System Sensor RTS151 User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-0469-014
RTS151 Remote Test Station
SPECIFICATIONS
Dimensions: 4.8˝ H × 2.90˝ W × 1.4˝ D Weight: .16 lbs.
Power Requirements
Alarm LED: 2.8 – 32 VDC, 10 mA max. Coil Current: 95 mA max. Test Switch: 10 VA @ 32 VDC Reset Switch: 10 VA @ 32 VDC Alarm Response Time: 40 sec. max. Temperature: –10°C to 60°C (14°F to 140°F) Humidity: 95% RH Non-condensing Max Listing: UL, FM, CE
NOTE: RTS151 replaces RTS451. NOTICE: This manual shall be left with the owner/user of this equipment. NOTE: A test coil is required only for use with D2/DNR/DH400/DH500 mod­els. For D2 models order part #DCoil. For the DH400/500 models order part is #Coil.
GENERAL INFORMATION
System Sensor’s RTS151 is an automatic fire detector accessory designed to test a remotely located detector. Consult detector installation instructions for additional information.
The National Fire Protection Association has published codes, standards, and recommended practices for the installation and use of the above product. It is recommended that the installer be familiar with these requirements, with local codes, and any special requirements of the local authority having jurisdiction.
RTS151 CONTENTS
1 RTS151 remote test station
1 screw pack (2 mounting screws)
1 M02-04 test magnet
WIRING OF RTS151
Consult the appropriate detector installation instructions for the applicable wiring diagram. The RTS151 mounts to a single gang box (2 1/2” minimum depth), or directly to the wall or ceiling.
See Figure 8 for wiring diagram of RTS151 with Duct Smoke Detectors.
In Canadian applications, the RTS151 is intended to be located in the same room as the smoke detector and within 60 feet of the unit.
OPERATION
Test Function
Place and hold the painted side of the magnet to the test location RTS151.
Alarm Indication
With the magnet in place some time will elapse (40 sec. maximum) depend­ing on the detector type, before the alarm indicating LED will light.
Reset Function
Gently insert a 1/8˝ maximum diameter tool into the hole until it stops and LED turns off. The RTS151 is capable of resetting only certain System Sensor models of detectors. Refer to detector installation instructions for additional information.
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
FIGURE 1. RTS151 REMOTE TEST STATION:
H0196-01
FIGURE 2. WIRING DIAGRAM FOR RTS151 TO D4120 4-WIRE DUCT SMOKE DETECTOR:
RTS151
FIELD INSTALLED JUMPER
(RED LED)
ALARM
AUX OUT +
19
2
4
1
5
3
20
15
11
2
AUX OUT –
ALARM
R TEST
R RESET
D4120
H0582-20
FIGURE 3. WIRING DIAGRAM FOR RTS151 TO DNR 2-WIRE DUCT SMOKE DETECTOR WITH REMOTE TEST CAPABLE HEAD:
TEST COIL +
TEST COIL –
COMM +
RTS451/RTS451KEY RTS151/RTS151KEY
1
OUT (CONV ONLY) +
COMM –
2
RA/RTS –
RA +
3
4
JUMPER
RTS +
5
H0633-00
D440-01-00 1 I56-0469-014
1
2
3
4
5
6
3
4
5
Test +
Test / Reset –
Reset +
Test
Reset
RA +
RA –
V Out +
DH100
RTS151
6
2
1
Alarm
LED
No Connection
AN ACCESSORY COIL, DCOIL, SOLD SEPARATELY.
FIGURE 4. WIRING DIAGRAM FOR RTS151 TO D2-2WIRE DUCT SMOKE DETECTOR:
MAGNET TEST SWITCH
ALARM LED (RED)
(OPTIONAL) REMOTE
4
5
2
(–)
(+)
1
RTS151
TEST STATION
+ TEST COIL
– TEST COIL
+ IN
+ OUT
– RA
+ RA
+ RTS
24 VDC
AUX POWER
(–)
SUPPLIED
BY USER
(+)
(100mA
SUPPLY)
24 VAC (+10%, –15%)
FULL WAVE RECTIFIED,
UNFILTERED POWER
MAY BE USED
D2
METHOD #1 - AUX POWER LOCATED
AT DUCT DETECTOR
NOTE: THE USE OF THE RTS151 REQUIRES THE INSTALLATION OF
FIGURE 5. WIRING DIAGRAM FOR RTS151 TO DH100ACDC 4-WIRE DUCT SMOKE DETECTOR:
DH100ACDC
Alarm Signal +
Aux. Power –
15
20
RTS151
(Red LED) Alarm
1
2
24 VDC
AUX POWER
SUPPLIED
BY USER
(100mA
SUPPLY)
24 VAC (+10%, –15%)
FULL WAVE RECTIFIED,
UNFILTERED POWER
MAY BE USED
RTS151
4
5
2
(–)
(+)
1
MAGNET TEST SWITCH
ALARM LED (RED)
(OPTIONAL) REMOTE
TEST STATION
+ TEST COIL
– TEST COIL
+ IN
+ OUT
– RA
+ RA
+ RTS
D2
METHOD #2 - AUX POWER LOCATED
AT TEST STATION
H0612-11
FIGURE 6. WIRING DIAGRAM FOR RTS151 TO DH100 2-WIRE DUCT SMOKE DETECTOR:
Reset
2
3
Reset
Field Installed
4
Jumper
Test
Test
11
5
H0197-01
FIGURE 7. WIRING DIAGRAM FOR RTS151 TO DH400ACDC DUCT SMOKE DETECTOR:
DH400ACDC
ALARM SIGNAL (+)
AUX POWER (–)
RESET (–)
TEST (–)
5
6
FIELD INSTALLED
3
JUMPER
4
RTS151
1
2
4
3
RESET
5
TEST
R E D
FIGURE 8. WIRING DIAGRAM FOR RTS151 TO BEAM1224/ BEAM1224S SMOKE DETECTOR:
RTS151BEAM1224/BEAM1224S
REMOTE ALARM OUT
AUX (–)
RESET INPUT
REMOTE TROUBLE OUTPUT
TEST INPUT
T2-1
1
T2-2
2
T2-4
3
T3-3
4
OPTIONAL YELLOW LED
T2-3
5
(RED LED) ALARM
1
2
3
4
5
RESET
TEST
H0149-02
Three-Year Limited Warranty
System Sensor warrants its enclosed product to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for the enclosed product. No agent, representative, dealer, or employee of the Company has the authority to in­crease or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the replacement of any part of the product which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Returns Department, RA
D440-01-00 2 I56-0469-014 ©2011 System Sensor
#__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.