INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
Selectable Output Strobes, Horns, and Horn/Strobes
For use with the following models: P2R, P2RH, P2RK, P2RHK, P2W, P2WK, P2WH, P2WHK, P4R, P4RH, P4RK, P4W, P4WK, P4WHK, SR, SRH, SRK, SRHK, SW, SWK, SWH, SWHK,
SW-CLR-ALERT, PC2R, PC2RH,PC2RK, PC2RHK, PC2W, PC2WK, PC2WH, PC2WHK, PC4R, PC4RH, PC4W, PC4WK, PC4WHK, SCR, SCRH, SCRK, SCRHK, SCW, SCWK, SCWH,
SCWHK, SCW-CLR-ALERT, HR, HRK, HW, SR-P, SW-P, SRH-P, SWH-P,P2R-P, P2W-P, P2WH-P, P4W-P, SCW-P, PC2R-P, PC2W-P, PC2WH-P, SRK-P, SRHK-P, P2RK-P, P2RHK-P, SWK-P,
SWHK-P, P2WK-P, P2WHK-P, SR-SP, P2R-SP, PC2W-SP, SRK-R, SWK-R, SRHK-R, SWHK-R, P2RK-R, P2WK-R, P2RHK-R, P2WHK-R
NOTE: All -R models are specifically designed for use with the WTP Series of Weatherproof plates
NOTE: When replacing outdoor units; device and back box must be replaced
PRODUCT SPECIFICATIONS
Operating Temperature: Standard Products 32°F to 120°F (0°C to 49°C)
K Series –40°F to 151°F
Humidity Range: Standard Products 10 to 93% Non-condensing
K Series Meets NEMA 4X requirements
Strobe Flash Rate: 1 flash per second
Nominal Voltage: Regulated 12VDC/FWR or regulated 24DC/FWR
Operating Voltage Range (includes fire alarm panels with built in sync): 8 to 17.5V (12V nominal) or 16 to 33V (24V nominal)
Operating Voltage with MDL Sync Module: 9 to 17.5V (12V nominal) or 17 to 33V (24V nominal)
Input terminal wire gauge: 12 to 18 AWG
NOTE : Strobes will operate at 12 V nominal for 15 & 15/75 candela settings only. Switching between ranges is automatic.
DIMENSIONS FOR PRODUCTS AND ACCESSORIES
WALL PRODUCTS LENGTH WIDTH DEPTH CEILING PRODUCTS DIAMETER DEPTH
Strobes and Horn/Strobes
(including lens)
Horns
SA-WBB Weatherproof Back Box
SA-WBBW Weatherproof Back Box
BBS-2
BBSW-2
Back Box Skirt
5.6˝ 4.7˝ 2.5˝
142 mm 119 mm 64 mm 173 mm 64 mm
5.6˝ 4.7˝ 1.3˝
142 mm 119 mm 33 mm 180 mm 51 mm
5.7˝ 5.1˝ 2.0˝
145 mm 130 mm 51 mm 180 mm 57 mm
5.0˝ 5.9˝ 2.2˝
130 mm 152 mm 57 mm
Strobes and Horn/Strobes
(including lens)
SA-WBBC Weatherproof Back Box
SA-WBBCW Weatherproof Back Box
BBSC-2
BBSCW-2
Back Box Skirt
NOTE: SA-WBB, SA-WBBW, SA-WBBC and SA-WBBCW dimensions
do not include the two mounting tabs
800/736-7672, FAX: 630/377-6495
www.systemsensor.com
6.8˝ 2.5˝
7.1˝ 2.0˝
7.1˝ 2.2˝
I56-2769-015R
MOUNTING BOX OPTIONS
2-Wire Indoor Products 4-Wire Indoor Products K Series Products
4 × 4 × 11/2, Single Gang, Double Gang, 4˝ Octagon 4 × 4 × 11/2, Double Gang, 4˝ Octagon SA-WBB/W (wall), SA-WBBC/CW (ceiling)
NOTICE: This manual shall be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The SpectrAlert Advance series of notification appliances offers a wide range
of horns, strobes, and horn/strobes, for wall and ceiling applications, indoors
and outdoors. They are designed to be used in 12 or 24 volt, DC or FWR
(full wave rectified) systems. These products are electrically backward compatible with the previous generation of SpectrAlert notification appliances. Horn/
strobe products are available in two versions. The 2-wire products fit systems
where a single NAC controls both horn and strobe. The 4-wire products are intended for systems which have separate wiring circuits for the horn and strobe.
All SpectrAlert Advance products are suitable for use in synchronized systems.
The System Sensor MDL module may be used to provide synchronization.
K Series products are designed to be used over a wider range of temperatures
and are suitable for use in wet locations.
Wall and ceiling products may be used interchangeably (wall products may
be used on the ceiling and ceiling products may be used on the wall.)
FIRE ALARM SYSTEM CONSIDERATIONS
The National Fire Alarm Code, NFPA 72, requires that all horns, used for
building evacuation produce temporal coded signals. Signals other than those
used for evacuation purposes do not have to produce the temporal coded signal. System Sensor recommends spacing notification appliances in compliance with NFPA 72.
LOOP DESIGN AND WIRING
The system designer must make sure that the total current drawn by the devices on the loop does not exceed the current capability of the panel supply,
and that the last device on the circuit is operated within its rated voltage.
The current draw information for making these calculations can be found in
the tables within this manual. For convenience and accuracy, use the voltage
drop calculator on the System Sensor website (www.systemsensor.com) or
CD-ROM.
When calculating the voltage available to the last device, it is necessary to
consider the voltage drop due to the resistance of the wire. The thicker the
wire, the smaller the voltage drop. Wire resistance tables can be obtained
from electrical handbooks. Note that if Class A wiring is installed, the wire
length may be up to twice as long as it would be for circuits that are not
fault tolerant.
NOTE: The total number of strobes on a single NAC must not exceed 40 for
24 volt applications or 12 for 12 volt applications. Loop resistance on a single
NAC should not exceed 120 ohms for 24 volt and 30 ohms for 12 volt systems.
For 4-Wire installations, terminals 1, 2, and 3 connect to the strobe; terminals
4 and 5 connect to the horn. The horn and strobe circuits must be wired independently, and each circuit must be terminated with the appropriate EOL
device. Removal of a notification device will result in an open circuit indication on the strobe loop.
D690-03-00 1 I56-2769-015R

FIGURE 1. WIRING 2-WIRE PRODUCTS:
INPUT
FROM
FACP
OR
PRIOR
DEVICE
+
–
FIGURE 2. WIRING 4-WIRE PRODUCTS:
OUTPUT
TO
NEXT
DEVICE
OR EOL
+
–
A0367-01
TABLE 1. STROBE CURRENT DRAW ( ) FOR S, SC, P4 & PC4 SERIES:
Standard Candela Range
mA
Candela
8–17.5 Volts 16–33 Volts
DC FWR DC FWR
15 123 128 66 71
15/75 142 148 77 81
30 NA NA 94 96
75 NA NA 158 153
95 NA NA 181 176
110 NA NA 202 195
115 NA NA 210 205
High Candela Range 135 NA NA 228 207
150 NA NA 246 220
177 NA NA 281 251
185 NA NA 286 258
FROM
FACP OR
PRIOR
STROBE
+
–
+
–
INPUT FROM
OUTPUT TO NEXT
TO NEXT
STROBE
OR EOL
+
–
+
–
A0366-00
FIGURE 3. SHORTING SPRING:
SHORTING SPRING
A0368-00
NOTE: A shorting spring is provided between terminals 2 and 3 of the mounting plate to enable wiring checks after the system has been wired, but prior
to installation of the final product. This spring will automatically disengage
when the product is installed, to enable supervision of the final system.
CANDELA SELECTION
Adjust the slide switch on the rear of the product to position the desired candela setting in the small window on the front of the unit. All products meet
the light output profiles specified in the appropriate UL Standards. For K series
products used outdoors at low temperatures, listed candela ratings must be reduced in accordance with Table 2. Use Table 1 to determine the current draw
for each candela setting. WIRING DIAGRAMS
NOTE: SpectrAlert products set at 15 and 15/75 candela automatically work
on either 12V or 24V power supplies. The products are not listed for 12V operating voltages when set to any other candela settings. For 4-Wire products,
total current draw may be determined by adding current draw for the specific
candela selection in Table 1 with the current draw for the specific horn selection in Table 3.
TABLE 2. CANDELA DERATING:
Listed Candela
Candela rating at –40°F
(K Series Outdoor Applications Only)
15
Do not use below 32°F15/75
30
75 44
95 70
110 110
115 115
135 135
150 150
177 177
185 185
HORN SELECTION
Turn the rotary switch on the back of the product to the desired setting. For
horn and 4-wire horn/strobe products, the current draw for each setting is
listed in Table 3. For 2-wire horn/strobe products (P2 series), current draws
are listed in Tables 4 and 5. The sound output measurement for each horn
setting is shown in Table 6.
TABLE 3. HORN CURRENT DRAW ( ) FOR H, P4 & PC4 SERIES:
Pos Sound Pattern dA Out
mA
8–17.5 Volts 16–33 Volts
DC FWR DC FWR
1 Temporal High 57 55 69 75
2 Temporal Medium 44 49 58 69
3 Temporal Low 38 44 44 48
4 Non-temporal High 57 56 69 75
5 Non-temporal Medium 42 50 60 69
6 Non-temporal Low 41 44 50 50
7 Coded High 57 55 69 75
8 Coded Medium 44 51 56 69
9 Coded Low 40 46 52 50
NOTE: In positions 7, 8, and 9, temporal coding must be provided by the NAC.
If the NAC voltage is held constant, the horn output will remain constantly on.
Positions 7, 8, and 9 are not available on 2-wire horn/strobe products.
D690-03-00 2 I56-2769-015R