System Sensor S1224MCP, S1224MCSP, P1224MC, S1224MCSPW, P1224MCW Installation And Maintenance Instructions Manual

...
INSTALLATION AND MAINTENANCE INSTRUCTIONS
1
/2 Sec.
On
1
/2 Sec.
Off
1
/2 Sec.
On
1
/2 Sec.
Off
1
/2 Sec.
On
11/2 Sec.
Off
Repeats
SpectrAlert Selectable Output Strobes, Horns, and Horn/Strobes
For use with the following models: Strobes - 12/24 volt: S1224MC, S1224MCW, S1224MCSP, S1224MCSPW, S1224MCP, S1224MCPW Combo - 12/24 volt: P1224MC, P1224MCW, P1224MCSP, P1224MCSPW, P1224MCP, P1224MCPW Horns - H12/24, H12/24W
Suffix “W” indicates white housing models. Suffix “SP” indicates “FUEGO” (Spanish word for “FIRE”) lettering on housing. Suffix “P” indicates plain housing (no lettering). The Products to which this manual applies may be covered by one or more of the following U.S. Patent numbers: 5,914,665; 5,850,178; 5,598,139; 6,049,446; 5,593,569, 6,133,843; 6,522,261
Specifications
Automatic selection for 12 or 24 volt rated operation (DC or Full-Wave Rectified) Electrical For Horns, Strobes, and Horn/Strobes Voltages: Regulated 12 DC/FWR and Regulated 24 DC/FWR Operational Voltage Ranges: 8-17.5 Volts and 16-33 Volts Synchronous Applications with MDL Module: 9-17.5 Volts and 17-33 Volts
NOTE: Horn units will operate on walk tests with on-time durations of .25 sec. or greater.
Flash Rate: 1 flash per second Operating Temperature: 32° F to 120° F (0° C to 49° C) Selectable Light Outputs: All candelas are selectable via a manual slide switch. 12/24 Volt Applications: 15 or 15/75 candela 24 Volt Application: 30, 75, 110 candela 15/75 is listed at 15 candela per UL 1971 but will provide 75 candela on axis (straight
ahead). 15, 30, 75, or 110 are rated for that candela.
Sound Output: Sound output levels are established at Underwriters Laboratories in their reverberant
room. Always use the sound output specified as UL Reverberant Room when compar­ing products.
Listings: UL S5512 (Strobe); UL S4011 (Combo) Note for Strobes: Do not exceed: 1) 8-17.5 or 16-33 voltage range limit; 2) maximum number of 70
strobe lights when connecting the MDL Sync module with a maximum line imped­ance of 4 ohms per loop and; 3) maximum line impedance as required by the fire alarm control manufacturer.
The models P1224MCPW benefit to the customer is a high quality strobe device.
S1224MC, S1224MCW, S1224MCSP, S1224MCSPW, S1224MCP, S1224MCPW, P1224MC, P1224MCW, P1224MCSP, P1224MCSPW, P1224MCP, and
incorporate a new patent-pending voltage booster design that has a more consistent flash bulb voltage over the range of candela selections. The
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
General Description
The SpectrAlert series notification appliances are designed to meet the requirements of most agencies governing these devices, including: NFPA, ADA, The National Fire Alarm Code, UL, ULC, FM, CSFM, MEA. Also, check with your local Authority Having Jurisdiction for other codes or stan­dards that may apply.
The SpectrAlert series can be installed in systems using 12­or 24-volt panels having DC or full-wave rectified (FWR) power supplies. The series can also be installed in systems requiring synchronization (module MDL or compatible equivalent required) or systems that do not require syn­chronization (no module required).
NOTICE: This manual shall be left with the owner/user of this equipment.
D900-28-00 1 I56-1796-008R
Fire Alarm System Considerations
Temporal and Non-Temporal Coded Signals:
The American National Standards Institute and the National Fire Alarm Code require that all horns used for building evacuation installed after July 1, 1996, must produce Temporal Coded Signals.
Signals other than those used for evacuation purposes do not have to produce the Temporal Coded Signal. Temporal coding is accomplished by interrupting a steady sound in the following manner:
Viewing Window
WARNING
Power Supply Considerations
Panels typically supply DC filtered voltage or FWR (full­wave rectified) voltage. The system design engineer must calculate the number of units used in a zone based on the type of panel supply. Be certain the sum of all the device
Typical wire size resistance: 18 AWG solid: Approximately 8 ohms/1,000 ft. 16 AWG solid: Approximately 5 ohms/1,000 ft. 14 AWG solid: Approximately 3 ohms/1,000 ft.
12 AWG solid: Approximately 2 ohms/1,000 ft. currents do not exceed the current capability of the panel. Calculations are based on using the device current found in the subsequent charts and must be the current specified for the type of panel power supply used.
Example: Assume you have 10 devices on a zone and each
requires 50 mA average and 2000 Ft. of 14 AWG wiring
(total length=outgoing +return). The voltage at the end
of the loop is 0.050 amps per device x 10 devices x 3 ohms/
Wire Sizes
1,000 ft. x 2000 ft =3 volts drop.
The designer must be sure that the last device on the circuit has sufficient voltage to operate the device within its rated voltage. When calculating the voltage available to the last
Note: If class “A” wiring is installed, the wire length may be
up to 4 times the single wire length in this calculation.
device, it is necessary to consider the voltage drop due to the resistance of the wire. The thicker the wire, the less the voltage drop. Generally, for purposes of determining the wire size necessary for the system, it is best to consider all of the devices as “lumped” on the end of the supply circuit (simulates “worst case”).
The same number of devices using 12 AWG wire will pro-
duce only 2 volts drop. The same devices using 18 AWG
wire will produce 8 volts drop. Consult your panel manu-
facturer’s specifications, as well as SpectrAlert’s operating
voltage range to determine acceptable voltage drop.
Figure 1A: Current Draw Measurements
NOTE: All ‘S’ and ‘P’ models were only tested at the 8-17.5 and 16-33 Volt-FWR/DC limits. This does not include the
80% low-end or 110% high-end voltage limits.
FWR Operating
Current–Strobe
Model No.
S1224MC Strobe
P1224MC Horn/Strobe
H12/24 Horn 45.7 57.5 44.4 57 75
Candela Setting
15 112 64 127 59 15/75 135 74 127 69 30 93 90 75 158 160 110 208 209 15 112 64 127 59 45.7 57.5 44.4 57 75 15/75 135 74 127 69 45.7 57.5 44.4 57 75 30 93 90 57.5 57 75 75 158 160 57.5 57 75 110 208 209 57.5 57 75
(mA RMS)
DC Operating
Current–Strobe
(mA RMS)
FWR Operating
Current–Horn
(mA RMS)
DC Operating Current–Horn
(mA RMS)
Horn
Audibility
(dBA)12V 24V 12V 24V 12V 24V 12V 24V
Figure 1B: Selectable Horn Tones
Temporal Low Volume Electromechanical
3000 Hz Interrupted
High Volume Electromechanical
3000 Hz Interrupted
Non­Temporal
D900-28-00 2 I56-1796-008R
Low Volume Electromechanical
3000 Hz Interrupted
High Volume Electromechanical
3000 Hz Interrupted
Figure 2: Candela Selections
For strobe candela selection, adjust slide switch located on the rear of the prod­uct while watching the viewing window on the side of the reflector.
Permissible Candela Settings:
A0133-00
Candela
Setting
15 OK OK
15/75 OK OK
30 OK
75 OK
110 OK
Operating Voltage
12V 24V
NOTE: SpectrAlert selectable output strobes, set at 15 and 15/75cd, auto­matically work on both 12V and 24V power supplies. NOTE: The strobe is not listed for 12V operating voltages when set to 30, 75 or 110 candelas. Use only those settings marked as OK in the chart above.
When using a 12V panel, this device will yield required light output only in the 15 or 15/75 candela setting.
HORN
(+)
(–)
(+)
(–)
E O L
(+)
(–)
(+)
(–)
HORN/STROBE
STROBE ONLY
TWO WIRE SYSTEM ANY MIX OF MODELS WIRED FOR TANDEM
OPERATION
HORN
SYNCHRONIZATION MODULE
MDL
(+)
(–)
(+)
(–)
E O L
(+)
(–)
(+)
(–)
HORN/STROBE
STROBE ONLY
TWO WIRE SYSTEM ANY MIX OF MODELS WIRED FOR TANDEM
OPERATION
(+)
(–)
(+)
(–)
(+)
(–)
FOUR WIRE SYSTEM
COMBO MODELS
WIRED FOR INDEPENDENT
OPERATION
(HORN CAN BE TURNED OFF
AT THE PANEL WHILE STROBES
CONTINUE TO OPERATE)
E O L
(+)
(–)
(+)
(–)
(+)
(–)
E O L
S T R O B E
C O M B O
H O R N
H O R N
S T R O B E
FROM: FACP, MODULE OR PREVIOUS DEVICE
TO NEXT
DEVICE OR
EOL
+
Strobe +
Strobe – Horn –
Horn +
TANDEM OPERATION
HORN/STROBE COMBO
FACTORY INSTALLED JUMPERS
FROM: FACP, MODULE (MDL) OR PREVIOUS DEVICE
Break wire as shown for supervision of connection. DO NOT allow stripped wire leads to extend beyond switch housing. DO NOT loop wires.
TO NEXT
DEVICE OR
EOL
INDEPENDENT OPERATION
HORN AND STROBE
TO NEXT
DEVICE OR
EOL
STROBE +
HORN +
STROBE +
STROBE –
STROBE
HORN –
HORN
HORN +
FACTORY INSTALLED
JUMPER WIRES REMOVED
NOTE: STROBES MUST BE POWERED CONTINUOUSLY FOR HORN OPERATION.
Figure 3: Horn Factory Default Setting
Low
OFF ON
Temporal
Electromech.
DIP Switch
Factory
Default
High
Non-Temporal
3000Hz
Base (rear)
WARNING
The factory default setting is High, Temporal 3, and
Electromechanical tone.
A0110-00
Horn selections using 3-position DIP switch on horn/
strobe (refer to Figure 3):
Note: When powered from a FWR supply, the horn will be
modulated (turned on and off) by 120Hz causing it to sound different than if powered by a DC supply.
High/Low Volume
ON=High Volume, OFF=Low Volume
Note: The low volume setting of some tones must NOT be
used for public mode applications when the device
Check terminal polarity before wiring. For proper operation, make sure the correct wire polarity is applied to the unit.
is powered from a 12-volt panel. Refer to the Sound Output Guide on the previous page.
Temp/Non-Temp
ON=NON-Temporal, OFF=Temporal
3KHz/Electromechanical
ON=3KHz, OFF=Electromechanical
Tone pattern override options using compatible panels:
The Selectable Output Horn/Strobe may be commanded to override the horn selection. Horns and strobes may be overridden to the patterns listed below:
1. Continuous EM
2. Temporal EM
3. Double March Time EM (240 strokes/min.)
4. March Time EM (120 strokes/min.)
5. Canadian EM (20 strokes/min.)
6. Strobe Disable
7. Strobe Enable For complete details, refer to panel Installation Manual.
System Operation – Non-Synchronized Devices:
Figure 4a: Any combination of models powered by a
2-wire circuit:
System Operation – Synchronized Devices:
Figure 4b: Any combination of models powered by a
2-wire circuit:
Figure 5: Horns and strobes powered in tandem
NOTE: Supply power must be continuous for proper
operation.
D900-28-00 3 I56-1796-008R
A0111-00
A0112-00
Figure 6: Any combination of models powered by a 4-wire circuit to provide independent horn and strobe operation (remove factory installed jumpers, see Figure 8)
NOTE: Strobes must be powered continuously for horn operation.
A0113-00
Figure 7: Horns and strobes powered independently (horn operated on coded power supply)
NOTE: Strobes must be powered continuously for horn operation.
A0114-00
PLASTIC SNAP LEVER
TA
B SLOT
TA
B
INSERT REMOVAL TOOL
4-INCH BACK BOX
WA
LL OPENING MUST
EQUAL PLATE OPENING
LOCKING RIB SLOT
LOCKING RIB
D-MP, D-MPW, D-MP-FC, D-MPW-FC
A
A
4-INCH BACK BOX
BBS, BBSW
LOCKING RIB SLOT
A
A
LOCKING RIB
WARNING
Figure 8: Removal of horns and strobes from mount-
2-INCH BACK BOX
WA
LL OPENING MUST
EQUAL PLATE OPENING
B
B
LOCKING RIB SLOT
LOCKING RIB
S-MP, S-MPW
ing plates
To remove units from mounting plates, insert Quick Click Removal Tool as shown to unlock snap. While pushing in Removal Tool to release the snap, pull back on the horn/strobe. Hinge the horn/strobe module, disengage the Locking Rib, and lift the horn/strobe away from the mount­ing plate.
A0115-00
Mounting Diagrams:
Screw types used for mounting:
A = 8-32 x 3⁄4 flat head B = 6-32 x 15⁄16 pan head
Strobe or Horn/Strobe with universal mounting plate:
A0117-00
1. Mount plate to back box using screws A, making sure wall opening is equal to the plate opening.
2. Complete field wiring.
3. Insert locking rib into slot on plate.
4. Press into plate, unit will make a “click” when it has locked into place.
Strobe or Horn/Strobe with small footprint mounting plate:
1. Mount plate to back box using screws B.
2. Break off four tabs from unit.
3. Complete field wir­ing, making sure wall opening is large enough for terminals to fit through.
A0116-00
4. Insert locking rib into slot on plate.
5. Press into plate; unit will make a “click” when it has locked into place.
Strobe or Horn/Strobe sur face mount:
1. Mount skirt to back box with screws A.
2. Complete field wiring.
3. Insert locking rib on unit into slot on skirt.
4. Press into skirt; unit will make a “click” when it has locked into place.
(Note: Strobe and skirt may also be mounted to a 2-inch box using screws B instead of screws A.)
A0118-00
Please refer to insert for the Limitations of Fire Alarm Systems
The horn and/or strobe will not work without power. The horn/strobe gets its power from the fire/security panel monitoring the alarm system. If power is cut off for any reason, the horn/strobe will not provide the desired audio or visual warning.
The horn may not be heard. The loudness of the horn meets (or exceeds) current Underwriters Laboratories’ standards. However, the horn may not alert a sound sleeper or one who has recently used drugs or has been drinking alcoholic beverages. The horn may not be heard if it is placed on a different floor from the person in hazard or if placed too far away to be heard over the ambient noise such as traffic, air conditioners, machinery or music appliances that may prevent alert persons from hearing the alarm. The horn may not be heard by persons who are hearing impaired.
NOTE: Strobes must be powered continuously for horn operation.
System Sensor warrants its enclosed horn. strobe, or horn/strobe to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manu­facture. System Sensor makes no other express warranty for this horn, strobe, or horn/strobe. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the horn, strobe, or horn/strobe which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid
SpectrAlert Strobes and Horn/Strobes have been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a com­mercial environment. This equipment generates, uses, and can radiate radio frequency energy
D900-28-00 4 I56-1796-008R
The Limitations of Horn/Strobes
The signal strobe may not be seen. The electronic visual warning signal uses an extremely reliable xenon flash tube. It flashes at least once every second. The strobe must not be installed in direct sunlight or areas of high light intensity (over 60 foot candles) where the visual flash might be disre­garded or not seen. The strobe may not be seen by the visually impaired.
The signal strobe may cause seizures. Individuals who have positive photoic response to visual stimuli with seizures, such as persons with epilepsy, should avoid prolonged exposure to environ­ments in which strobe signals, including this strobe, are activated.
The signal strobe cannot operate from coded power supplies. Coded power supplies produce interrupted power. The strobe must have an uninterrupted source of power in order to operate cor­rectly. System Sensor recommends that the horn and signal strobe always be used in combination so that the risks from any of the above limitations are minimized.
Three-Year Limited Warranty
to: System Sensor, Returns Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of dam­age, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
FCC Statement
and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.