INSTALLATION AND MAINTENANCE INSTRUCTIONS
* Sup. contacts cannot be used if they are wired to control panel.
RTS151KEYA
6581 Kitimat Road, Unit 6, Mississauga, Ontario L5N-3T5
1-800-SENSOR2, FAX: 905-812-0771
Remote Test Station
www.systemsensor.ca
SPECIFICATIONS
Dimensions: 4.6˝ H × 2.75˝ W × 1.8˝ D
Weight: 0.24 Lbs.
Power Requirements
Power LED (Green): 14 – 35 VDC, 12 mA maximum
Alarm LED (Red): 2.8 – 32 VDC, 12 mA maximum
Alarm Response Time: 40 seconds maximum
Temperature: –10°C to 60°C (14°F to 140°F)
Humidity: 95% relative humidity, noncondensing Max
NOTE: RTS151KEYA replaces RTS451KEYA.
FIGURE 1. RTS151KEYA
NOTICE: This manual shall be left with the owner/user of this equipment.
NOTE: A test coil is required only for use with D2A,DNRA,DH400A,DH500A
models. For D2A models order part # DCOIL. For DH400A/500A models
order part #Coil.
GENERAL INFORMATION
The System Sensor RTS151KEYA is an automatic fire detector accessory
designed to test remotely located duct and beam detectors. For 4-wire detectors, the RTS151KEYA features a multi-colored LED that alternates between
OFF
RESET TEST
steady green and red. Green indicates power and that the detector board is
in place. Red indicates alarm. For 2-wire detectors, the LED will show red for
alarm. Consult the detector installation instructions for additional information.
The National Fire Protection Association and CAN/ULC-S536 has published
codes, standards, and recommended practices for the installation and use
of this product. It is recommended that the installer be familiar with these requirements, with local codes, and any special requirements of the local authority having jurisdiction.
RTS151KEYA CONTENTS
1 RTS151KEYA remote test station
1 screw pack (2 mounting screws)
2 Keys
OPERATION
Test Function
FIGURE 2: WIRING DIAGRAM FOR RTS151KEYA TO D4120A
4-WIRE DUCT SMOKE DETECTOR:
RTS151KEYA
FIELD
INSTALLED
JUMPER
2
4
D4120A
AUX OUT +
AUX OUT –
H0195-01
Insert the key and turn clockwise to the “TEST” position.
EXTERNAL
*
(-) POWER (+)
SUPPLY
ALARM
R TEST
R RESET
*
SUP, NO
SUP, C
4 5
321
RTS151KEYA
REMOTE TEST STATION
LED OPTION
1 PER UNIT
10mA CURRENT DRAW
TEST COIL OPTION
1 PER UNIT
95mA CURRENT DRAW
H0582-13
H0571-10
Alarm Indication
With the key in the “TEST” position, some time will elapse (40 seconds maximum) depending on the detector type, before the alarm indicating LED will
turn red.
Reset Function
Turn the key counterclockwise to the “RESET” position and hold. The LED
should turn off. Then, turn the key back to the “NORMAL” position and remove. The RTS151KEYA is capable of resetting only certain models of detectors. Refer to the detector installation instructions for additional information.
Wiring Instructions
Consult the appropriate detector installation instructions for the applicable
wiring diagram. The RTS151KEYA mounts to a single gang box (2 1/2˝ minimum depth), or directly to the wall or ceiling.
In Canadian applications, the RTS151KEYA is intended to be located in the
same room as the smoke detector and within 60 feet of the unit.
(RED LED)
ALARM
(GREEN LED)
POWER
1
5
3
6
FIGURE 3: WIRING DIAGRAM FOR RTS151KEYA TO D2A 2-WIRE
DUCT SMOKE DETECTOR:
TEST COIL +
TEST COIL –
COMM +
OUT (CONV ONLY) +
COMM –
RA/RTS –
RA +
RTS +
NOTE: THE RTS151KEYA TEST COIL
CIRCUIT REQUIRES AN EXTERNAL 24 VDC
POWER SUPPLY WHICH MUST BE UL LISTED.
NOTE: THE USE OF A REMOTE TEST STATION REQUIRES THE
INSTALLATION OF AN ACCESSORY COIL, PART NUMBER DCOIL,
SOLD SEPARATELY.
D440-03-00 1 I56-3475-000

FIGURE 4: WIRING DIAGRAM FOR RTS151KEYA TO DNRA 2-WIRE DUCT SMOKE DETECTOR:
1
2
3
4
5
6
3
4
5
Test +
Test / Reset –
Reset +
Test
Reset
RA +
RA –
V Out +
DH100
RTS151KEYA
6
2
1
Alarm
LED
No Connection
MAGNET
TEST
SWITCH
ALARM
LED (RED)
4
5
2
(–)
(+)
1
RTS151KEYA
(OPTIONAL) REMOTE
TEST STATION
+ TEST COIL
– TEST COIL
+ IN
+ OUT
–
– RA
+ RA
+ RTS
24 VDC
AUX POWER
(–)
SUPPLIED
BY USER
(+)
(100mA
SUPPLY)
24 VAC (+10%, –15%)
FULL WAVE RECTIFIED,
UNFILTERED POWER
MAY BE USED
DNRA
METHOD #1 - AUX POWER LOCATED
AT DUCT DETECTOR
NOTE: THE USE OF THE RTS151KEYA REQUIRES THE INSTALLATION OF
AN ACCESSORY COIL, DCOIL, SOLD SEPARATELY.
FIGURE 5. WIRING DIAGRAM FOR RTS151KEYA TO DH100ACDC
4-WIRE DUCT SMOKE DETECTOR:
DH100ACDCLPA
Alarm Signal
Aux. Power +
Sup. N. O.
Sup. COM
Aux. Power –
Reset
Test
15
19
14
3
20
2
11
RTS151KEYA
(Red LED) Alarm
1
* Sup. contacts
cannot
be used if they are
wired to control
panel.
(Green LED)
6
Power
2
3
4
5
*
24 VDC
AUX POWER
SUPPLIED
BY USER
(100mA
SUPPLY)
24 VAC (+10%, –15%)
FULL WAVE RECTIFIED,
UNFILTERED POWER
MAY BE USED
MAGNET
TEST
SWITCH
ALARM
LED (RED)
4
5
2
(–)
(+)
1
RTS151KEYA
(OPTIONAL) REMOTE
TEST STATION
+ TEST COIL
– TEST COIL
+ IN
+ OUT
–
– RA
+ RA
+ RTS
DNRA
METHOD #2 - AUX POWER LOCATED
AT TEST STATION
H0612-10
FIGURE 6. WIRING DIAGRAM FOR RTS151KEYA TO DH100 2-WIRE
DUCT SMOKE DETECTOR:
NOTE: Terminal 6 of the RTS151KEYA is not used when wired to a 2-wire detector.
FIGURE 7. WIRING DIAGRAM FOR RTS151KEYA TO DH400ACDCA
DUCT SMOKE DETECTOR:
DH400ACDCA
1
6
2
3
4
5
Alarm Signal
Aux. Power +
Sup. N. O.
Sup. COM
Aux. Power –
System Sensor warrants its enclosed product to be free from defects in materials and
workmanship under normal use and service for a period of three years from date of
manufacture. System Sensor makes no other express warranty for the enclosed product. No agent, representative, dealer, or employee of the Company has the authority to
increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the replacement of any part of the product which
is found to be defective in materials or workmanship under normal use and service
during the three year period commencing with the date of manufacture. After phoning
System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization
Reset
Test
5
7
11
10
6
3
4
number, send defective units postage prepaid to: System Sensor, Returns Department,
D440-03-00 2 I56-3475-000
©2009 System Sensor
RTS151KEYA
(Red LED) Alarm
* Sup. contacts
cannot be used if
they are wired to
control panel.
(Green LED)
Power
H0156-08
FIGURE 8. WIRING DIAGRAM FOR RTS151KEYA TO BEAM1224A/
BEAM1224SA SMOKE DETECTOR:
*
H0156-09
REMOTE ALARM OUT
REMOTE TROUBLE OUTPUT
NOTE: RTS151KEYA CAN BE USED WITH INTELLIGENT BEAM DETECTOR PRODUCTS.
CONSULT INTELLIGENT BEAM DETECTOR MANUAL FOR ADDITIONAL INSTRUCTIONS
Three-Year Limited Warranty
RA #__________, 6581 Kitimat Road, Unit 6, Mississauga, Ontario L5N-3T5. Please
include a note describing the malfunction and suspected cause of failure. The Company
shall not be obligated to replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages
for breach of this or any other Warranty, expressed or implied whatsoever, even if the
loss or damage is caused by the Company’s negligence or fault. Some states do not
allow the exclusion or limitation of incidental or consequential damages, so the above
limitation or exclusion may not apply to you. This Warranty gives you specific legal rights,
and you may also have other rights which vary from state to state.
AUX (–)
RESET INPUT
TEST INPUT
T2-1
T2-2
T2-4
T3-3
OPTIONAL YELLOW LED
T2-3
RTS151KEYABEAM1224A/BEAM1224SA
(RED LED) ALARM
1
2
3
4
5
H0193-05
RESET
TEST
H0585-04