated.
The signal strobe cannot operate from coded power supplies. Coded power supplies produce interrupted power. The strobe must have an uninterrupted source of power in order
to operate correctly. System Sensor recommends that the horn and signal strobe always be
used in combination so that the risks from any of the above limitations are minimized.
#__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing
the malfunction and suspected cause of failure. The Company shall not be obligated to
replace units which are found to be defective because of damage, unreasonable use,
modifications, or alterations occurring after the date of manufacture. In no case shall the
Company be liable for any consequential or incidental damages for breach of this or any
other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by
the Company’s negligence or fault. Some states do not allow the exclusion or limitation of
incidental or consequential damages, so the above limitation or exclusion may not apply
to you. This Warranty gives you specific legal rights, and you may also have other rights
which vary from state to state.
radio frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. operation of this
equipment in a residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.