System Sensor PR-3 User Manual

YELLOW
BLUE
ORANGE
INSTALLATION INSTRUCTIONS
+
+
Non-Power Limited
Power Limited
Blue Wire
Yellow Wire
Orange Wire
Red Wire
Black Wire
I56-2192-005
PR-2/PR-3 Multi-Voltage Relay
Specifications
Operating Voltage: 10 to 40 VDC
Operating Current: 30 mA max.
Operating Temperature Range: –40ºF to 158ºF (–40ºC to 70ºC)
Storage Temperature Range: –40ºF to 185ºF (–40ºC to 85ºC)
Humidity: 10 to 93% RH non-condensing
Wire Length: 8 min. (203 mm)
Dimensions: 0.91H x 1.65W x 1.22D
(23 mm H x 42 mm W x 31 mm D)
Accessories: PR-2: 5 wire nuts
PR-3: 7 wire nuts
One piece of double sided tape
One 11/4 screw
Contact Ratings: 120 VAC 10A max. (resistive load)
120 VAC 7A max. (0.35 PF)
250 VAC 10A max. (resistive load)
30 VDC 10A max. (resistive load)
NOTICE: This manual should be left with the owner/user of this
equipment.
General Description
Model PR-2 and PR-3 are epoxy encapsulated single pull double throw
(SPDT) relays that are activated by 10 to 40 VDC. The PR-2 also uses a red
LED as a visible indication of relay coil energization. The PR-3 contains an
additional black and red wire used for redundant power input.
WIRE DEFINITIONS
RED POWER INPUT (+)
BLACK POWER INPUT (–)
BLUE RELAY - COMMON
YELLOW RELAY - NORMALLY CLOSED
ORANGE RELAY - NORMALLY OPEN
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Mounting
provided for additional support.
C0208-01
Wiring
NOTE: All wiring must conform to applicable local codes, ordinances,
and regulations.
The PR-2/PR-3 connections are shown on the label on the side of the relay.
Using the enclosed wire nuts, secure the electrical connections appropriate
to the application. Provisions must be taken to separate power limited
and non-power limited wiring per National Electrical Code requirements. Field installable wiring connected to the product must have a minimum
1/4 inch spacing between the power limited and non-power limited wire.
Three-Year Limited Warranty
System Sensor warrants its enclosed relay to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this relay. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the relay which is found to be defective in materials or workmanship under normal use and service dur­ing the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Repair Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note
D140-03-00 1 I56-2192-005
describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or inci­dental damages for breach of this or any other Warranty, expressed or implied what­soever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
C0898-00
2006 System Sensor
©
Loading...