INSTALLATION AND MAINTENANCE INSTRUCTIONS
SpectrAlert Selectable Output Outdoor
Wall Speaker/Strobes for
Fire Protective Signaling Systems
Model SP2R1224MCK
U.S. Patent Nos. 5,850,178; 5,598,139; 6,049,446; 6,522,261; 6,661,337; 6,793,375;
6,822,400; 6,833,783; 5,931,569; 6,856,241
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Specifications:
Mechanical:
Input Terminals: 12 to 18 AWG
Speaker Size: 4 inches (101 mm)
Grille Size: 413/16˝ (122 mm)
Outdoor Back Box: 9.22˝ × 5.87˝ × 2.38˝
Electrical:
Operating Temp. Range: –40°F to 150.8°F (–40°C to 66°C)
Max. Supervisory Voltage: 50 VDC
For Speaker:
Voltage Input: 25 volts or 70.7 volts
(nominal)
Frequency Range: 400 – 4000 Hz
Input Power Settings:
1
/4, 1/2, 1 and 2 Watts
Sound Output:
Sound output levels are established at Underwriters
Laboratories in their anechoic room. Always use the
sound output specified as UL Anechoic Room when
comparing products.
For Strobe:
Voltages: Regulated 12 DC/FWR and
Regulated 24 DC/FWR
Operational Volt. Ranges: 8–17.5 Volts and 16–33 Volts
Synchronous Applications
with MDL Module: 9–17.5 Volts and 17–33 Volts
NOTE: The outdoor speaker/strobe is suitable for use in
dry and wet environments.
Flash Rate: 1 flash per second
Selectable Light Outputs: All candelas are selectable via
a manual slide switch.
12/24 Volt Applications: 15 or 15/75 candela
24 Volt Application: 30, 75, 110 candela
15/75 is listed at 15 candela per UL 1971 but will provide
75 candela on axis (straight ahead). 15, 30, 75, or 110 are
rated for that candela.
Listings: UL 1971/1638 (Strobe); UL 1480 (Speaker); NEMA 3R
Note for Strobes: Do not exceed; 1) 8-17.5 or 16-33 voltage
range limit; 2) maximum number of 70 strobe lights when
connecting the MDL Sync module with a maximum line
impedance of 4 ohms per loop and; 3) maximum line impedance as required by the fire alarm control manufacturer.
Model
SP2R1224MCK
The benefit to the customer is a high quality strobe device.
incorporates a new patented voltage booster design that has a more consistent flash bulb voltage over the range of candela selections.
NOTICE: This manual shall be left with the owner/user of
this equipment.
General Description
The SpectrAlert SP2 series speaker/strobes are designed to
meet the requirements of most agencies governing these
devices, including: NFPA, ADA, The National Fire Alarm
Code, UL. Also, check with your local Authority Having
Jurisdiction for other codes or standards that may apply.
The SpectrAlert SP2 series speakers can be operated with
distribution amplifiers having an output voltage of either
25 volts or 70.7 volts.
The speakers operate at any one of four input power levels.
The output sound level is selected at the time of installation, but can be changed, if necessary.
The speaker is also equipped with a capacitive input to
allow for DC supervision.
The SpectrAlert SP2 series strobe can be installed in systems
using 12 or 24-volt panels having DC or full-wave rectified
(FWR) power supplies. The strobes can also be installed
in applications requiring synchronization (module MDL or
compatible equivalent required) or applications that do not
require synchronization (no module required).
Power Supply Considerations For Strobes
Panels typically supply DC filtered voltage or FWR (fullwave rectified) voltage. The system design engineer must
calculate the number of units used in a zone based on the
type of panel supply. Be certain the sum of all the device
currents do not exceed the current capability of the panel.
Calculations are based on using the device current found
in Table 2 and must be the current specified for the type of
panel power supply used.
D900-40-00 1 I56-2609-002R
25.0V
70.7V
2W
1W
1/2W
1/4W
25.0V
70.7V
2W
1W
1/2W
1/4W
CORRECT
SW1
SW1
INCORRECT
Wire Sizes
TO NEXT
STROBE OR EOL
INPUT FROM
POWER SUPPLY
INPUT FROM
AMPLIFIER
TO NEXT
SPEAKER OR EOL
STROBESPEAKER
The designer must be sure that the last device on the circuit
has sufficient voltage to operate the device within its rated
voltage. When calculating the voltage available to the last
device, it is necessary to consider the voltage drop due to
the resistance of the wire. The thicker the wire, the less the
voltage drop. Generally, for purposes of determining the
wire size necessary for the system, it is best to consider all
of the devices as “lumped” on the end of the supply circuit
(simulates “worst case”).
Typical wire size resistance:
18 AWG solid: Approximately 8 ohms/1,000 ft.
16 AWG solid: Approximately 5 ohms/1,000 ft.
14 AWG solid: Approximately 3 ohms/1,000 ft.
12 AWG solid: Approximately 2 ohms/1,000 ft.
Example: Assume you have 10 devices on a zone and each
requires 50 mA average and 2000 Ft. of 14 AWG wiring
(total length=outgoing+return). The voltage at the end of
the loop is 0.050 amps per device × 10 devices × 3 ohms/
1,000 ft. × 2000 ft =3 volts drop.
Figure 1. Electrical connections:
A0101-00
NOTE: Supply power for strobe must be continuous for
proper operation.
2. See Figure 2 as an example of how to select a 1⁄4 Watt
input when a 25 volt amplifier is being used. Notice that
the header, SW1, has two shunts. One shunt is used to
select either 25 or 70.7 volts input. The other shunt is
used to select input power of 1⁄4, 1⁄2, 1 or 2 Watts. Table 1
lists the UL reverberant and anechoic output sound levels
for each power tap on the SP2 series speaker/strobes.
Figure 2. Speaker Voltage and Power Selection:
The same number of devices using 12 AWG wire will produce only 2 volts drop. The same devices using 18 AWG
wire will produce 8 volts drop. Consult your panel manufacturer’s specifications, as well as SpectrAlert’s operating
voltage range to determine acceptable voltage drop.
NOTE: If class “A” wiring is installed, the wire length may
be up to 4 times the single wire length in this calculation.
Installation
All wiring must be installed in compliance with the National
Electrical Code (NEC) and applicable local codes as well as
special requirements of the authority having jurisdiction,
using the proper wire size. This also includes all applicable
NFPA Standards, ANSI/UL 1480, UL 1971 and NEC 760.
Electrical
1. Connect the speaker/strobe as shown in Figure 1. Keep
Table 1. Sound levels for each transformer power tap:
INPUT
VOLTS
25.0 89 87 85 81
2 W 1 W1/2 W1/4 W
Reverberant
(dBA @ 10 ft.)
70.7 90 87 84 81
in mind that even though the speaker and strobe are a
single mechanical unit, they are electrically independent
and require separate power sources.
Signal levels exceeding 130% rated signal voltage can dam-
NOTE: Do NOT loop electrical wiring under terminal
screws. Wires connecting the device to the control
D900-40-00 2 I56-2609-002R
panel must be broken at the device terminal connection in order to maintain electrical supervision.
age the speaker. Consequently, an incorrect tap connection
may cause speaker damage. This means that if a 25V tap
is selected when a 70.7V amplifier is being used, speaker
damage may result. Therefore, be sure to select the proper
taps for the amplifier voltage/input power level combination being used.
A0102-00
UL