System Sensor RTS151KEYА User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-0758-015
RTS151KEY(A) Remote Test Station
SpECIfICATIONS
Dimensions: 4.6˝ H × 2.75˝ W × 1.8˝ D Weight: 0.24 Lbs.
Power Requirements
Power LED (Green): 14 – 35 VDC, 12 mA maximum Alarm LED (Red): 2.8 – 32 VDC, 12 mA maximum Alarm Response Time: 40 seconds maximum Temperature: –10°C to 60°C (14°F to 140°F) Humidity: 95% relative humidity, noncondensing Max Listing: UL, FM, CE
NOTE: RTS151KEY(A) replaces RTS451KEY. NOTICE: This manual shall be left with the owner/user of this equipment. NOTE: A test coil is required only for use with D2/DNR/DH400/DH500 mod­els. For D2 models order part # DCOIL. For DH400/500 models order part #Coil.
GENERAL INfORMATION
The System Sensor RTS151KEY(A) is an automatic fire detector accessory de­signed to test remotely located duct and beam detectors. For 4-wire detectors, the RTS151KEY(A) features a multi-colored LED that alternates between steady green and red. Green indicates power and that the detector board is in place. Red indicates alarm. For 2-wire detectors, the LED will show red for alarm. Consult the detector installation instructions for additional information.
The National Fire Protection Association has published codes, standards, and recommended practices for the installation and use of this product. It is rec­ommended that the installer be familiar with these requirements, with local codes, and any special requirements of the local authority having jurisdiction.
RTS151 CONTENTS
1 RTS151KEY(A) remote test station
1 screw pack (2 mounting screws)
2 Keys
OpERATION
Test Function
Insert the key and turn clockwise to the “TEST” position.
Alarm Indication
With the key in the “TEST” position, some time will elapse (40 seconds maxi­mum) depending on the detector type, before the alarm indicating LED will turn red.
Reset Function
Turn the key counterclockwise to the “RESET” position and hold. The LED should turn off. Then, turn the key back to the “NORMAL” position and re­move. The RTS151KEY(A) is capable of resetting only certain models of detec­tors. Refer to the detector installation instructions for additional information.
Wiring Instructions
Consult the appropriate detector installation instructions for the applicable wiring diagram. The RTS151KEY(A) mounts to a single gang box (2 1/2˝ mini­mum depth), or directly to the wall or ceiling.
In Canadian applications, the RTS151KEY(A) is intended to be located in the same room as the smoke detector and within 60 feet of the unit.
fIGURE 1. RTS151KEY(A)
fIGURE 2: WIRING DIAGRAM fOR RTS151KEY(A) TO D4120 4-WIRE DUCT SMOKE DETECTOR:
fIGURE 3: WIRING DIAGRAM fOR RTS151KEY(A) TO DNR 2-WIRE DUCT SMOKE DETECTOR WITH REMOTE TEST CApABLE HEAD:
OUT (CONV ONLY) +
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
AUX OUT +
AUX OUT –
ALARM
R TEST
R RESET
D4120
*
14
3
RTS451KEY(A)
FIELD INSTALLED JUMPER
(RED LED)
(GREEN LED)
POWER
* Sup. contacts cannot be used if they are wired to control panel.
ALARM
2
4
1
5
3
6
19
20
15
11
2
TEST COIL +
TEST COIL –
COMM +
RTS451/RTS451KEY RTS151/RTS151KEY
1
2
COMM –
RA/RTS –
RA +
3
4
H0195-01
SUP, NO
SUP, C
H0582-21
JUMPER
RTS +
5
H0633-00
D440-03-00 1 I56-0758-015
fIGURE 4: WIRING DIAGRAM fOR RTS151KEY(A) TO D2 2-WIRE DUCT SMOKE DETECTOR:
1
2
3
4
5
6
3
4
5
Test +
Test / Reset –
Reset +
Test
Reset
RA +
RA –
V Out +
DH100
RTS151KEY(A)
6
2
1
Alarm
LED
No Connection
AN ACCESSORY COIL, DCOIL, SOLD SEPARATELY.
MAGNET TEST SWITCH
ALARM LED (RED)
4
5
2
(–)
(+)
1
RTS151KEY(A)
(OPTIONAL) REMOTE
TEST STATION
+ TEST COIL
– TEST COIL
+ IN
+ OUT
– RA
+ RA
+ RTS
24 VDC
AUX POWER
(–)
SUPPLIED
BY USER
(+)
(100mA
SUPPLY)
24 VAC (+10%, –15%)
FULL WAVE RECTIFIED,
UNFILTERED POWER
MAY BE USED
D2
METHOD #1 - AUX POWER LOCATED
AT DUCT DETECTOR
NOTE: THE USE OF THE RTS151KEY(A) REQUIRES THE INSTALLATION OF
fIGURE 5. WIRING DIAGRAM fOR RTS151KEY(A) TO DH100ACDC 4-WIRE DUCT SMOKE DETECTOR:
DH100ACDCLP
Alarm Signal
Aux. Power +
Sup. N. O.
Sup. COM
Aux. Power “
Reset
Test
15
19
14
3
20
2
11
RTS151KEY(A)
(Red LED) Alarm
1
* Sup. contacts cannot be used if they are wired to control panel.
(Green LED)
6
Power
2
3
4
5
*
24 VDC
AUX POWER
SUPPLIED
BY USER
(100mA
SUPPLY)
24 VAC (+10%, –15%)
FULL WAVE RECTIFIED,
UNFILTERED POWER
MAY BE USED
MAGNET TEST SWITCH
ALARM LED (RED)
4
5
2
(–)
(+)
1
RTS151KEY(A)
(OPTIONAL) REMOTE
TEST STATION
+ TEST COIL
– TEST COIL
+ IN
+ OUT
– RA
+ RA
+ RTS
D2
METHOD #2 - AUX POWER LOCATED
AT TEST STATION
H0612-12
fIGURE 6. WIRING DIAGRAM fOR RTS151KEY(A) TO DH100 2-WIRE DUCT SMOKE DETECTOR:
NOTE: Terminal 6 of the RTS151KEY(A) is not used when wired to a 2-wire detector.
H0156-08
fIGURE 7. WIRING DIAGRAM fOR RTS151KEY(A) TO DH400ACDC DUCT SMOKE DETECTOR:
DH400ACDC
Alarm Signal
Aux. Power +
Sup. N. O.
Sup. COM
Aux. Power –
Reset
Test
5
7
11
10
6
3
4
RTS151KEY(A)
(Red LED) Alarm
1
* Sup. contacts cannot be used if they are wired to control panel.
(Green LED)
6
Power
2
3
4
5
*
fIGURE 8. WIRING DIAGRAM fOR RTS151KEY(A) TO BEAM1224/ BEAM1224S SMOKE DETECTOR:
RTS151KEY(A)BEAM1224/BEAM1224S
AUX (–)
T2-1
T2-2
T2-4
T3-3
T2-3
OPTIONAL YELLOW LED
(RED LED) ALARM
1
2
3
4
5
RESET
TEST
REMOTE ALARM OUT
RESET INPUT
REMOTE TROUBLE OUTPUT
TEST INPUT
NOTE: RTS151KEY(A) CAN BE USED WITH INTELLIGENT BEAM DETECTOR PRODUCTS. CONSULT INTELLIGENT BEAM DETECTOR MANUAL FOR ADDITIONAL INSTRUCTIONS
H0156-09
System Sensor warrants its enclosed product to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for the enclosed product. No agent, representative, dealer, or employee of the Company has the authority to in­crease or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the replacement of any part of the product which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Returns Department, RA
D440-03-00 2 I56-0758-015 ©2011 System Sensor
THREE-YEAR LIMITED WARRANTY
#__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
H0193-05
H0585-05