INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-0758-015
RTS151KEY(A)
Remote Test Station
SpECIfICATIONS
Dimensions: 4.6˝ H × 2.75˝ W × 1.8˝ D
Weight: 0.24 Lbs.
Power Requirements
Power LED (Green): 14 – 35 VDC, 12 mA maximum
Alarm LED (Red): 2.8 – 32 VDC, 12 mA maximum
Alarm Response Time: 40 seconds maximum
Temperature: –10°C to 60°C (14°F to 140°F)
Humidity: 95% relative humidity, noncondensing Max
Listing: UL, FM, CE
NOTE: RTS151KEY(A) replaces RTS451KEY.
NOTICE: This manual shall be left with the owner/user of this equipment.
NOTE: A test coil is required only for use with D2/DNR/DH400/DH500 models. For D2 models order part # DCOIL. For DH400/500 models order part #Coil.
GENERAL INfORMATION
The System Sensor RTS151KEY(A) is an automatic fire detector accessory designed to test remotely located duct and beam detectors. For 4-wire detectors,
the RTS151KEY(A) features a multi-colored LED that alternates between steady
green and red. Green indicates power and that the detector board is in place.
Red indicates alarm. For 2-wire detectors, the LED will show red for alarm.
Consult the detector installation instructions for additional information.
The National Fire Protection Association has published codes, standards, and
recommended practices for the installation and use of this product. It is recommended that the installer be familiar with these requirements, with local
codes, and any special requirements of the local authority having jurisdiction.
RTS151 CONTENTS
1 RTS151KEY(A) remote test station
1 screw pack (2 mounting screws)
2 Keys
OpERATION
Test Function
Insert the key and turn clockwise to the “TEST” position.
Alarm Indication
With the key in the “TEST” position, some time will elapse (40 seconds maximum) depending on the detector type, before the alarm indicating LED will
turn red.
Reset Function
Turn the key counterclockwise to the “RESET” position and hold. The LED
should turn off. Then, turn the key back to the “NORMAL” position and remove. The RTS151KEY(A) is capable of resetting only certain models of detectors. Refer to the detector installation instructions for additional information.
Wiring Instructions
Consult the appropriate detector installation instructions for the applicable
wiring diagram. The RTS151KEY(A) mounts to a single gang box (2 1/2˝ minimum depth), or directly to the wall or ceiling.
In Canadian applications, the RTS151KEY(A) is intended to be located in the
same room as the smoke detector and within 60 feet of the unit.
fIGURE 1. RTS151KEY(A)
fIGURE 2: WIRING DIAGRAM fOR RTS151KEY(A) TO D4120 4-WIRE
DUCT SMOKE DETECTOR:
fIGURE 3: WIRING DIAGRAM fOR RTS151KEY(A) TO DNR 2-WIRE
DUCT SMOKE DETECTOR WITH REMOTE TEST CApABLE HEAD:
OUT (CONV ONLY) +
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
AUX OUT +
AUX OUT –
ALARM
R TEST
R RESET
D4120
*
14
3
RTS451KEY(A)
FIELD
INSTALLED
JUMPER
(RED LED)
(GREEN LED)
POWER
* Sup. contacts cannot be used if they are wired to control panel.
ALARM
2
4
1
5
3
6
19
20
15
11
2
TEST COIL +
TEST COIL –
COMM +
RTS451/RTS451KEY
RTS151/RTS151KEY
1
2
COMM –
RA/RTS –
RA +
3
4
H0195-01
SUP, NO
SUP, C
H0582-21
JUMPER
RTS +
5
H0633-00
D440-03-00 1 I56-0758-015
fIGURE 4: WIRING DIAGRAM fOR RTS151KEY(A) TO D2 2-WIRE DUCT SMOKE DETECTOR:
1
2
3
4
5
6
3
4
5
Test +
Test / Reset –
Reset +
Test
Reset
RA +
RA –
V Out +
DH100
RTS151KEY(A)
6
2
1
Alarm
LED
No Connection
AN ACCESSORY COIL, DCOIL, SOLD SEPARATELY.
MAGNET
TEST
SWITCH
ALARM
LED (RED)
4
5
2
(–)
(+)
1
RTS151KEY(A)
(OPTIONAL) REMOTE
TEST STATION
+ TEST COIL
– TEST COIL
+ IN
+ OUT
–
– RA
+ RA
+ RTS
24 VDC
AUX POWER
(–)
SUPPLIED
BY USER
(+)
(100mA
SUPPLY)
24 VAC (+10%, –15%)
FULL WAVE RECTIFIED,
UNFILTERED POWER
MAY BE USED
D2
METHOD #1 - AUX POWER LOCATED
AT DUCT DETECTOR
NOTE: THE USE OF THE RTS151KEY(A) REQUIRES THE INSTALLATION OF
fIGURE 5. WIRING DIAGRAM fOR RTS151KEY(A) TO DH100ACDC
4-WIRE DUCT SMOKE DETECTOR:
DH100ACDCLP
Alarm Signal
Aux. Power +
Sup. N. O.
Sup. COM
Aux. Power “
Reset
Test
15
19
14
3
20
2
11
RTS151KEY(A)
(Red LED) Alarm
1
* Sup. contacts cannot
be used if they are
wired to control panel.
(Green LED)
6
Power
2
3
4
5
*
24 VDC
AUX POWER
SUPPLIED
BY USER
(100mA
SUPPLY)
24 VAC (+10%, –15%)
FULL WAVE RECTIFIED,
UNFILTERED POWER
MAY BE USED
MAGNET
TEST
SWITCH
ALARM
LED (RED)
4
5
2
(–)
(+)
1
RTS151KEY(A)
(OPTIONAL) REMOTE
TEST STATION
+ TEST COIL
– TEST COIL
+ IN
+ OUT
–
– RA
+ RA
+ RTS
D2
METHOD #2 - AUX POWER LOCATED
AT TEST STATION
H0612-12
fIGURE 6. WIRING DIAGRAM fOR RTS151KEY(A) TO DH100 2-WIRE
DUCT SMOKE DETECTOR:
NOTE: Terminal 6 of the RTS151KEY(A) is not used when wired to a 2-wire detector.
H0156-08
fIGURE 7. WIRING DIAGRAM fOR RTS151KEY(A) TO DH400ACDC
DUCT SMOKE DETECTOR:
DH400ACDC
Alarm Signal
Aux. Power +
Sup. N. O.
Sup. COM
Aux. Power –
Reset
Test
5
7
11
10
6
3
4
RTS151KEY(A)
(Red LED) Alarm
1
* Sup. contacts
cannot be used if
they are wired to
control panel.
(Green LED)
6
Power
2
3
4
5
*
fIGURE 8. WIRING DIAGRAM fOR RTS151KEY(A) TO BEAM1224/
BEAM1224S SMOKE DETECTOR:
RTS151KEY(A)BEAM1224/BEAM1224S
AUX (–)
T2-1
T2-2
T2-4
T3-3
T2-3
OPTIONAL YELLOW LED
(RED LED) ALARM
1
2
3
4
5
RESET
TEST
REMOTE ALARM OUT
RESET INPUT
REMOTE TROUBLE OUTPUT
TEST INPUT
NOTE: RTS151KEY(A) CAN BE USED WITH INTELLIGENT BEAM DETECTOR PRODUCTS.
CONSULT INTELLIGENT BEAM DETECTOR MANUAL FOR ADDITIONAL INSTRUCTIONS
H0156-09
System Sensor warrants its enclosed product to be free from defects in materials and
workmanship under normal use and service for a period of three years from date of
manufacture. System Sensor makes no other express warranty for the enclosed product.
No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the replacement of any part of the product which
is found to be defective in materials or workmanship under normal use and service
during the three year period commencing with the date of manufacture. After phoning
System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization
number, send defective units postage prepaid to: System Sensor, Returns Department, RA
D440-03-00 2 I56-0758-015
©2011 System Sensor
THREE-YEAR LIMITED WARRANTY
#__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing
the malfunction and suspected cause of failure. The Company shall not be obligated to
replace units which are found to be defective because of damage, unreasonable use,
modifications, or alterations occurring after the date of manufacture. In no case shall the
Company be liable for any consequential or incidental damages for breach of this or any
other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by
the Company’s negligence or fault. Some states do not allow the exclusion or limitation of
incidental or consequential damages, so the above limitation or exclusion may not apply
to you. This Warranty gives you specific legal rights, and you may also have other rights
which vary from state to state.
H0193-05
H0585-05