INSTALLATION AND MAINTENANCE INSTRUCTIONS
ALARM
RESET
M02-04
TEST MAGNET
LOCATIONS
RTC100 Remote Test Coil Kit for use with the
Low Prole B114LP and B114LPBT Bases
Specications
Dimensions: 6.1″ diameter anged base
1.66″ high
RTS451 Power Requirements
Alarm LED: 2.8 – 32 VDC, 10 mA max.
Test Coil: 15.5 – 32 VDC, 95 mA max.
Total Current: 105 mA max.
Test Switch: 10 VA @ 32 VDC
Reset Switch: 10 VA @ 32 VDC
Alarm Response Time: 40 seconds max.
Operating Temperature Range: –10°C to 60°C (14°F to 140°F)
Humidity: 10 to 95% RH, noncondensing
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
NOTICE: This manual should be left with the owner/user
of this equipment.
General Description
The System Sensor Model RTC100 Remote Test Coil Kit allows for the remote testing of duct smoke detectors using
the B114LP (120 VAC) or B114LPBT (24 VAC/DC) bases
when installed in inconvenient or difcult-to-reach locations. Model RTC100 can be installed in almost any convenient location and can be attached to a standard 2″ × 4″
electrical box.
The National Fire Protection Association has published
standards and practices for the installation and use of this
device. As a result, System Sensor recommends that the
installer be familiar with these standards and practices,
local codes, and any special requirements of the authority
having jurisdiction.
RTC100 Contents
1 RTS451 Remote Test Station
1 Test Coil Replacement Ring
1 Screw Pack (2 mounting Assembly screws)
1 Jumper with spade lugs
1 M02-04 Test Magnet
Figure 1:
H0235-00
Installation
Installation of the Model RTC100 consists of attaching the
test station to the mounting surface, mounting the test coil
replacement ring on the detector, and routing the necessary
wiring between them. This installation procedure assumes
that the associated detector base is already installed and
ready for operation.
D140-01-00 1 I56-1493-01
A. Ring Replacement
1
B114LP/B114LPBT RTS451
2
3
4
5
1
2
3
4
5
REMOTE
ANNUNCIATOR (+)
TEST COIL (+)
RT
C (–)
RESET
ALARM
TEST
COIL
TEST
COIL
K1
RELAY
4-POSITION
TERMINAL
BLOCK
3-POSITION
TERMINAL
BLOCK
1. Remove the decorative ring from the B114LP/
B114LPBT base by rotating it in either direction to
release the hooks. Separate the ring from the base.
2. Position the Test Coil Replacement Ring Assembly on
the base, as shown in Figure 2. Be sure to position the
test coil directly over the 4-Position Terminal Block.
Otherwise, the coil may not activate the switch during
a test.
3. Route the the Test Coil Replacement Ring Assembly
wires through the slot in the base as indicated in
Figure 2.
4. Rotate the ring in either direction until it snaps in
place. Dress all wiring, as needed.
B. Wiring
1. Route four wires from the B114LP/B114LPBT to the
test station mounting location. Be sure to comply
with all applicable electrical codes when installing
this wiring. This includes selecting the proper wire
size and routing through conduit, if necessary.
2. Connect the wiring to the B114LP/B114LPBT Base and
RTS451 Test Station, as shown in Figure 3.
Figure 2. Ring Replacement:
H0199-01
C. Test Station Mounting
Attach the test station to a standard 2″ × 4″ electrical
box, using the screws supplied with the box.
Operation
Test
Position the painted side of the test magnet on the RTS451
Test Station on either the left or right side of the LED as
shown in Figure 1. The LED should light within 40 seconds,
indicating that the detector being is latched in alarm.
Reset
Reset the detector by inserting a narrow bladed pocket
screwdriver, or other similar tool, into the RESET hole
on the front of the test station. Gently press until the LED
turns off.
System Sensor warrants its enclosed smoke detector to be free from defects in materials and workmanship under normal use and service for a
period of three years from date of manufacture. System Sensor makes no
other express warranty for this smoke detector. No agent, representative,
dealer, or employee of the Company has the authority to increase or alter
the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the repair or replacement of any part
of the smoke detector which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll
free number 800-SENSOR2 (736-7672) for a Return Authorization number,
send defective units postage prepaid to: System Sensor, Returns Depart-
D140-01-00 2 I56-1493-01
© System Sensor 2003
Figure 3. RTC100 Wiring Diagram:
H0234-01
Three-Year Limited Warranty
ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please
include a note describing the malfunction and suspected cause of failure.
The Company shall not be obligated to repair or replace units which are
found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case
shall the Company be liable for any consequential or incidental damages
for breach of this or any other Warranty, expressed or implied whatsoever,
even if the loss or damage is caused by the Company’s negligence or fault.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to
you. This Warranty gives you specific legal rights, and you may also have
other rights which vary from state to state.