INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-2600-02R
3825 Ohio Avenue, St. Charles, Illinois 60174
PF24 Directional Sounder
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Specifications
Mechanical
Input terminals: 12 – 24 AWG
Sounder size: 4 inches (101mm)
Grille Size: 4 7/8″ (127mm)
Electrical
Voltage Input: Regulated 24 Volts
Operation Voltage Range: 16 to 33 Volts
Operating Humidity Range: 10% to 93% relative humidity non-condensing
Frequency range: 20 Hz to 20 kHz
Operating Temperature range: 32° to 120°F (0° to 49°C)
Power:
1
/4″, 1/2″, 1, 2 and 4 Watts, selectable
Listings: UL 464 Directional Sounder, supplemental notification appliance
NOTICE: This manual should be left with the owner/user of the equipment.
General Description
Before installing, please read the Directional Sound
Applications Guide, available through System Sensor. The
installation must meet the requirements of the authority
having jurisdiction. Directional sounders are used as supplemental signals on a fire alarm system to aid in the evacuation of building occupants. Although directional sounders may be connected to notification appliance circuits
(NAC) for fire alarm service, they are not a replacement for
audible or visible notification appliances as required by the
Power Supply Considerations for
Directional Sounders
Panels typically supply DC filtered voltage or FWR (fullwave rectified) voltage. This device is only compatible
with DC filtered supplies and must not be used with panel
supplies that are FWR. Be certain the sum of all the device
currents do not exceed the current capability of the panel
power supply. Calculations are based on using the device
current found in Table 1 and must be the current specified
for the installed settings of the device.
authority having jurisdiction.
Wire Sizes
The directional sounder can be installed in systems using
24 Volt DC regulated power supplies only. It is not approved
for use with FWR unregulated power supplies.
The last device on the circuit must have sufficient voltage
to operate the device within its rated voltage range. When
calculating the voltage available to the last device, it is necessary to consider the voltage drop due to the resistance of
Directional sound is a broadband, multi-frequency sound.
The sound source is easily and quickly located by building
occupants, making it ideal for rapid building evacuation.
The Sounder incorporates four different pulse patterns.
The patterns consist of pulses of broadband noise. The four
the wire. The thicker the wire, the less the voltage drop.
Generally, for purposes of determining the wire size necessary for the system, it is best to consider all of the devices
as “lumped” on the end of the supply circuit (simulates
“worst case”).
patterns can be used to create an egress pathway out of a
building. The sound pattern becomes faster as the building
occupant approaches the perimeter exit. Three additional
tone pulses can be added to each of the four pulse patterns.
The first two tone pulses are used to alert occupants that
they are approaching a stairway and need to proceed either
Typical wire size resistance:
18 AWG solid: Approximately 8 ohms/1,000 ft.
16 AWG solid: Approximately 5 ohms/1,000 ft.
14 AWG solid: Approximately 3 ohms/1,000 ft.
12 AWG solid: Approximately 2 ohms/1,000 ft.
up or down. The second tone pulse is a special tone used
to identify areas of refuge.
Example: Assume you have 10 devices on a zone and each
requires 50mA average and 2000 ft. of 14 AWG wiring (total
length = outgoing + return). The voltage at the end of the
loop is 0.050 Amps per device
× 10 devices × 3 ohms/1000
ft. × 2000 ft. = 3 volts drop.
D550-10-00 1 I56-2600-02R
The same number of devices using 12 AWG wire will
produce only a 2 volt drop. The same number of devices
using 18 AWG wire will produce an 8 volt drop. Consult
your panel manufacturer’s specifications, as well as the
sounder’s operating voltage to determine the acceptable
voltage drop.
NOTE: If class “A” wiring is installed the wire length may
be up to 4 times the single wire length in this calculation.
Table 1: Current Draw Measurements and
Sound Output Guide
Maximum DC
Speed Selection
Switch
Selection
FAST (exit) 10 4 Watt 225 85 78
FAST (exit) 10 2 Watt 114 82 76
FAST (exit) 10 1 Watt 75 79 73
FAST (exit) 10
FAST (exit) 10
MED1 9 4 Watt 221 85 77
MED1 9 2 Watt 112 82 74
MED1 9 1 Watt 74 79 71
MED1 9
MED1 9
MED2 8 4 Watt 203 85 78
MED2 8 2 Watt 103 82 75
MED2 8 1 Watt 68 79 73
MED2 8
MED2 8
SLOW 7 4 Watt 189 85 76
SLOW 7 2 Watt 96 82 73
SLOW 7 1 Watt 63 79 70
SLOW 7
SLOW 7
Power
Setting
1
/2 Watt 62 76 69
1
/4 Watt 49 73 66
1
/2 Watt 61 76 68
1
/4 Watt 48 73 65
1
/2 Watt 56 76 69
1
/4 Watt 44 73 66
1
/2 Watt 52 76 67
1
/4 Watt 41 73 64
Operating
Current
(mA RMS)
(16 to 33V)
Audibility
(dBA)
(16 to
33V)
Note 1
Audibility
(dBA)
(16 to
33V)
Note 2Speed
NOTE 1: Sound output measured in anechoic room at 10 feet.
NOTE 2: Sound output measured in a reverberant room at 10 feet.
more than one switch is selected the sounder will default
to the fastest selected setting.
Switch positions 5 and 6 are used to select additional
tone pulses that can be inserted in between bursts of the
directional sound pulses. The additional tone pulse will
be inserted on every 6th directional sound pulse. These
switches should be used when the sounder will be placed
near a stairway to guide a building occupant up or down
the stairs. Switch setting 5 inserts a down sweep indicat
ing the presence of a downward stairway. Switch setting 6
inserts an up sweep indicating the presence of an upward
stairway. If switch positions 5 and 6 are both set to “on”
this will insert a special tone for use near areas of refuge.
The area of refuge tone should be used if the directional
sounder is marking an area of refuge. This tone provides
a distinct signal indicating that the sounder is not marking an exit. If both switches are set to “off” the sounder
will default to no additional tones. In this case only the
directional sound pulses will be heard. See Table 2 for tone
selection options.
Table 2: Additional Tone Selection Guide
Switch
Position 5
Setting
on on Refuge
on off DOWN Stairs
off on UP Stairs
off off no tones
Switch
Position 6
Setting
Sound Output
Switch setting 4 enables a directional sound device to
become disabled when used in conjunction with devices
with dry contacts such as heat sensors or control modules.
The sounder has a set of input terminals that can be configured for an “active open” or “active closed” state. When
the switch is in the “on” position, the sounder is “on”
when the disable connection is closed. When the switch is
in the “off” position, the sounder is “on” when the disable
connection is open. See Table 3 for operation modes.
-
Installation
Consult the Directional Sound Applications Guide for
information regarding the appropriate mounting locations
of directional sounders.
Switch Settings
Selections are made via DIP switches on the back of
Table 3: Enable/Disable Function Logic Table
Switch
Position 4
Setting
on open disabled
on closed enabled
off open enabled
off closed disabled
Terminals 3
& 4
Sound
Output
the sounder. Switch positions 7-10 are used to select the
pulse pattern of the sounder. Switch 10 is used to mark
the perimeter exit locations (fastest pulse). The remaining
settings are used for egress routing to the perimeter exit.
The egress route would originate with the “slow” (switch
7) tone and follow “medium 2” (switch 8) to “medium 1”
(switch 9) and finally the exit point “fast” (switch 10). If
D550-10-00 2 I56-2600-02R
There are five different power settings for the sound output
pressure. Switch settings 1, 2, and 3 set the power setting
for the sounder. Switch 1 selects the 2 watt setting, switch 2
selects the 1 watt setting, switch 3 selects the 1/2 watt setting.
If all three switches are “off” this selects the 4 watt setting and
if all three switches are “on” this selects the 1/4 watt setting.