SpectrAlert Selectable Output Strobes,
Horns, and Horn/Strobes
For use with the following models:
Strobes - 12/24 volt: S1224MC, S1224MCW, S1224MCSP, S1224MCSPW, S1224MCP, S1224MCPW
Combo - 12/24 volt: P1224MC, P1224MCW, P1224MCSP, P1224MCSPW, P1224MCP, P1224MCPW
Horns - H12/24, H12/24W
Suffix “W” indicates white housing models. Suffix “SP” indicates “FUEGO” (Spanish word for “FIRE”) lettering on housing.
Suffix “P” indicates plain housing (no lettering).
The Products to which this manual applies may be covered by one or more of the
following U.S. Patent numbers: 5,914,665; 5,850,178; 5,598,139; 6,049,446; 6,133,843; 6,522,261; 6,661,337; 5,931,569; 6,793,375; 6,822,400; 6,833,783; 6,838,997
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Specifications
Automatic selection for 12 or 24 volt rated operation (DC or Full-Wave Rectified)
Electrical
Horns, Strobes, and
Horn/Strobes Voltages: Regulated 12 DC/FWR and Regulated 24 DC/FWR
Operational Voltage Ranges: 12V=8-17.5 Volts; 24V=16-33 Volts
Synchronous Applications
with MDL Module: 12V=9-17.5 Volts; 24V=17-33 Volts
Operational Humidity Range: 10-93% RH (non-condensing)
NOTE: Horn units will operate on walk tests with on-time durations of .25 sec. or greater.
Flash Rate: 1 flash per second
Operating Temperature: 32° F to 120° F (0° C to 49° C)
Selectable Light Outputs: All candelas are selectable via a manual slide switch.
12/24 Volt Applications: 15 or 15/75 candela
24 Volt Application: 30, 75, 110 candela
15/75 is listed at 15 candela per UL 1971 but will provide 75 candela on axis
(straight ahead). 15, 30, 75, or 110 are rated for that candela.
Sound Output: Sound output levels are established at Underwriters Laboratories in their reverber-
ant room. Always use the sound output specified as UL Reverberant Room when
comparing products.
Listings: UL S5512 (Strobe); UL S4011 (Combo)
Note for Strobes: Do not exceed: 1) 8-17.5 or 16-33 voltage range limit; 2) maximum number of 70
strobe lights when connecting the MDL Sync module with a maximum line im-
pedance of 4 ohms per loop and; 3) maximum line impedance as required by the
fire alarm control manufacturer.
The models
P1224MCPW
the customer is a high quality strobe device.
incorporate a patented voltage booster design that has a more consistent flash bulb voltage over the range of candela selections. The benefit to
General Description
The SpectrAlert series notification appliances are designed to
meet the requirements of most agencies governing these devices,
including: NFPA, ADA, The National Fire Alarm Code, UL, ULC,
FM, CSFM, MEA. Also, check with your local Authority Having
Jurisdiction for other codes or standards that may apply.
The SpectrAlert series can be installed in systems using 12- or 24volt panels having DC or full-wave rectified (FWR) power supplies.
The series can also be installed in systems requiring synchroniza
tion (module MDL or compatible equivalent required) or systems
that do not require synchronization (no module required).
NOTICE: This manual shall be left with the owner/user of this equipment.
Fire Alarm System Considerations
Temporal and Non-Temporal Coded Signals:
The American National Standards Institute and the National Fire
Alarm Code require that all horns used for building evacuation in
D900-28-00 1 I56-1796-011R
stalled after July 1, 1996, must produce Temporal Coded Signals.
Signals other than those used for evacuation purposes do not have
to produce the Temporal Coded Signal. Temporal coding is accom
plished by interrupting a steady sound in the following manner:
-
Power Supply Considerations
Panels typically supply DC filtered voltage or FWR (full-wave
rectified) voltage. The system design engineer must calculate the
number of units used in a zone based on the type of panel supply.
Be certain the sum of all the device currents do not exceed the
current capability of the panel. Calculations are based on using
the device current found in the subsequent charts and must be
the current specified for the type of panel power supply used.
-
-
Wire Sizes
The designer must be sure that the last device on the circuit has
sufficient voltage to operate the device within its rated voltage.
When calculating the voltage available to the last device, it is nec
essary to consider the voltage drop due to the resistance of the
wire. The thicker the wire, the less the voltage drop. Generally, for
purposes of determining the wire size necessary for the system, it
is best to consider all of the devices as “lumped” on the end of the
supply circuit (simulates “worst case”).
Typical wire size resistance:
18 AWG solid: Approximately 8 ohms/1,000 ft.
16 AWG solid: Approximately 5 ohms/1,000 ft.
14 AWG solid: Approximately 3 ohms/1,000 ft.
12 AWG solid: Approximately 2 ohms/1,000 ft.
Example: Assume you have 10 devices on a zone and each re
quires 50 mA average and 2000 Ft. of 14 AWG wiring (total
length=outgoing +return). The voltage at the end of the loop is
0.050 amps per device x 10 devices x 3 ohms/1,000 ft. x 2000 ft
=3 volts drop.
NOTE: If class “A” wiring is installed, the wire length may be up
to 4 times the single wire length in this calculation.
The same number of devices using 12 AWG wire will produce only
2 volts drop. The same devices using 18 AWG wire will produce
8 volts drop. Consult your panel manufacturer’s specifications, as
well as SpectrAlert’s operating voltage range to determine accept
able voltage drop.
Figure 1A: Current Draw Measurements (RMS)
NOTE: All ‘S’ and ‘P’ models were only tested at the 8-17.5 and
16-33 Volt-FWR/DC limits. This does not include the 80% lowend or 110% high-end voltage limits.
Strobe Current Draw
Candela
Setting
15
15/75
30
75
110
FWR
Operating
Current
Strobe
12V24V12V 24V
1126412759
1357412769
9390
158160
208209
DC
Operating
Current
Strobe
Figure 1B: Horn Sound Measurements (dBA):
Selectable Horn Tones
Temporal Low
NonTemporal
Volume
High
Volume
Low
Volume
High
Volume
Electromechanical6775
3000 Hz Interr upted6875
Electromechanical7180
3000 Hz Interr upted7281
Electromechanical
3000 Hz Interr upted7279
Electromechanical7684
3000 Hz Interr upted7786
8-17.5V16-33V
7179
Figure 1C: Horn Current Draw Measurements (RMS):
-
-
Selectable Horn Tones
Temporal Low
NonTemporal
Volume
High
Volume
Low
Volume
High
Volume
NOTE: Regulated 12 VDC, max operating current 44.4 mA
Regulated 24 VDC, max operating current 57.0 mA
12 V FWR, max operating current 45.7 mA
24 V FWR, max operating current 57.5 mA
NOTE: 12VDC 2-wire horn/strobe current is shown in Figure 1D.
24VDC 2-wire horn/strobe current is shown in Figure 1E. Current
draw for other horn/strobe power supplies can be calculated by
adding the strobe current draw (Figure 1A) for chosen candela set
ting to the horn current draw (Figure 1C) for chosen setting.
Electromechanical15231323
3000 Hz Interr upted15331323
Electromechanical36532044
3000 Hz Interr upted43572140
Electromechanical
3000 Hz Interr upted16321833
Electromechanical38494649
3000 Hz Interr upted44564258
DCFWR
12V24V12V24V
16371929
Figure 1D: 12VDC Horn/Strobe Current Draw
Measurements (mA RMS)
TWO WIRE SYSTEM
ANY MIX OF MODELS
WIRED FOR TANDEM
OPERATION
HORN
(+)
(–)
(+)
(–)
E
O
L
(+)
(–)
(+)
(–)
HORN/STROBE
STROBE ONLY
TWO WIRE SYSTEM
ANY MIX OF MODELSWIRED FOR TANDEM
OPERATION
HORN
SYNCHRONIZATION MODULE
MDL
(+)
(–)
(+)
(–)
E
O
L
(+)
(–)
(+)
(–)
HORN/STROBE
STROBE ONLY
TWO WIRE SYSTEM
ANY MIX OF MODELS
WIRED FOR TANDEM
OPERATION
For strobe candela selection, adjust slide switch located
on the rear of the product while watching the viewing window on the side of the reflector.
Permissible Candela Settings:
A0133-00
Candela
Setting
15OKOK
15/75OKOK
30OK
75OK
110OK
Operating Voltage
12V24V
Check terminal polarity before wiring. For proper operation, make sure the correct wire
polarity is applied to the unit.
NOTE: SpectrAlert selectable output strobes, set at 15 and 15/75cd,
automatically work on both 12V and 24V power supplies.
NOTE: The strobe is not listed for 12V operating voltages when
set to 30, 75 or 110 candelas. Use only those settings marked as
OK in the chart above.
NOTE: The low volume setting of some tones must NOT be used
for public mode applications when the device is powered from a 12volt panel. Refer to the Sound Output Guide on the previous page.
The factory default setting is High, Temporal 3, and Electromechanical tone.
A0110-00
Horn selections using 3-position DIP switch on horn/
strobe (refer to Figure 3):
NOTE: When powered from a FWR supply, the horn will be modulated (turned on and off) by 120Hz causing it to sound different
than if powered by a DC supply.
High/Low Volume
ON=High Volume, OFF=Low Volume
System Operation – Non-Synchronized Devices:
Figure 4a: Any combination of models powered by a
2-wire circuit:
Figure 5: Horns and strobes powered in tandem
NOTE: Supply power must be continuous for proper operation.
A0112-00
Figure 6: Any combination of models powered by a
4-wire circuit to provide independent horn and strobe operation (remove factory installed jumpers, see Figure 8)
NOTE: Strobes must be powered continuously for horn operation.
A0111-00
System Operation – Synchronized Devices:
Figure 4b: Any combination of models powered by a
2-wire circuit:
D900-28-00 3 I56-1796-011R
A0111-00
A0113-00
PLASTIC SNAP LEVER
TAB SLOT
TAB
INSERT REMOVAL TOOL
4-INCH BACK BOX
WALL OPENING MUST
EQUAL PLATE OPENING
LOCKING RIB SLOT
LOCKING RIB
D-MP, D-MPW, D-MP-FC, D-MPW-FC
A
A
4-INCH BACK BOX
BBS, BBSW
LOCKING RIB SLOT
A
A
LOCKING RIB
2-INCH BACK BOX
WALL OPENING MUST
EQUAL PLATE OPENING
B
B
LOCKING RIB SLOT
LOCKING RIB
S-MP, S-MPW
Figure 7: Horns and strobes powered independently
FROM:
FACP, MODULE (MDL)
OR PREVIOUS
DEVICE
Break wire as shown for
supervision of connection.
DO NOT allow stripped wire
leads to extend beyond switch
housing. DO NOT loop wires.
TO NEXT
DEVICE OR
EOL
INDEPENDENT OPERATION
HORN AND STROBE
TO NEXT
DEVICE OR
EOL
STROBE +
HORN +
STROBE +
STROBE –
STROBE –
HORN –
HORN –
HORN +
FACTORY INSTALLED
JUMPER WIRES REMOVED
NOTE: STROBES MUST
BE POWERED CONTINUOUSLY
FOR HORN OPERATION.
(horn operated on coded power supply)
NOTE: Strobes must be powered continuously for horn operation.
A0114-00
Mounting Diagrams:
Screw types used for mounting:
A = 8-32 x 3⁄4 flat head
B = 6-32 x 15⁄16 pan head
Strobe or Horn/Strobe with universal mounting plate:
Figure 8: Removal of horns and strobes from
mounting plates
To remove units from mounting plates, insert Quick Click Removal Tool as shown to unlock snap. While pushing in Removal
Tool to release the snap, pull back on the horn/strobe. Hinge the
horn/strobe module, disengage the Locking Rib, and lift the horn/
strobe away from the mounting plate.
A0115-00
Strobe or Horn/Strobe with small footprint
mounting plate:
1. Mount plate to back box using screws B.
2. Break off four tabs from unit.
3. Complete field wiring, making sure wall opening is large enough for
terminals to fit through.
4. Insert locking rib into slot on plate.
5. Press into plate; unit will make a “click” when it has locked into place.
A0117-00
Strobe or Horn/Strobe surface mount:
1. Mount plate to back box using screws A, making sure wall
opening is equal to the plate opening.
2. Complete field wiring.
3. Insert locking rib into slot on plate.
4. Press into plate, unit will make a “click” when it has locked
into place.
1. Mount skirt to back box with screws A.
2. Complete field wiring.
3. Insert locking rib on unit into slot on skirt.
4. Press into skirt; unit will make a “click” when it has locked into place.
(NOTE: Strobe and skirt may also be mounted to a 2-inch box using
screws B instead of screws A.)
Please refer to insert for the Limitations of Fire Alarm Systems
Three-Year Limited Warranty
System Sensor warrants its enclosed horn. strobe, or horn/strobe to be free from defects in materials
and workmanship under normal use and service for a period of three years from date of manu
facture. System Sensor makes no other express warranty for this horn, strobe, or horn/strobe. No
agent, representative, dealer, or employee of the Company has the authority to increase or alter
the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be
limited to the repair or replacement of any part of the horn, strobe, or horn/strobe which is found
to be defective in materials or workmanship under normal use and service during the three year
period commencing with the date of manufacture. After phoning System Sensor’s toll free number
800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid
SpectrAlert Strobes and Horn/Strobes have been tested and found to comply with the limits for a
Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated in a com
mercial environment. This equipment generates, uses, and can radiate radio frequency energy
to: System Sensor, Returns Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174.
-
Please include a note describing the malfunction and suspected cause of failure. The Company
shall not be obligated to repair or replace units which are found to be defective because of dam
age, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no
case shall the Company be liable for any consequential or incidental damages for breach of this or
any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the
Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or
consequential damages, so the above limitation or exclusion may not apply to you. This Warranty
gives you specific legal rights, and you may also have other rights which vary from state to state.
and, if not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area is likely
-
to cause harmful interference in which case the user will be required to correct the interference
at his own expense.
A0116-00
A0118-00
-
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.