System Sensor
3825 Ohio Avenue
St. Charles, IL 60174
1-800-SENSOR2
Fax: 630-377-6495
PDRP1002.CD
The PDRP-1002/PDRP-1002E
Agent Release Control System
Manual
Document 51135
I56-1358-00
03/11/99Revision:
PN 51135:AECN 99-017
A
Installation Precautions
g
d
u
n
s
e
t
d
s
o
I
o
n
o
b
o
s
– Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING
fire alarm control panel. Disconnect all sources of power before
servicing. Control unit and associated equipment may be damaged by
removing and/or inserting cards, modules, or interconnecting cables
while the unit is energized. Do not attempt to install, service, or operate
this unit until this manual is read and understood.
CAUTION
ensure proper system operation, this product must be tested in
accordance with NFPA 72-1993 Chapter 7 after any programming
operation or change in site-specific software. Reacceptance testing is
required after any change, addition or deletion of system components, or
after any modification, repair or adjustment to system hardware or
wiring.
All components, circuits, system operations or software functions known
to be affected by a change must be 100% tested. In addition, to ensure
that other operations are not inadvertently affected, at least 10% of
initiating devices that are not directly affected by the change, up to a
maximum of 50 devices must also be tested and proper system
operation verified.
This system
32-120
30
and the electronic components may be adversely affected by extreme
temperature ranges and humidity. Therefore, it is recommended that this
system and its peripherals be installed in an environment with a nominal
room temperature of 15-27
Verify that wire sizes are adequate
devices cannot tolerate more than a 10% I.R. drop from the specified
device voltage.
- Sever al different sources of power can be connected to the
- System Reacceptance Test after Software Changes: To
O
meets NFPA requirements for operation at 0-49
O
F and at a relative humidity of 85% RH (non-condensing) at
O
C/86O F. However, the useful life of the system's standby batteries
O
C/60-80O F.
for all initiating device loops. Most
C/
Fire Alarm System Limitati on s
An automatic fire alarm system
detectors, heat detectors, manual pull stations, audible warning devices
and a fire alarm control with remote notification capability can provide
early warning of a developing fire. Such a system, howev er, does not
assure protection against property damage or loss of life resulting from a
fire.
Any fire alarm system may fail for a variety of reasons:
Smoke detectors
detectors such as in chimneys, in walls, or roofs, or on the other side of
closed doors. Smoke detectors also may not sense a fire on another
level or floor of a building. A second floor detector , for example, may not
sense a first floor or basement fire. Furthermore, all types of smoke
detectors - both ionization and photoelectric types, have sensing
limitations. No type of smoke detector can sense every kind of fire
caused by carelessness and safety hazards like smoking in bed, violent
explosions, escaping gas, improper storage of flammable materials,
overloaded electrical circuits, children playing with matches, or arson.
IMPORTANT!
the control panel and in rooms used by the system for the connection of
alarm transmission wiring, communications, signaling and /or power. If
detectors are not so located, a developing fire may damage the alarm
system, crippling its ability to report a fire.
may not sense fire where smoke cannot reach the
Smoke detectors must be installed in the same room as
- typically made up of smoke
FCC Warning
Like all solid state electronic devices
erratically or can be damaged when subjected to lightning induced
transients. Although no system is completely immune from lightnin
transients and interferences, proper grounding will reduce
susceptibility. Overhead or outside aerial wiring is not recommendedue to an increased susceptibility to nearby lightning strikes. Cons
with the Technical Services Department if any problems are
anticipated or encountered.
Disconnect AC power and batteries
circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies
or punching of the enclosure. When possible, make all cable entrie
from the sides or rear. Before making modifications, verify that they
will not interfere with battery, transformer and printed circuit board
location.
Do not tighten screw terminals
may damage threads, resulting in reduced terminal contact pressur
and difficulty with screw terminal removal.
This system
yourself with a proper wrist strap before handling any circuits so tha
static charges are removed from the body. Use static suppressive
packaging to protect electronic assemblies removed from the unit.
Follow the instructions
programming manuals. These instructions must be followed to avoi
damage to the control panel and associated equipment. FACP
operation and reliability depend upon proper installation.
While installing a fire alarm system may make lower insurance
rates possible, it is not a substitute for fire insurance!
Audible warning devices
devices are located on the other side of closed or partly open doors
are located on another floor of a building.
A fire alarm system will
AC power f ails, the system will operate from standby batteries only f
a specified time.
Rate-of-Rise heat detectors
over time. For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire protection
specialist.
Equipment used in the system
with the control panel. It is essential to use only equipment listed fo
service with your control panel.
T
elephone lines
central monitoring station may be out of service or temporarily
disabled.
The most common cause
inadequate maintenance. All devices and system wiring should be
tested and maintained by professional fire alarm installers following
written procedures supplied with each device. System inspection a
testing should be scheduled monthly or as required by National and/
local fire codes. Adequate written records of all inspections should
kept.
needed to transmit alarm signals from a premise to
of fire alarm malfunctions, however, is
, this system may operate
prior to removing or inserting
prior to any drilling, filing, reami
more than 9 in-lbs. Over tightenin
may not be technically compatible
WARNING:
frequency energy and if not installed and used in accordance with the
instruction manual, may cause interference to radio communications, It
has been tested and found to comply with the limits for class A
computing device pursuant to Subpart B of 15 of FCC Rules, which is
designed to provide reasonable protection against such interference
when operated in a commercial environment. Operation of this
equipment in a residential area is likely to cause interference, in which
case the user will be required to correct the interference at his own
expense.
This equipment generates, uses and can radiate radio
2The PDRP-1002 PN 51135:A 03/11 / 99
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiati
noise emissions from digital apparatus set out in the Radio
Interference Regulations of the Canadian Department of
Communications.
Le present appareil numerique n'emet pas de bruits radioelectrique
depassant les limites applicables aux appareils numeriques de la
classe A prescrites dans le Reglement sur le brouillage
radioelectrique edicte par le ministere des Communications du
Canada.
The PDRP-1002 PN 51135: A 03/11/993
4The PDRP-1002 PN 51135:A 03/11 / 99
NFPA Standards
This control panel complies with the following NFPA standards:
NFPA 12 CO
NFPA 12A Halon 1301 Extinguishing Systems
NFPA 12B Halon 1211 Extinguishing Systems
NFPA 72 Central Statio n Signaling Systems (Automatic, M a nual, and Waterflow). Protected
Premises Unit (Requires NOTI•FIRE 911AC DACT or MS-5012 Slave Communicat or)*
NFPA 72 Local (Automatic, Manual, Waterflow and Sprinkler Supervisory) Fire Alarm Systems
NFPA 72 Auxiliary (Automatic, Manual, and Waterflow) Fire Alarm Systems. (Requires 4XTM)
NFPA 72 Remote Station (Automatic, Manual, and Waterflow) Fire Alarm Systems. Requires
4XTM, NOTI•FIRE 911AC DACT*
NFPA 2001 Clean Agent Fire Extinguish in g Sys te m s
*Applications which require the NOTI•FIRE 911AC are not FM approved.
Additional Information
Before proceeding, the installer should be familiar with the following documents and
standards:
NFPA Standards:
NFPA 12 CO2 Fire Extinguishing Systems
NFPA 12A Halon 1301 Fire Ext inguishing Systems
NFPA 12B Halon 1211 Fire Extinguishing Systems
NFPA 72 Installation, Maintenance and Use of Central Station Signaling Systems
NFPA 72 Local, Auxiliary, Remote Station and Proprietary Fire Alarm Systems
NFPA 72 Automatic Fire Detectors
NFPA 72 Installation, Maintenance and Use of Notification Appliances for Fire Alarm Systems
NFPA 72 Testing Procedures for Signaling Systems
NFPA 2001 Clean Agent Fire Extinguish in g Sys te m s
Extinguishing Systems (High Pressure Only)
2
Underwriters Laboratories Documents:
UL 38 Manual Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers - Holders for Fire Alarm Systems
UL 268 Smoke Detectors for Fire Alarm Systems
UL 268A Smoke De te c t o r s for D uc t Ap plications
UL 346 Waterflow Indicators for Fire Alarm systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Alarm Systems
UL 864 Standard for Control Units for Fire Alarm Systems
UL 1481 Power Supplies for Fire Alarm Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for the Hearing Impaired
CAN/ULC-S524-M91 Standard for Installation of Fire Alarm Systems
CAN/ULC-S527-M87 Standard for Control Units for Fire Alarm Systems
Other:
NEC Article 300 Wiring Methods
NEC Article 760 Fire Alarm Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction
Notifier Device Compatibility Document, 15378
ADA Americans with Disabilities Act
The PDRP-1002 PN 51135: A 03/11/995
1 The PDRP-1002/PDRP-1002E
1 The PDRP-1002/PDRP-1002E
Features
•Microprocessor-controlled
•Power-limited on all circuits except Municipal Box output
•Alarm and trouble resound
•Four Class A (Style D)/Class B (Style B) Initiating Device Circuits
•Two Class A (Style Z)/Class B (Style Y) Notification Appliance circuits
•Two Class B (Style Y) Release Circuits
•General alarm and trouble relays
•Optional module for 4 zone/function relays (4XZM)
•Optional transmitter module (4XTM). Complies with NFPA 72 Auxiliary and
Remote Station Fire Alarm systems
•Optional volt/amp meter module (4XMM)
•Optional supervised remote annunciator (RZA-4X)
•Requires LED Interface Module (4XLM)
•Optional digital communicator (NOTI•FIRE 911AC)*
•Complies with NFPA 72 Central Station and Remote Station Fire Alarm Systems
•Supervisory Input Option
•Delay timer (adjustable)
•Three abort function options
•Designed for suppression standards NFPA 12, 12A and 12B
•Disable/enable controls per initiating zone
•Last Event Recall
•Battery/Earth fault supervision
•Fuse protection on all Notification/Release Circuits
•RMS regulated output power, 2.25 amps
•7 amp/hour to 15 amp/hour battery options, up to 90 hours standby
•Resettable and non-resettable regulated power outputs
•Extensive transient protection
•Watchdog timer to supervise microprocessor
•Output circuits protected against false activations
•Slide-in zone identification labels
•Steel cabinet 14.5 in (368.3 mm) wid e b y 16 i n ( 406. 4 mm) high b y 5 in (127 m m)
deep
•Dead-front dress panel option (DP-4X)
•Trim ring for flush mount between 16 in (406.4 mm) center studs (TR-4XR)
•Abort and manual release circuits
•Cross-zone option
Input Circuits
Applications which require the NOTI•FIRE 911AC are not FM approved
*
.
Circuits
Input Circuits
Detector Zone 1, Class A (Style D)/Class B (Style B)
Detector Zone 2, Class A (Style D)/Class B (Style B)
Abort, Class A (Style D)/Class B (Style B)
Manual Release, Class A (Style D)/Class B (Style B)
Output circuits (optional auxiliary relays track these four circuits)
Notification Appliance Circuit 1, Class A(Style Z)/Class B (Style Y)
Notification appliance Circuit 2, Class A(Style Z)/Class B (Style Y)
Releasing Circuit 1, Class B (Style Y)
Releasing Circuit 2, Class B (Style Y)/Supervis ory Input, Class B (Style B)
*Jumper “OPT 1” must
be cut if a module is
installed in this position
OPT 1
*
4XTM
or
4XLM
or
4XZM
*Jumper “OPT 2” must
be cut if a module is
installed in this position
O
123456
Cross Zone
Supervisory
Delay Timer
N
SW1
Abort Option
Abort Option
Delay Timer
Micro Fail LED
BATT
EARTH
Ground Fault LEDBattery Fail LED
Figure 1 PDRP-1002/P DRP-1002E Installatio n Di agram
The PDRP-1002 PN 51135: A 03/11/997
OPT 2
*
4XRP1002.cdr
1 The PDRP-1002/PDRP-1002E
4XTM.cdr
4XLM.cdr
Optional Boards
The PDRP-1002/PDRP-1002E has mounting slots for two option boards. Any two of
the three option modules may be installed.
Transmitter Module (4XTM - NOTIFIER)
The Transmitter Module provides a supervised output for
local energy municipal box transmitter (for NFPA 72
Auxiliary Fire Alarm System) and alarm and trouble
reverse polarity circuits (for NFPA 72 Remote Statio n Fi re
Alarm System). Also included is a DISABLE switch and
disable trouble LED.
As a jumper option, the alarm reverse polarity circuit will
open on trouble if no alarm exists.
LED Interface Module (4XLM - NOTIFIER)
The LED Interface Module supports the RZA-4X Remote
Annunciator module. Annu nciator wi ring is superv ised for
open conditions by this module. The Annunciator Driver
Module mounts to the main board, occupying on e of the
two option connectors.
Transmitter Module (4XTM - NOTIFIER)
Zone Relay Module (4XZM - NOTIFIER)
The Zone Relay module provides Form-C contacts for the
following:
As a jumper option, the first four relays described below can
be made silenceable.
DIP 1=OFF
Either Zone
Alarm Detected First AlarmAlarm Detected First Alarm
Alarm Detected Second Alarm Alarm Detected Second Alarm
Release 1Release 1ReleaseRelease
Release 2Release 2Not UsedNot Used
8The PDRP-1002 PN 51135:A 03/11 / 99
DIP 1=ON
Cross Zone
If Supervisory (DIP 2=ON)
Either ZoneCross Zone
4XZM.cdr
Transmitter Module (4XTM - NOTIFIER)
RZA4Xfr.cdr
voltmter.cdr
Transmitter Module (4XTM - NOTIFIER)
For Local Energy Municipal Box service (NFPA 72 Auxiliary Fire Alarm System)
Supervisory current: 5.0 mA
Trip current: 0.35 amps. (Subtracted from Notification Appliance power)
Coil Voltage: 3.65 VDC
Coil resistance: 14.6 ohms
Maximum allowable wire resistance between panel and trip coil: 3 ohms
Municipal Box wiring can leave the building
For Remote Station service (NFPA 72 Remote Station Fire Alarm
System):
Maximum load for each circuit: 10mA
Reverse polarity output voltage: 24 VDC
Remote Alarm and Remote Trouble wiring can leave the b uilding
The Remote Annunciator mounts on a standard singlegang box, and provides LED indication of the same
functions as the zone relay module. For example with
DIP 1=ON and DIP 2=OFF:
•One Zone in Alarm (red)
•Two Zones in Alarm (red)
•Releasing Circuit 1 (red)
•Releasing Circuit 2 (red)
•System Trouble (yellow)
A Local Trouble Sounder and Silence Switch are also
provided. All LED wiring is supervised for open
conditions. Any open condition will cause the System
Trouble LED to illuminate.
Note: The Remote Annunc iator requir es the use of an LED Interface m od ule (4XLM).
Voltage, Current Meters (4XMM - NOTIFIER)
The Meter Module provides a voltmeter to measure the
voltage across the batteries and an ammeter to measure
the charging current to the batteries. The meters are
provided as an assembly that mounts to the lower lefthand corner of the cabinet.
20
10
DC VOLTS
0
30
5
0
5
DC AMPERES
The PDRP-1002 PN 51135: A 03/11/999
1 The PDRP-1002/PDRP-1002E
AC Circuit
Breaker
Acctbrkr.cdr
Specifications
AC Power
For the PDRP-1002: 120 VAC, 50/60 Hz, 1.2 amps
For the PDRP-1002E: 220/240 VAC, 50 Hz, 0.6 amps
Wire size: minimu m #14 AWG with 600V insulation
Battery (lead acid only)
Maximum Charging Circuit: 27.6V, 1.5 amps
Maximum Battery Capacity: 15 AH. (Batteries larger
than 12 AH require NOTIFIER #BB-17 or other UL
listed external battery cabinet.)
Initiating Device Circuits
Power-limited circuitry
Operation: Class A (Style D)/Class B (Style B)
Normal Operating Voltage: 24 VDC (ripple = 1.0V peak-to-peak)
Alarm current: 15 mA minimum
Short circuit current: 40 mA maximum
Maximum detector current in standby: 2 mA (max) per zone
Maximum loop resistance: 200 ohms
End-of-line resistor: 4.7K, 1/2-Watt (NOTIFIER part # 71252, UL listed)
Detector loop current is sufficient to ensure operation of one alarmed detector per zone.
Supervisory current: 5 mA (including end-of-line resistor)
AC Power
Notification Appliance and Releasing Circuits
Power-limited circuitry
Maximum allowable voltage drop due to wiring: 2 VDC
Normal Operating Voltage: 24 VDC
Total current available to all external devices: 2.25 amps
Maximum signaling current per circuit: 1.5 amps
End-of-line resistor: 4.7K, 1/2-Watt (NOTIFIER part # 71252, UL listed)
Alarm and Trouble Relays
Dry Form-C contacts rated: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC
(resistive). All relays must be connected to a power limited power supply.
Four-wire Smoke Detector Power
Up to 200 mA is available for powering 4-wire smoke detectors.
Maximum ripple voltage: 1.0 V p/p
Non-resettable Power
Total DC current available from this output is up to 200 mA (subtracted from 4-wire
smoke power).
Maximum ripple voltage: 1.0 V p/p
RMS Regulated Power
Total DC current available for powering external devices is 0.5 amp (subtracted from
2.25 amps available to notification appliance circuits).
Maximum ripple voltage: 100 mV p/p
Note: For device compatibility, refer to Device Compatibility Chart.
10The PDRP-1002 PN 51135:A 03/11 / 99
RMS Regulated Power
Door = 16.125 in.
(409.58 mm)
Backbox = 16 in.
(406.4 mm)
Door = 14.625 in.
(371.48 mm)
Backbox = 14.5 in.
(368.3 mm)
1 The PDRP-1002/PDRP-1002E
Cabinet = 5.375 in.
(136.53 mm)
Backbox = 4.750 in.
(120.65 mm)
TR-4XR
RUBY RD
STEEL
16 GA.
14.594 in.
(370.69 mm)
Optional Trim Ring
TR-4XR
Figure 2 Cabinet Dimensions
1.5 in
(38.1 mm)
16.094 in.
(408.79 mm)
RPCABDIM.cdr
The PDRP-1002 PN 51135: A 03/11/9911
2 System Operation
2 System Operation
WARNING:When used for CO2 releasing applications, observe proper
precautions as stated in NFPA 12. Do not enter the protected space unless physical
!
lockout and other safety procedures are fully completed. Do not use software
disable functions in the panel as lockout.
System Status LEDs
Alarm, Trouble and Supe rvisory LEDs will flash on and off until the event(s) has been
acknowledged (TONE or ALARM SILENCE), at which point the LED will illuminate
steadily.
AC POWER
Green LED that illuminates steadily to
indicate presence of AC power.
SYSTEM ALARM
Red LED that flashes when an alarm
occurs.
RELEASE
Red LED that illuminates steadily when
release occurs.
RMS Regulated Power
SUPERVISOR Y
Yellow LED that flashes upon activation of
a supervisory device (such as tamper
switch) on Output 4 if selected (see
“Setting Mode of Operation” in Section 3
of this manual).
SYSTEM TROUBLE
BATT
EARTH
MICRO
FAIL
Yellow LED that flashes for any trouble
condition, including those associated with option boards.
CIRCUIT TROUBLE
Yellow LED that flashes for trouble conditions on output circuits (notification and
releasing circuits).
ALARM SILENCED
Yellow LED that illuminates steadily when the ALARM SILENCE switch has been
pushed after an alarm.
POW ER TROUBLE
Yellow LED that flashes for low or disconnected batteries and earth fault conditions.
BA TT
Yellow LED that illuminates steadily on mother boar d when battery is low or not
detected (not visible through door).
EARTH
Yellow LED that illuminates steadily on mother boar d during a ground fault condition
(not visible through door)
4Xoper2.cdr
MICRO FAIL
Yellow LED that illuminates on motherboard when watchdog timer de tects
microprocessor failure (no t visi b le throu gh doo r)
12The PDRP-1002 PN 51135:A 03/11 / 99
RMS Regulated Power
Control Switches
2 System Operation
Tone Silence
Acknowledge alarms, troubles and
supervisories. The panel has alarm and
trouble resound with LED flash of new
conditions. The flashing trouble LED(s)
illuminate steadily on TONE SILENCE and
the piezo sounder silences. A second trouble
will resound the piezo. The piezo has three
sounds for alarm, trouble, and supervisory.
Trouble cond i tio ns are self- res to ring . Alar ms
latch and require RESET to clear.
Alarm Silence
Acknowledge for alarms and supervisories.
The ALARM SILENCE switch will silence
the local piezo, change any flashing alarm
LEDs to steady, and turn off the notification
circuits (not the releasing circuits). The
“ALARM SILENCED” LED will illuminate.
Alarm silence is a latching function and
requires a RESET to clear.
Alarm Activate
The ALARM A CTIVATE switch may be used
to activate Notification Appliance Circuits.
ALARM ACTIVATE also activates the
System Alarm relay. ALARM Activate is a
latching function. Pressing ALARM
SILENCE silences the notification circuits
and System Alarm Relay and lights the Alarm
Silenced LED. Pressing RESET returns the
system to normal.
System Reset
The RESET switch breaks power to all
initiating circuits, 4-wire smoke power and
option boards and will clear any activated
output circuits. If any alarms or troubles still
exist after reset, they will reacti vate th e panel.
Holding RESET down will perform a LAMP
TEST function and will activate the piezo sounder.
4XPTL.cdr
Zone Status LEDs
The alarm and/or trouble LED(s)
will flash until the event(s) has
been acknowledged (TONE or
ALARM SILENCE), at which
point the LED(s) will illuminate
steadily.
ABORT TROUBLE LED
MANUAL RELEASE TROUBLE LED
The PDRP-1002 PN 51135: A 03/11/9913
ALARM LED
TROUBLE LE D
ALARM LED
TROUBLE LE D
ABORT LED
MANUAL RELEASE
Zone 1
Zone 2
Abort
Manual
Release
2 System Operation
Supervisory
Zone Disable
RMS Regulated Power
Output circuit #4 is used as an input for monitoring supervisory devices such as valve
tamper switches (note that SW1 DIP switch #2 must be set “ON” -- see section “Setting
Mode of Operation”) By setting Switch short circuit on this input (activation of a N.O.
contact) will cause the supervisory LED to flash. The piezo sounder will generate a
unique sound. TONE SILENCE will silence the piezo and cause the LED to illuminate
steadily. Supervisory signals latch and require RESET to clear . An open circuit will be
reported as a circuit trouble.
If a zone has been disabled, an alarm
that occurs on that zone will flash the
red zone LED, but not the p iez o or any
output circuit.
If both power sources
are removed from the system, all zones
will be re-enabled upon restoration of
power. Disable status will be lost .
The Zone Disable routine m akes use of
the four panel switches as follows:
1.Press and hold in the TONE
SILENCE switch.
Last Event Recall
2.With the TONE SILENCE switch
held in, press (in sequence) the
ALARM SILENCE switch, the
ALARM ACTIVATE switch, and
then the RESET switch.
3.The Zone 1 Alarm LED will flash.
4.To disable Zone 1, press the RESET switch. The Zone 1 yellow LED will light to
show that the zone is disabled.
Note: The RESET switch toggles disable status for the selected zone.
5.To select the next zone, press the ALARM SILENCE switch.
6.To select the previous zone, press the ALARM ACTIVATE switch.
7.When disable selections are complete, release the TONE SILENCE switch.
If any zone has been disabled, the trouble relay will activate and System Trouble LED
will flash.
Last Event Recall allows the user to display the previous panel status. The last event
recall uses the four panel switches as follows:
1.Press and hold in the TONE SILENCE switch.
4XPTL.cdr
2.With the TONE SILENCE switch held in, press (in sequence) the RESET switch,
the ALARM ACTIVATE switch, and then the ALARM SILENCE switch.
3.Last Event is displayed.
4.Release the TONE SILENCE switch to return to normal operation.
Note: To clear the last event buffer, press RESET twice.
14The PDRP-1002 PN 51135:A 03/11 / 99
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.