System Sensor RTS151KEYA Installation Instructions Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
* Sup. contacts cannot be used if they are wired to control panel.
RTS151KEYA
6581 Kitimat Road, Unit 6, Mississauga, Ontario L5N-3T5
1-800-SENSOR2, FAX: 905-812-0771
Remote Test Station
www.systemsensor.ca
SPECIFICATIONS
Dimensions: 4.6˝ H × 2.75˝ W × 1.8˝ D
Weight: 0.24 Lbs.
Power Requirements
Power LED (Green): 14 – 35 VDC, 12 mA maximum Alarm LED (Red): 2.8 – 32 VDC, 12 mA maximum Alarm Response Time: 40 seconds maximum Temperature: –10°C to 60°C (14°F to 140°F) Humidity: 95% relative humidity, noncondensing Max
NOTE: RTS151KEYA replaces RTS451KEYA.
FIGURE 1. RTS151KEYA
GENERAL INFORMATION
The System Sensor RTS151KEYA is an automatic fire detector accessory designed to test remotely located duct and beam detectors. For 4-wire detec­tors, the RTS151KEYA features a multi-colored LED that alternates between
OFF
RESET TEST
steady green and red. Green indicates power and that the detector board is in place. Red indicates alarm. For 2-wire detectors, the LED will show red for alarm. Consult the detector installation instructions for additional information.
The National Fire Protection Association and CAN/ULC-S536 has published codes, standards, and recommended practices for the installation and use of this product. It is recommended that the installer be familiar with these re­quirements, with local codes, and any special requirements of the local au­thority having jurisdiction.
RTS151KEYA CONTENTS
1 RTS151KEYA remote test station
1 screw pack (2 mounting screws)
2 Keys
OPERATION Test Function
FIGURE 2: WIRING DIAGRAM FOR RTS151KEYA TO D4120A 4-WIRE DUCT SMOKE DETECTOR:
RTS151KEYA
FIELD INSTALLED JUMPER
2
4
D4120A
AUX OUT +
AUX OUT –
H0195-01
Insert the key and turn clockwise to the “TEST” position.
EXTERNAL
*
(-) POWER (+)
SUPPLY
ALARM
R TEST
R RESET
*
SUP, NO
SUP, C
4 5
321
RTS151KEYA
REMOTE TEST STATION
LED OPTION
1 PER UNIT
10mA CURRENT DRAW
TEST COIL OPTION
1 PER UNIT
95mA CURRENT DRAW
H0582-13
H0571-10
Alarm Indication
With the key in the “TEST” position, some time will elapse (40 seconds maxi­mum) depending on the detector type, before the alarm indicating LED will turn red.
Reset Function
Turn the key counterclockwise to the “RESET” position and hold. The LED should turn off. Then, turn the key back to the “NORMAL” position and re­move. The RTS151KEYA is capable of resetting only certain models of detec­tors. Refer to the detector installation instructions for additional information.
Wiring Instructions
Consult the appropriate detector installation instructions for the applicable wiring diagram. The RTS151KEYA mounts to a single gang box (2 1/2˝ mini­mum depth), or directly to the wall or ceiling.
In Canadian applications, the RTS151KEYA is intended to be located in the same room as the smoke detector and within 60 feet of the unit.
(RED LED)
ALARM
(GREEN LED)
POWER
1
5
3
6
FIGURE 3: WIRING DIAGRAM FOR RTS151KEYA TO D2A 2-WIRE DUCT SMOKE DETECTOR:
TEST COIL +
TEST COIL –
COMM +
OUT (CONV ONLY) +
COMM –
RA/RTS –
RA +
RTS +
NOTE: THE RTS151KEYA TEST COIL CIRCUIT REQUIRES AN EXTERNAL 24 VDC POWER SUPPLY WHICH MUST BE UL LISTED.
NOTE: THE USE OF A REMOTE TEST STATION REQUIRES THE INSTALLATION OF AN ACCESSORY COIL, PART NUMBER DCOIL, SOLD SEPARATELY.
D440-03-00 1 I56-3475-000
FIGURE 4: WIRING DIAGRAM FOR RTS151KEYA TO DNRA 2-WIRE DUCT SMOKE DETECTOR:
1
2
3
4
5
6
3
4
5
Test +
Test / Reset –
Reset +
Test
Reset
RA +
RA –
V Out +
DH100
RTS151KEYA
6
2
1
Alarm
LED
No Connection
MAGNET TEST SWITCH
ALARM LED (RED)
4
5
2
(–)
(+)
1
RTS151KEYA
(OPTIONAL) REMOTE
TEST STATION
+ TEST COIL
– TEST COIL
+ IN
+ OUT
– RA
+ RA
+ RTS
24 VDC
AUX POWER
(–)
SUPPLIED
BY USER
(+)
(100mA
SUPPLY)
24 VAC (+10%, –15%)
FULL WAVE RECTIFIED,
UNFILTERED POWER
MAY BE USED
DNRA
METHOD #1 - AUX POWER LOCATED
AT DUCT DETECTOR
NOTE: THE USE OF THE RTS151KEYA REQUIRES THE INSTALLATION OF
AN ACCESSORY COIL, DCOIL, SOLD SEPARATELY.
FIGURE 5. WIRING DIAGRAM FOR RTS151KEYA TO DH100ACDC 4-WIRE DUCT SMOKE DETECTOR:
DH100ACDCLPA
Alarm Signal
Aux. Power +
Sup. N. O.
Sup. COM
Aux. Power –
Reset
Test
15
19
14
3
20
2
11
RTS151KEYA
(Red LED) Alarm
1
* Sup. contacts cannot be used if they are wired to control panel.
(Green LED)
6
Power
2
3
4
5
*
24 VDC
AUX POWER
SUPPLIED
BY USER
(100mA
SUPPLY)
24 VAC (+10%, –15%)
FULL WAVE RECTIFIED,
UNFILTERED POWER
MAY BE USED
MAGNET TEST SWITCH
ALARM LED (RED)
4
5
2
(–)
(+)
1
RTS151KEYA
(OPTIONAL) REMOTE
TEST STATION
+ TEST COIL
– TEST COIL
+ IN
+ OUT
– RA
+ RA
+ RTS
DNRA
METHOD #2 - AUX POWER LOCATED
AT TEST STATION
H0612-10
FIGURE 6. WIRING DIAGRAM FOR RTS151KEYA TO DH100 2-WIRE DUCT SMOKE DETECTOR:
NOTE: Terminal 6 of the RTS151KEYA is not used when wired to a 2-wire detector.
FIGURE 7. WIRING DIAGRAM FOR RTS151KEYA TO DH400ACDCA DUCT SMOKE DETECTOR:
DH400ACDCA
1
6
2
3
4
5
Alarm Signal
Aux. Power +
Sup. N. O.
Sup. COM
Aux. Power –
System Sensor warrants its enclosed product to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for the enclosed prod­uct. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obliga­tion of this Warranty shall be limited to the replacement of any part of the product which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization
Reset
Test
5
7
11
10
6
3
4
number, send defective units postage prepaid to: System Sensor, Returns Department,
D440-03-00 2 I56-3475-000 ©2009 System Sensor
RTS151KEYA
(Red LED) Alarm
* Sup. contacts cannot be used if they are wired to control panel.
(Green LED) Power
H0156-08
FIGURE 8. WIRING DIAGRAM FOR RTS151KEYA TO BEAM1224A/ BEAM1224SA SMOKE DETECTOR:
*
H0156-09
REMOTE ALARM OUT
REMOTE TROUBLE OUTPUT
NOTE: RTS151KEYA CAN BE USED WITH INTELLIGENT BEAM DETECTOR PRODUCTS. CONSULT INTELLIGENT BEAM DETECTOR MANUAL FOR ADDITIONAL INSTRUCTIONS
Three-Year Limited Warranty
RA #__________, 6581 Kitimat Road, Unit 6, Mississauga, Ontario L5N-3T5. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to replace units which are found to be defective because of dam­age, unreasonable use, modifications, or alterations occurring after the date of manufac­ture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
AUX (–)
RESET INPUT
TEST INPUT
T2-1
T2-2
T2-4
T3-3
OPTIONAL YELLOW LED
T2-3
RTS151KEYABEAM1224A/BEAM1224SA
(RED LED) ALARM
1
2
3
4
5
H0193-05
RESET
TEST
H0585-04