System Sensor S1224MCK, P1224MCK, H1224K User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
1
/2 Sec.
On
1
/2 Sec.
Off
1
/2 Sec.
On
1
/2 Sec.
Off
1
/2 Sec.
On
11/2 Sec.
Off
Repeats
SpectrAlert Selectable Output Outdoor Strobes, Horn and Horn/Strobes
For use with the following models: Strobe - 12/24 volt: S1224MCK Combo - 12/24 volt: P1224MCK Horn - 12/24 volt: H12/24K
“K” model series are outdoor rated when installed with System Sensor WBB. The Products to which this manual applies may be covered by one or more of the following U.S. Patent numbers: 5,914,665; 5,850,178; 5,598,139; 6,049,446; 6,133,843; 6,522,261; 6,661,337; 6,793,375; 6,822,400; 5,931,569; 6,833,783; 6,838,997;
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Specifications
Automatic selection for 12 or 24 volt rated operation (DC or Full-Wave Rectified)
Electrical
Horns, Strobes, and Horn/Strobes Voltages: Regulated 12 DC/FWR and Regulated 24 DC/FWR Operational Voltage Ranges: 12V=8-17.5 Volts; 24V=16-33 Volts Synchronous Applications with MDL Module: 12V=9-17.5 Volts; 24V=17-33 Volts
NOTE: Horn units will operate on walk tests with on-time durations of .25 sec. or greater.
Flash Rate: 1 flash per second K Series Operating Temperature: Strobe, horn and horn/strobe models are indoor and outdoor listed, having a temperature
range of –40° F to 150.8° F (–40° C to 66° C) All models are indoor/outdoor listed, strobes per UL 1971 and UL 1638, horns per UL 464. Selectable Light Outputs: All candelas are selectable via a manual slide switch. 12/24 Volt Applications: 15 or 15/75 candela 24 Volt Application: 30, 75, 110 candela 15/75 is listed at 15 candela per UL 1971 but will provide 75 candela on axis (straight ahead).
15, 30, 75, or 110 are rated for that candela. Sound Output: Sound output levels are established at Underwriters Laboratories in their reverberant room.
Always use the sound output specified as UL Reverberant Room when comparing products. Listings: UL S3593/S5512 (Strobe); UL S4011 (Combo); UL 1638 and UL 1971 (Strobe); UL50 (Horn)
Note for Strobes: Do not exceed; 1) 8-17.5 or 16-33 voltage range limit; 2) maximum number of 70 strobe lights when connecting the MDL Sync module with a maximum line impedance of 4 ohms per loop and; 3) maximum line impedance as required by the fire alarm control manufacturer.
The models selections. The benefit to the customer is a high quality strobe device.
S1224MCK and P1224MCK
incorporate a patented voltage booster design that has a more consistent flash bulb voltage over the range of candela
General Description
The SpectrAlert series notification appliances are designed to meet the requirements of most agencies governing these devices, including: NFPA, ADA, The National Fire Alarm Code, UL, and ULC. Also, check with your local Authority Having Jurisdiction for other codes or standards that may apply.
The SpectrAlert series can be installed in systems using 12- or 24­volt panels having DC or full-wave rectified (FWR) power supplies. The series can also be installed in systems requiring synchroniza tion (module MDL or compatible equivalent required) or systems that do not require synchronization (no module required).
NOTICE: This manual shall be left with the owner/user of this equipment.
Fire Alarm System Considerations
Temporal and Non-Temporal Coded Signals:
The American National Standards Institute and the National Fire Alarm Code require that all horns used for building evacuation in stalled after July 1, 1996, must produce Temporal Coded Signals.
Signals other than those used for evacuation purposes do not have to produce the Temporal Coded Signal. Temporal coding is accom plished by interrupting a steady sound in the following manner:
D900-37-00 1 I56-2257-005R
Power Supply Considerations
Panels typically supply DC filtered voltage or FWR (full-wave rectified) voltage. The system design engineer must calculate the number of units used in a zone based on the type of panel supply. Be certain the sum of all the device currents do not exceed the
­current capability of the panel. Calculations are based on using
the device current found in the subsequent charts and must be the current specified for the type of panel power supply used.
Wire Sizes
The designer must be sure that the last device on the circuit has sufficient voltage to operate the device within its rated voltage. When calculating the voltage available to the last device, it is nec
-
essary to consider the voltage drop due to the resistance of the wire. The thicker the wire, the less the voltage drop. Generally, for purposes of determining the wire size necessary for the system, it is best to consider all of the devices as “lumped” on the end of the
­supply circuit (simulates “worst case”).
-
Typical wire size resistance:
18 AWG solid: Approximately 8 ohms/1,000 ft. 16 AWG solid: Approximately 5 ohms/1,000 ft. 14 AWG solid: Approximately 3 ohms/1,000 ft. 12 AWG solid: Approximately 2 ohms/1,000 ft.
Example: Assume you have 10 devices on a zone and each re quires 50 mA average and 2000 Ft. of 14 AWG wiring (total length=outgoing +return). The voltage at the end of the loop is
0.050 amps per device x 10 devices x 3 ohms/1,000 ft. x 2000 ft =3 volts drop.
NOTE: If class “A” wiring is installed, the wire length may be up to 4 times the single wire length in this calculation.
The same number of devices using 12 AWG wire will produce only 2 volts drop. The same devices using 18 AWG wire will produce 8 volts drop. Consult your panel manufacturer’s specifications, as well as SpectrAlert’s operating voltage range to determine accept able voltage drop.
Figure 1A: Current Draw Measurements (RMS)
NOTE: All ‘S’ and ‘P’ models were only tested at the 8-17.5 and 16-33 Volt-FWR/DC limits. This does not include the 80% low­end or 110% high-end voltage limits.
Strobe Current Draw
Candela Setting
15
15/75
30
75
110
FWR
Operating
Current
Strobe
12V 24V 12V 24V
112 64 127 59
135 74 127 69
93 90
158 160
208 209
DC
Operating
Current
Strobe
NOTE: 12 VDC 2-wire horn/strobe current is shown in Figure 1D. 24VDC 2-wire horn/strobe current draw is shown in Figure 1E. Horn/Strobe current draw can be calculated by adding the strobe current draw (Figure 1A) for chosen candela setting to the horn current draw (Figure 1C) for chosen setting.
Figure 1B: Horn Sound Measurements (dBA):
Selectable Horn Tones
Temporal Low
Non­Temporal
Volume
High Volume
Low Volume
High Volume
Electromechanical 67 75
3000 Hz Interr upted 68 75
Electromechanical 71 80
3000 Hz Interr upted 72 81
Electromechanical
3000 Hz Interr upted 72 79
Electromechanical 76 84
3000 Hz Interr upted 77 86
8-17.5V 16-33V
71 79
Figure 1C: Horn Current Draw Measurements (RMS):
Selectable Horn Tones
Temporal Low
-
Non­Temporal
Volume
High Volume
Low Volume
High Volume
NOTE: Regulated 12 VDC, max operating current 44.4 mA Regulated 24 VDC, max operating current 57.0 mA 12 V FWR, max operating current 45.7 mA
­ 24 V FWR, max operating current 57.5 mA
Electromechanical 15 23 13 23
3000 Hz Interr upted 15 33 13 23
Electromechanical 36 53 20 44
3000 Hz Interr upted 43 57 21 40
Electromechanical
3000 Hz Interr upted 16 32 18 33
Electromechanical 38 49 46 49
3000 Hz Interr upted 44 56 42 58
DC FWR
12V 24V 12V 24V
16 37 19 29
Figure 1D: 12VDC Horn/Strobe Current Draw Measurements (mA RMS)
Temporal
Low Volume High Volume
Candela
Setting
15 111 111 112 112
15/75 127 127 126 129
15 113 112 114 115
15/75 128 128 130 134
Electromechanical 3000 Hz Electromechanical 3000 Hz
Non-Temporal
Figure 1E: 24VDC Horn/Strobe Current Draw Measurements (mA RMS)
Temporal
Low Volume High Volume
Candela
Setting
15/75 86 85 87 88
110 209 209 210 213
15/75 86 88 93 96
110 213 213 218 222
Electromechanical 3000 Hz Electromechanical 3000 Hz
15 71 70 73 75
30 99 98 100 100
75 166 166 167 170
Non-Temporal
15 74 74 79 82
30 101 101 107 110
75 167 167 173 176
Candela equivalent at –40°C and below:
15cd 3cd 15/75cd 20cd 30cd 9cd 75cd 27cd 110cd 46cd
D900-37-00 2 I56-2257-005R
HORN
(+)
(–)
(+)
(–)
E O L
(+)
(–)
(+)
(–)
HORN/STROBE
STROBE ONLY
TWO WIRE SYSTEM ANY MIX OF MODELS WIRED FOR TANDEM
OPERATION
HORN
(+)
(–)
(+)
(–)
E O L
(+)
(–)
(+)
(–)
HORN/STROBE
STROBE ONLY
TWO WIRE SYSTEM ANY MIX OF MODELS WIRED FOR TANDEM
OPERATION
HORN
SYNCHRONIZATION MODULE
MDL
(+)
(–)
(+)
(–)
E O L
(+)
(–)
(+)
(–)
HORN/STROBE
STROBE ONLY
TWO WIRE SYSTEM ANY MIX OF MODELS WIRED FOR TANDEM
OPERATION
FROM: FACP, MODULE OR PREVIOUS DEVICE
TO NEXT
DEVICE OR
EOL
+
Strobe +
Strobe – Horn –
Horn +
TANDEM OPERATION
HORN/STROBE COMBO
FACTORY INSTALLED JUMPERS
(+)
(–)
(+)
(–)
(+)
(–)
FOUR WIRE SYSTEM
COMBO MODELS
WIRED FOR INDEPENDENT
OPERATION
(HORN CAN BE TURNED OFF
AT THE PANEL WHILE STROBES
CONTINUE TO OPERATE)
E O L
(+)
(–)
(+)
(–)
(+)
(–)
E O L
S
T R O B E
C O M B O
H O R N
H O R N
S T R O B E
FROM: FACP, MODULE (MDL) OR PREVIOUS DEVICE
Break wire as shown for supervision of connection. DO NOT allow stripped wire leads to extend beyond switch housing. DO NOT loop wires.
TO NEXT
DEVICE OR
EOL
INDEPENDENT OPERATION
HORN AND STROBE
TO NEXT
DEVICE OR
EOL
STROBE +
HORN +
STROBE +
STROBE –
STROBE –
HORN –
HORN –
HORN +
FACTORY INSTALLED
JUMPER WIRES REMOVED
NOTE: STROBES MUST BE POWERED CONTINUOUSLY FOR HORN OPERATION.
Candela Selections:
Low
OFF ON
Temporal
Electromech.
DIP Switch
Factory Default
High
Non-Temporal
3000Hz
Base (rear)
WARNING
Viewing Window
Figure 2: For strobe candela selection, adjust slide switch located on the rear of the product while watch­ing the viewing window on the side of the reflector.
NOTE: SpectrAlert selectable out­put strobes, set at 15 and 15/75cd, automatically work on both 12V and 24V power supplies.
NOTE: The strobe is not listed
A0133-00
for 12V operating voltages when set to 30, 75 or 110 candelas. Use only those settings marked as OK in this chart:
Permissible Candela Settings:
Candela
Setting
15 OK OK
15/75 OK OK
30 OK
75 OK
110 OK
Operating Voltage
12V 24V
Horn selections using 3-position DIP switch on horn/ strobe (refer to Figure 3):
NOTE: When powered from a FWR supply, the horn will be mod­ulated (turned on and off) by 120Hz causing it to sound different than if powered by a DC supply.
High/Low Volume ON=High Volume, OFF=Low Volume
NOTE: The low volume setting of some tones must NOT be used for public mode applications when the device is powered from a 12­volt panel. Refer to the Sound Output Guide on the previous page.
Temp/Non-Temp ON=NON-Temporal, OFF=Temporal 3KHz/Electromechanical ON=3KHz, OFF=Electromechanical
System Operation – Non-Synchronized Devices: Figure 4a. Any combination of models powered by a 2-wire circuit:
A0111-00
System Operation – Synchronized Devices: Figure 4b. Any combination of models powered by a 2-wire circuit:
A0111-00
Figure 5: Horns and strobes powered in tandem:
NOTE: Supply power must be continuous for proper operation.
A0112-00
Figure 6: Any combination of models powered by a 4­wire circuit to provide independent horn and strobe op­eration (remove factory installed jumpers, see Figure 8):
NOTE: Strobes must be powered continuously for horn operation.
Figure 3: Horn Factory Default Setting:
The factory default setting is High, Temporal 3, and Electrome­chanical tone.
Figure 7: Horns and strobes powered indepen­dently (horn operated on coded power supply):
NOTE: Strobes must be powered continuously for horn operation.
Check terminal polarity before wiring. For proper operation, make sure the correct wire polarity is applied to the unit.
D900-37-00 3 I56-2257-005R
A0110-00
A0113-00
A0114-00
WARNING
7""
'ASKET
0LATE
Xq&LAT(EAD 3CREWTOTAL
0APER,INER &OR0LATE 'ASKET
#ONDUIT %NTRANCE
3LOT
,OCKING2IB
Figure 8: Removal of horns and strobes from
PLASTIC SNAP LEVER
TAB SLOT
TAB
INSERT REMOVAL TOOL
mounting plates:
To remove units from mounting plates, insert Quick Click Re­moval Tool as shown to unlock snap. While pushing in Removal Tool to release the snap, pull back on the horn/strobe. Hinge the horn/strobe module, disengage the Locking Rib, and lift the horn/ strobe away from the mounting plate.
A0115-00
Typical outdoor mounting with universal plate:
A0120-00
1. Mount WBB in desired location.
2. For SpectrAlert models, mount plate to back box using 4 #8-
3. Complete field wiring.
4. Remove paper liner on gasket -
5. Insert locking rib into slot on plate.
6. Press into plate, the SpectrAlert model will make a “click”
NOTE: The outdoor notification appliance must be used with a WBB back box when installed in applications requiring the appli ance to be outdoor-listed. In such applications, using a back box other than the WBB will void the UL designation.
1
32
/2˝ screws.
NOTE: Perform electrical tests first, then remove liner. Paper liner must be re­moved from gasket before final installation.
when it has locked into place.
-
Please refer to insert for the Limitations of Fire Alarm Systems
The Limitations of Horn/Strobes
The horn and/or strobe will not work without power. The horn/strobe gets its power from the fire/security panel monitoring the alarm system. If power is cut off for any reason, the horn/strobe will not provide the desired audio or visual warning. The horn may not be heard. The loudness of the horn meets (or ex­ceeds) current Underwriters Laboratories’ standards. However, the horn may not alert a sound sleeper or one who has recently used drugs or has been drinking alcoholic beverages. The horn may not be heard if it is placed on a different floor from the person in hazard or if placed too far away to be heard over the ambient noise such as traffic, air conditioners, machinery or music appliances that may prevent alert persons from hear­ing the alarm. The horn may not be heard by persons who are hearing impaired. NOTE: Strobes must be powered continuously for horn operation.
System Sensor warrants its enclosed horn. strobe, or horn/strobe to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this horn, strobe, or horn/strobe. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the horn, strobe, or horn/strobe which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor,
Three-Year Limited Warranty
The signal strobe may not be seen. The electronic visual warning signal uses an extremely reliable xenon flash tube. It flashes at least once every second. The strobe must not be installed in direct sunlight or areas of high light intensity (over 60 foot candles) where the visual flash might be disre­garded or not seen. The strobe may not be seen by the visually impaired. The signal strobe may cause seizures. Individuals who have positive photoic response to visual stimuli with seizures, such as persons with epi­lepsy, should avoid prolonged exposure to environments in which strobe signals, including this strobe, are activated. The signal strobe cannot operate from coded power supplies. Coded power supplies produce interrupted power. The strobe must have an un­interrupted source of power in order to operate correctly. System Sensor recommends that the horn and signal strobe always be used in combina­tion so that the risks from any of the above limitations are minimized.
Returns Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be de fective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any conse quential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s neg ligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
-
-
-
SpectrAlert Strobes and Horn/Strobes have been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and
D900-37-00 4 I56-2257-005R © 2005 System Sensor
FCC Statement
used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Loading...