System Sensor PDRP-1002 User Manual

System Sensor 3825 Ohio Avenue St. Charles, IL 60174 1-800-SENSOR2 Fax: 630-377-6495
The PDRP-1002/PDRP-1002E Agent Release Control System
Manual
Document 51135
I56-1358-00
03/11/99 Revision:
PN 51135:A ECN 99-017
A
Installation Precautions
g
d
u
n
s
e
t
d
s
o
I o
n
o
b
o
s
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING
fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION
ensure proper system operation, this product must be tested in accordance with NFPA 72-1993 Chapter 7 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices must also be tested and proper system operation verified.
This system
32-120 30
and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a nominal
room temperature of 15-27
Verify that wire sizes are adequate
devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
- Sever al different sources of power can be connected to the
- System Reacceptance Test after Software Changes: To
O
meets NFPA requirements for operation at 0-49
O
F and at a relative humidity of 85% RH (non-condensing) at
O
C/86O F. However, the useful life of the system's standby batteries
O
C/60-80O F.
for all initiating device loops. Most
C/
Fire Alarm System Limitati on s
An automatic fire alarm system
detectors, heat detectors, manual pull stations, audible warning devices and a fire alarm control with remote notification capability can provide early warning of a developing fire. Such a system, howev er, does not assure protection against property damage or loss of life resulting from a fire.
Any fire alarm system may fail for a variety of reasons: Smoke detectors
detectors such as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second floor detector , for example, may not sense a first floor or basement fire. Furthermore, all types of smoke detectors - both ionization and photoelectric types, have sensing limitations. No type of smoke detector can sense every kind of fire caused by carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with matches, or arson.
IMPORTANT!
the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling and /or power. If
detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire.
may not sense fire where smoke cannot reach the
Smoke detectors must be installed in the same room as
- typically made up of smoke
FCC Warning
Like all solid state electronic devices
erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightnin transients and interferences, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommende due to an increased susceptibility to nearby lightning strikes. Cons with the Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries
circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies
or punching of the enclosure. When possible, make all cable entrie from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer and printed circuit board location.
Do not tighten screw terminals
may damage threads, resulting in reduced terminal contact pressur and difficulty with screw terminal removal.
This system
yourself with a proper wrist strap before handling any circuits so tha static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions
programming manuals. These instructions must be followed to avoi damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.
While installing a fire alarm system may make lower insurance rates possible, it is not a substitute for fire insurance!
Audible warning devices
devices are located on the other side of closed or partly open doors are located on another floor of a building.
A fire alarm system will
AC power f ails, the system will operate from standby batteries only f a specified time.
Rate-of-Rise heat detectors
over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist.
Equipment used in the system
with the control panel. It is essential to use only equipment listed fo service with your control panel.
T
elephone lines
central monitoring station may be out of service or temporarily disabled.
The most common cause
inadequate maintenance. All devices and system wiring should be tested and maintained by professional fire alarm installers following written procedures supplied with each device. System inspection a testing should be scheduled monthly or as required by National and/ local fire codes. Adequate written records of all inspections should kept.
contains static-sensitive components Always ground
in the installation, operating and
such as bells may not alert people if the
not operate without any electrical power.
may be subject to reduced sensitivity
needed to transmit alarm signals from a premise to
of fire alarm malfunctions, however, is
, this system may operate
prior to removing or inserting
prior to any drilling, filing, reami
more than 9 in-lbs. Over tightenin
may not be technically compatible
WARNING:
frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications, It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense.
This equipment generates, uses and can radiate radio
2 The PDRP-1002 PN 51135:A 03/11 / 99
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiati noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectrique depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
The PDRP-1002 PN 51135: A 03/11/99 3
4 The PDRP-1002 PN 51135:A 03/11 / 99

NFPA Standards

This control panel complies with the following NFPA standards: NFPA 12 CO
NFPA 12A Halon 1301 Extinguishing Systems NFPA 12B Halon 1211 Extinguishing Systems NFPA 72 Central Statio n Signaling Systems (Automatic, M a nual, and Waterflow). Protected Premises Unit (Requires NOTI•FIRE 911AC DACT or MS-5012 Slave Communicat or)* NFPA 72 Local (Automatic, Manual, Waterflow and Sprinkler Supervisory) Fire Alarm Systems NFPA 72 Auxiliary (Automatic, Manual, and Waterflow) Fire Alarm Systems. (Requires 4XTM) NFPA 72 Remote Station (Automatic, Manual, and Waterflow) Fire Alarm Systems. Requires 4XTM, NOTI•FIRE 911AC DACT* NFPA 2001 Clean Agent Fire Extinguish in g Sys te m s
*Applications which require the NOTI•FIRE 911AC are not FM approved.

Additional Information

Before proceeding, the installer should be familiar with the following documents and standards:
NFPA Standards:
NFPA 12 CO2 Fire Extinguishing Systems NFPA 12A Halon 1301 Fire Ext inguishing Systems
NFPA 12B Halon 1211 Fire Extinguishing Systems NFPA 72 Installation, Maintenance and Use of Central Station Signaling Systems NFPA 72 Local, Auxiliary, Remote Station and Proprietary Fire Alarm Systems NFPA 72 Automatic Fire Detectors NFPA 72 Installation, Maintenance and Use of Notification Appliances for Fire Alarm Systems NFPA 72 Testing Procedures for Signaling Systems NFPA 2001 Clean Agent Fire Extinguish in g Sys te m s
Extinguishing Systems (High Pressure Only)
2
Underwriters Laboratories Documents:
UL 38 Manual Actuated Signaling Boxes UL 217 Smoke Detectors, Single and Multiple Station UL 228 Door Closers - Holders for Fire Alarm Systems UL 268 Smoke Detectors for Fire Alarm Systems UL 268A Smoke De te c t o r s for D uc t Ap plications UL 346 Waterflow Indicators for Fire Alarm systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Alarm Systems UL 864 Standard for Control Units for Fire Alarm Systems UL 1481 Power Supplies for Fire Alarm Systems UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for the Hearing Impaired CAN/ULC-S524-M91 Standard for Installation of Fire Alarm Systems CAN/ULC-S527-M87 Standard for Control Units for Fire Alarm Systems
Other:
NEC Article 300 Wiring Methods NEC Article 760 Fire Alarm Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction Notifier Device Compatibility Document, 15378 ADA Americans with Disabilities Act
The PDRP-1002 PN 51135: A 03/11/99 5

1 The PDRP-1002/PDRP-1002E

1 The PDRP-1002/PDRP-1002E

Features

Microprocessor-controlled
Power-limited on all circuits except Municipal Box output
Alarm and trouble resound
Four Class A (Style D)/Class B (Style B) Initiating Device Circuits
Two Class A (Style Z)/Class B (Style Y) Notification Appliance circuits
Two Class B (Style Y) Release Circuits
General alarm and trouble relays
Optional module for 4 zone/function relays (4XZM)
Optional transmitter module (4XTM). Complies with NFPA 72 Auxiliary and Remote Station Fire Alarm systems
Optional volt/amp meter module (4XMM)
Optional supervised remote annunciator (RZA-4X)
Requires LED Interface Module (4XLM)
Optional digital communicator (NOTI•FIRE 911AC)*
Complies with NFPA 72 Central Station and Remote Station Fire Alarm Systems
Supervisory Input Option
Delay timer (adjustable)
Three abort function options
Designed for suppression standards NFPA 12, 12A and 12B
Disable/enable controls per initiating zone
Last Event Recall
Battery/Earth fault supervision
Fuse protection on all Notification/Release Circuits
RMS regulated output power, 2.25 amps
7 amp/hour to 15 amp/hour battery options, up to 90 hours standby
Resettable and non-resettable regulated power outputs
Extensive transient protection
Watchdog timer to supervise microprocessor
Output circuits protected against false activations
Slide-in zone identification labels
Steel cabinet 14.5 in (368.3 mm) wid e b y 16 i n ( 406. 4 mm) high b y 5 in (127 m m) deep
Dead-front dress panel option (DP-4X)
Trim ring for flush mount between 16 in (406.4 mm) center studs (TR-4XR)
Abort and manual release circuits
Cross-zone option
Input Circuits
Applications which require the NOTI•FIRE 911AC are not FM approved
*
.

Circuits

Input Circuits
Detector Zone 1, Class A (Style D)/Class B (Style B) Detector Zone 2, Class A (Style D)/Class B (Style B) Abort, Class A (Style D)/Class B (Style B) Manual Release, Class A (Style D)/Class B (Style B)
Output circuits (optional auxiliary relays track these four circuits)
Notification Appliance Circuit 1, Class A(Style Z)/Class B (Style Y) Notification appliance Circuit 2, Class A(Style Z)/Class B (Style Y) Releasing Circuit 1, Class B (Style Y) Releasing Circuit 2, Class B (Style Y)/Supervis ory Input, Class B (Style B)
6 The PDRP-1002 PN 51135:A 03/11 / 99
Front Panel Control Switches
1 The PDRP-1002/PDRP-1002E
Front Panel Control Switches
Switch 1 Tone Silence Switch 2 Alarm Silence Switch 3 Alarm Activate Switch 4 System Reset
Ground
Neutral
Hot
Transformer
J1
TB5
J2
Optional Ammeter Connection
J9
Batteries
­+
Optional
J3
VoltmeterConnection
+24VU
+ -
+ -
TB1
AC Circuit Breaker
24 VVU
RMS-REGULATED
24 VR
+24VR
Notification Appliance
Circuits
Class A (Style Z) Class B (Style Y)
1234
24 VNR
REGULATED
REGULATED
NON-RESETTABLE
RESETTABLE
+24VNR
B+ A+ A- B-
+ -
B+ A+ A- B-
Releasing
Circuits
B+ B-
B+ B-
Relays
TroubleAlarm
Contacts Contacts
NO NC C NO NC C
Initiating Device
Circuits
Class A (Style D) Class B (Style B)
Abort
Switch
Manual Release
1234
B+ A+ A- B-
B+ A+ A- B-
B+ A+ A- B-B+ A+ A- B-
TB4
TB2
TB3
JP 1
NO DACT
DACT
SUPV 2
4XTM
GEN ALM2
or
4XLM
or
4XZM
*Jumper “OPT 1” must be cut if a module is installed in this position
OPT 1
*
4XTM
or
4XLM
or
4XZM
*Jumper “OPT 2” must be cut if a module is installed in this position
O
123456
Cross Zone
Supervisory
Delay Timer
N
SW1
Abort Option
Abort Option
Delay Timer
Micro Fail LED
BATT
EARTH
Ground Fault LEDBattery Fail LED
Figure 1 PDRP-1002/P DRP-1002E Installatio n Di agram
The PDRP-1002 PN 51135: A 03/11/99 7
OPT 2
*
4XRP1002.cdr
1 The PDRP-1002/PDRP-1002E
4XTM.cdr
4XLM.cdr

Optional Boards

The PDRP-1002/PDRP-1002E has mounting slots for two option boards. Any two of the three option modules may be installed.
Transmitter Module (4XTM - NOTIFIER)
The Transmitter Module provides a supervised output for local energy municipal box transmitter (for NFPA 72 Auxiliary Fire Alarm System) and alarm and trouble reverse polarity circuits (for NFPA 72 Remote Statio n Fi re Alarm System). Also included is a DISABLE switch and disable trouble LED.
As a jumper option, the alarm reverse polarity circuit will open on trouble if no alarm exists.
LED Interface Module (4XLM - NOTIFIER)
The LED Interface Module supports the RZA-4X Remote Annunciator module. Annu nciator wi ring is superv ised for open conditions by this module. The Annunciator Driver Module mounts to the main board, occupying on e of the two option connectors.
Transmitter Module (4XTM - NOTIFIER)
Zone Relay Module (4XZM - NOTIFIER)
The Zone Relay module provides Form-C contacts for the following:
As a jumper option, the first four relays described below can be made silenceable.
DIP 1=OFF Either Zone
Alarm Detected First Alarm Alarm Detected First Alarm Alarm Detected Second Alarm Alarm Detected Second Alarm Release 1 Release 1 Release Release Release 2 Release 2 Not Used Not Used
8 The PDRP-1002 PN 51135:A 03/11 / 99
DIP 1=ON Cross Zone
If Supervisory (DIP 2=ON) Either Zone Cross Zone
4XZM.cdr
Transmitter Module (4XTM - NOTIFIER)
RZA4Xfr.cdr
voltmter.cdr
Transmitter Module (4XTM - NOTIFIER)
For Local Energy Municipal Box service (NFPA 72 Auxiliary Fire Alarm System) Supervisory current: 5.0 mA Trip current: 0.35 amps. (Subtracted from Notification Appliance power) Coil Voltage: 3.65 VDC Coil resistance: 14.6 ohms Maximum allowable wire resistance between panel and trip coil: 3 ohms Municipal Box wiring can leave the building
For Remote Station service (NFPA 72 Remote Station Fire Alarm System):
Maximum load for each circuit: 10mA Reverse polarity output voltage: 24 VDC Remote Alarm and Remote Trouble wiring can leave the b uilding
LED Interface Module (4XLM - NOTIFIER)
Maximum voltage/current, each output: 27.6V/8mA
Note: Outputs are power limited
Zone Relay Module (4XZM - NOTIFIER)
Dry Form-C contacts rated: 2.0 amps @ 30VDC (resistive), 0.5 amps @ 30 VAC (resistive)
1 The PDRP-1002/PDRP-1002E

Remote Annunciator

Optional Meters

Remote Annunciator (RZA-4X - NOTIFIER)
The Remote Annunciator mounts on a standard single­gang box, and provides LED indication of the same functions as the zone relay module. For example with DIP 1=ON and DIP 2=OFF:
One Zone in Alarm (red)
Two Zones in Alarm (red)
Releasing Circuit 1 (red)
Releasing Circuit 2 (red)
System Trouble (yellow)
A Local Trouble Sounder and Silence Switch are also provided. All LED wiring is supervised for open conditions. Any open condition will cause the System Trouble LED to illuminate.
Note: The Remote Annunc iator requir es the use of an LED Interface m od ule (4XLM).
Voltage, Current Meters (4XMM - NOTIFIER)
The Meter Module provides a voltmeter to measure the voltage across the batteries and an ammeter to measure the charging current to the batteries. The meters are provided as an assembly that mounts to the lower left­hand corner of the cabinet.
20
10
DC VOLTS
0
30
5
0
5
DC AMPERES
The PDRP-1002 PN 51135: A 03/11/99 9
1 The PDRP-1002/PDRP-1002E
AC Circuit Breaker
Acctbrkr.cdr

Specifications

AC Power
For the PDRP-1002: 120 VAC, 50/60 Hz, 1.2 amps For the PDRP-1002E: 220/240 VAC, 50 Hz, 0.6 amps Wire size: minimu m #14 AWG with 600V insulation
Battery (lead acid only)
Maximum Charging Circuit: 27.6V, 1.5 amps Maximum Battery Capacity: 15 AH. (Batteries larger than 12 AH require NOTIFIER #BB-17 or other UL listed external battery cabinet.)
Initiating Device Circuits
Power-limited circuitry Operation: Class A (Style D)/Class B (Style B) Normal Operating Voltage: 24 VDC (ripple = 1.0V peak-to-peak) Alarm current: 15 mA minimum Short circuit current: 40 mA maximum Maximum detector current in standby: 2 mA (max) per zone Maximum loop resistance: 200 ohms End-of-line resistor: 4.7K, 1/2-Watt (NOTIFIER part # 71252, UL listed) Detector loop current is sufficient to ensure operation of one alarmed detector per zone. Supervisory current: 5 mA (including end-of-line resistor)
AC Power
Notification Appliance and Releasing Circuits
Power-limited circuitry Maximum allowable voltage drop due to wiring: 2 VDC Normal Operating Voltage: 24 VDC Total current available to all external devices: 2.25 amps
Maximum signaling current per circuit: 1.5 amps End-of-line resistor: 4.7K, 1/2-Watt (NOTIFIER part # 71252, UL listed)
Alarm and Trouble Relays
Dry Form-C contacts rated: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive). All relays must be connected to a power limited power supply.
Four-wire Smoke Detector Power
Up to 200 mA is available for powering 4-wire smoke detectors. Maximum ripple voltage: 1.0 V p/p
Non-resettable Power
Total DC current available from this output is up to 200 mA (subtracted from 4-wire smoke power). Maximum ripple voltage: 1.0 V p/p
RMS Regulated Power
Total DC current available for powering external devices is 0.5 amp (subtracted from
2.25 amps available to notification appliance circuits).
Maximum ripple voltage: 100 mV p/p
Note: For device compatibility, refer to Device Compatibility Chart.
10 The PDRP-1002 PN 51135:A 03/11 / 99
RMS Regulated Power
Door = 16.125 in. (409.58 mm) Backbox = 16 in. (406.4 mm)
Door = 14.625 in. (371.48 mm) Backbox = 14.5 in. (368.3 mm)
1 The PDRP-1002/PDRP-1002E
Cabinet = 5.375 in. (136.53 mm) Backbox = 4.750 in. (120.65 mm)
TR-4XR RUBY RD STEEL 16 GA.
14.594 in. (370.69 mm)
Optional Trim Ring
TR-4XR
Figure 2 Cabinet Dimensions
1.5 in (38.1 mm)
16.094 in. (408.79 mm)
RPCABDIM.cdr
The PDRP-1002 PN 51135: A 03/11/99 11

2 System Operation

2 System Operation
WARNING:When used for CO2 releasing applications, observe proper precautions as stated in NFPA 12. Do not enter the protected space unless physical
!
lockout and other safety procedures are fully completed. Do not use software disable functions in the panel as lockout.

System Status LEDs

Alarm, Trouble and Supe rvisory LEDs will flash on and off until the event(s) has been acknowledged (TONE or ALARM SILENCE), at which point the LED will illuminate steadily.
AC POWER
Green LED that illuminates steadily to indicate presence of AC power.
SYSTEM ALARM
Red LED that flashes when an alarm occurs.
RELEASE
Red LED that illuminates steadily when release occurs.
RMS Regulated Power
SUPERVISOR Y
Yellow LED that flashes upon activation of a supervisory device (such as tamper switch) on Output 4 if selected (see “Setting Mode of Operation” in Section 3 of this manual).
SYSTEM TROUBLE
BATT
EARTH
MICRO
FAIL
Yellow LED that flashes for any trouble condition, including those associated with option boards.
CIRCUIT TROUBLE
Yellow LED that flashes for trouble conditions on output circuits (notification and releasing circuits).
ALARM SILENCED
Yellow LED that illuminates steadily when the ALARM SILENCE switch has been pushed after an alarm.
POW ER TROUBLE
Yellow LED that flashes for low or disconnected batteries and earth fault conditions.
BA TT
Yellow LED that illuminates steadily on mother boar d when battery is low or not detected (not visible through door).
EARTH
Yellow LED that illuminates steadily on mother boar d during a ground fault condition (not visible through door)
4Xoper2.cdr
MICRO FAIL
Yellow LED that illuminates on motherboard when watchdog timer de tects microprocessor failure (no t visi b le throu gh doo r)
12 The PDRP-1002 PN 51135:A 03/11 / 99
RMS Regulated Power

Control Switches

2 System Operation
Tone Silence
Acknowledge alarms, troubles and supervisories. The panel has alarm and trouble resound with LED flash of new conditions. The flashing trouble LED(s) illuminate steadily on TONE SILENCE and the piezo sounder silences. A second trouble will resound the piezo. The piezo has three sounds for alarm, trouble, and supervisory. Trouble cond i tio ns are self- res to ring . Alar ms latch and require RESET to clear.
Alarm Silence
Acknowledge for alarms and supervisories. The ALARM SILENCE switch will silence the local piezo, change any flashing alarm LEDs to steady, and turn off the notification circuits (not the releasing circuits). The “ALARM SILENCED” LED will illuminate. Alarm silence is a latching function and requires a RESET to clear.
Alarm Activate
The ALARM A CTIVATE switch may be used to activate Notification Appliance Circuits. ALARM ACTIVATE also activates the System Alarm relay. ALARM Activate is a latching function. Pressing ALARM SILENCE silences the notification circuits and System Alarm Relay and lights the Alarm Silenced LED. Pressing RESET returns the system to normal.
System Reset
The RESET switch breaks power to all initiating circuits, 4-wire smoke power and option boards and will clear any activated output circuits. If any alarms or troubles still exist after reset, they will reacti vate th e panel. Holding RESET down will perform a LAMP TEST function and will activate the piezo sounder.
4XPTL.cdr

Zone Status LEDs

The alarm and/or trouble LED(s) will flash until the event(s) has been acknowledged (TONE or ALARM SILENCE), at which point the LED(s) will illuminate steadily.
ABORT TROUBLE LED
MANUAL RELEASE TROUBLE LED
The PDRP-1002 PN 51135: A 03/11/99 13
ALARM LED
TROUBLE LE D
ALARM LED
TROUBLE LE D
ABORT LED
MANUAL RELEASE
Zone 1
Zone 2
Abort
Manual Release
2 System Operation

Supervisory

Zone Disable

RMS Regulated Power
Output circuit #4 is used as an input for monitoring supervisory devices such as valve tamper switches (note that SW1 DIP switch #2 must be set “ON” -- see section “Setting Mode of Operation”) By setting Switch short circuit on this input (activation of a N.O. contact) will cause the supervisory LED to flash. The piezo sounder will generate a unique sound. TONE SILENCE will silence the piezo and cause the LED to illuminate steadily. Supervisory signals latch and require RESET to clear . An open circuit will be reported as a circuit trouble.
If a zone has been disabled, an alarm that occurs on that zone will flash the red zone LED, but not the p iez o or any output circuit.
If both power sources are removed from the system, all zones will be re-enabled upon restoration of power. Disable status will be lost .
The Zone Disable routine m akes use of the four panel switches as follows:
1. Press and hold in the TONE
SILENCE switch.

Last Event Recall

2. With the TONE SILENCE switch
held in, press (in sequence) the ALARM SILENCE switch, the ALARM ACTIVATE switch, and then the RESET switch.
3. The Zone 1 Alarm LED will flash.
4. To disable Zone 1, press the RESET switch. The Zone 1 yellow LED will light to
show that the zone is disabled.
Note: The RESET switch toggles disable status for the selected zone.
5. To select the next zone, press the ALARM SILENCE switch.
6. To select the previous zone, press the ALARM ACTIVATE switch.
7. When disable selections are complete, release the TONE SILENCE switch.
If any zone has been disabled, the trouble relay will activate and System Trouble LED will flash.
Last Event Recall allows the user to display the previous panel status. The last event recall uses the four panel switches as follows:
1. Press and hold in the TONE SILENCE switch.
4XPTL.cdr
2. With the TONE SILENCE switch held in, press (in sequence) the RESET switch,
the ALARM ACTIVATE switch, and then the ALARM SILENCE switch.
3. Last Event is displayed.
4. Release the TONE SILENCE switch to return to normal operation.
Note: To clear the last event buffer, press RESET twice.
14 The PDRP-1002 PN 51135:A 03/11 / 99
UL Power Limited Wiring Requirements
imited

3 Installation Procedur e

General

Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean dry, vibration-free area in which extreme temperatures are not encountered. The location should be readily accessible with sufficient room for easy installation and maintenance. Locate the top of the cabinet approximately f ive feet abov e the floo r with the hinge mounting on the left. Determine the number of conductors required for the devices to be employed. Pull required conductors into the box through the knockout provided. All wiring should be in accordance with the National and/or Local codes for fire alarm systems.
UL Power Limited Wiring Requirements
Power limited and non-power limited circuit wiring must remain separated in the cabinet. All power limited circuit wiring must remain at least 0.25 in (6.35 mm) away from any non-power limited circuit wiring. Furthermore, all power limited circuit wiring and non-power limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram for the PDRP-1002/ PDRP-1002E is shown below.
3 Installation Procedure
AC Power
Power L
Circuits
Notification Appliance
Circuits
Non-Power
Limited Circuits
R
e
la
PC Board
Power Limited
Circuits
y
s
I
n
it
ia
ti
n
g
C
i
r
c
u
it
s
4XTM
Power Limited
Circuit
4XZM
Non-Power
Limited Circuit
RP1002PL.cdr
Figure 3 Typical Wiring Diagram for UL Power Limited Requir emen t s
The PDRP-1002 PN 51135: A 03/11/99 15
3 Installation Procedure

Initiating Device Circuits

Zones
Wire all alarm initiating devices sequentially for proper supervision. Initiating devices include: heat, photoelectric, and ionization type detectors; and waterflow alarm devices. Refer to the Compatibility Chart in Appendix B.
Note:
Observe polarity when connecting polarized devices.
All circuits are supervised and power limi te d.
Leave Dummy Load (provided) on al l unused circuits.
4.7K, 1/2-Watt (part # 71252 UL listed)
Two-wire
Smoke
Detector
Heat
Detector
Class B (Style B)
Initiating Device Circuit
Class A (Style D)
Initiating Device
+
+
_
_
+
+
Circuit
_
_
Abort Switch
4.7K, 1/2-Watt (part # 71252
UL listed)
Manual Release
4.7K, 1/2-Watt (part # 71252
UL listed)
Zones
Manual
Pull Station
TB4
+
B+ A+ A-
1234
_
+
B+ A+ A-
B-
5678910
_
B-
B+ A+ A-
11 12
B+ A+ A-
B-
13
IN #1 IN #2 IN #3 IN #4
Figure 4 Example of an A larm Initiating Device
14
B-
15 16
AIDEX.cdr
16 The PDRP-1002 PN 51135:A 03/11 / 99
Zones

4-Wire Smoke Detector Connections

Refer to the Device Compatibility Document for suitable 4-wire smoke detectors.
3 Installation Procedure
24 VDC (+)
+ +
Common (-)
-
-
IDC (+)
+ +
-
-
IDC (-)
Four-wire Smoke Detectors
TB1
+
-
1234
+24VR
A maximum of 200mA is available from the +24VDC 4-wire smoke detector power circuit on TB1 terminals 3 and 4. Any power that is drawn from the +24VDC Non­resettable Power on TB2 terminals 1 an d 2 mu st be subtracted from available 4-wire detector power. (See “Specifications” and “Power” sections.)
UL listed 24 VDC
Class B Initiating Device Circuit
24 VDC (+)
+ +
Common (-)
-
-
IDC (+)
+ +
-
-
IDC (-)
Red
Black
UL listed
4.7K, 1/2-Watt ELR
TB4
B+ A+ A- B-
1234
IN #1
Initiating Device Circuits 1,2, 3, or 4 can be used. Class A (Style D) wiring can also be employed.
Listed Power
Supervision
Relay
RP4WR.cdr
Figure 5 Diagram of Connections for a 4-Wire Smoke Detector
Notes on Class A (Style D) and Class B (Style B) field wiring:
1) The Power Supervision Relay coil leads must be connected to the last detector base 24V screw terminals.
2) Calculation of the maximum allowable resistance in the 24VDC detector power wiring:
R
Where:
R
is the maximum resistance of the 24V wires.
MAX
V
is the minimum operating voltage of the detector or end-of-line relay, whiche ver is
OM
greater, in volts.
N
is the total number of detectors on the 24V supply loop.
I
is the detector current standby.
S
N
is the number of detectors on the 24V power loop which must function at the same
A
time in alarm.
I
is the detector current in alarm.
A
I
is the end-of-line relay current.
R
= (20.6 - VOM)
MAX
_________________________________________________________________________________________
(N x I
) + (NA x IA) + (IR)
S
The PDRP-1002 PN 51135: A 03/11/99 17
3 Installation Procedure
a
,

Output Circuits

Notification Appliance Circuits
Notification Appliance Circuits
This control panel can provide two Class A (Style Z)/Class B (Style Y) Notification Appliance Circuits and two Class B (Style Y) Releasing Circuits (see section “Setting Mode of Operation” for DIP switch configuration). Each circuit is capab le of 1 .5 am ps of current. Total current drawn from all four circuits cannot exceed 2.25 amps. Refer to the Compatibility Chart. Circuits are supervised and power-limited.
Note: Wirin g mu st be configured to maintain a minimum volta ge o f 20.4V on release circuits. Calcu lat ion of maximum allowable resistance:
= 20.6V-20.4V
________________________________________________________________________
R
MAX
Where:
Class A
(Style Z)
Notification
Applianc e Circuit
R
= maximum allowable resistance of wiring
MAX
I
= solenoid current
S
Class B (Style Y) Notification
Applianc e Circuit
4.7K, 1/2-Watt
(part #71252 UL listed)
I
S
Polarized Bell
Polarized Strobe
Polarized Horn
TB2
+
-
+ -
B+ A+ A-
345678910111213141516
OUT #1
4.7K, 1/4-Watt
B+ A+ A-
B-
+
+ -
OUT #2
-
Releasing Circuits
UL listed & FM approved
Releasing Devices
No Connection
NCNCB+ B-
B-
OUT #3
4.7K, 1/4-Watt
No Connection
B+
B-
OUT #4 See note below
Dummy Load all unused Notification Appliance Circuits
Note: Output #4 can be configured for relea sing or supervisory circuit (see Section “Se tt in g M ode of O pe r configured as a releasing circuit, the circuit will be non-power limited. If configured as a supervisory circuit will be power limited. All wiring must follow the power limited “General” Section.
B+ A + A-
B-
B+
Dummy Load all
B-
unused Releasing Circuits
Figure 6 Notification Appliance Circuits
18 The PDRP-1002 PN 51135:A 03/11 / 99
RPNAC.cdr
Alarm Relay
3 Installation Procedure
Alarm Relay
One Form-C dry alarm contact is provided in the basic panel for controlling supplementary devices. It is rated 2 amps at 30 VDC and 0.5 amps at 30 VAC (resistive), and is non-silenceable when an alarm occurs. See below for terminal location.
Trouble Relay
One Form-C dry trouble contact is provided in the basic panel for controlling supplementary devices. It is rated 2 amps at 30 VDC and 0.5 amps at 30 VAC (resistive), and will silence when trouble condition is cleared. See below for terminal location.
Note: The alarm and tr ouble Form-C dry contact relay s must be power limited relays. They must be wired from one of the 24V power limited ter mi nals as shown in the figure below or a comparable UL liste d power limited power supply.
Alarm
NO NC C
Trouble
NO NC C

Power

or
TB1
1234 12
+24VU +24VR
or
+24VNR
TB2
TB3
1234
Alarm
Schematic representa tion of
Alarm/Trouble coil s and c ont acts.
56
Trouble
Figure 7 Alarm/Trouble Coils and Contacts
CAUTION: Several different sources of power can be connected to this panel.
!
Disconnect all sources of power before servicing. The pane l and associated equipmen t may be damaged by removing and/or inserting cards, modules, or interconnecting cables while this unit is energized.
This output is not suitable for powering devices requiring fil tered DC power.
RMS-Regulated Power
24 VDC power for inductive­type devices such as door holders can be connected to TB1 terminals 1 (+) and 2(-).
The combined current draws from the Resettable and Non-resettable outputs cannot exceed 200 mA.
4-Wire Smoke Detector Power
24 VDC filtered, resettable power for 4-wire smoke detectors can be obtained from TB1 Terminals 3(+) and 4(-).
Non-resettable Power
24 VDC filtered, nonresettable power can be drawn from TB2 Terminals 1 (+) and 2(-).
RPALMTBL.CDR
+24VU
+ - + -
TB1
+24VR +24VNR
+ -
TB2
1234 12
Figure 8 Diagram of Power Termi nals
The PDRP-1002 PN 51135: A 03/11/99 19
RPPWRTRM.cdr
3 Installation Procedure
AC Power
Primary power required for the PDRP-1002 panel is 120 VAC, 50/60 Hz, 1.2 amps and primary power for the PDRP-1002E is 220/240 VAC, 50 Hz, 0.6 amps. Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Code (NEC) and/or local codes. Use #14 AWG (2.00 mm
2
)or larger wire with 600 volt rating.
Battery Power
Observe polarity when connecting battery. Connect battery cable to J9 on the main board using the plug-in connector provided. See Appen dix A for calcul ation of correct battery rating.
CA UTION: Batteries contain s ulfuric acid which can cause se ver e b urns to the skin and
!
eyes, and can destroy fabrics. If contact is made with sulfuric acid, immediately flush skin or eyes with water for 15 minutes and seek immediate medical attention.
Voltmeter/Ammeter
To monitor battery voltage and battery charging current, a 4XMM (NOTIFIER) is required. To install the power meter module, remove the jumper labeled “AMP” and connect cable assembly P2 to pin connector J2 and cable assembly P3 to pin connector J3 on the main board. Secure the 4XMM to the backbox with the two screws provided. On some models, it will be necessary to install the meter b racket with the nuts and bolts provided.
AC Power
5
0
10
DC VOLT S
0
DC AMPERES
P2
20
J2
J9
P3
J3
30
5
RPMBVM.cdr
Figure 9 Diagram of the 4XMM Voltmeter Connected to the Main Board
20 The PDRP-1002 PN 51135:A 03/11 / 99
Voltmeter/Ammeter

Optional Modules

Transformer
Ground
Neutral
Hot
Optional Ammeter Connection
3 Installation Procedure
The fire control panel has two module connectors - J5 and J8. Three modules are available for the panel and they can be used in any combination, including duplicate modules. The corresponding option jumper must be cut before installation of an optional module.
J4
*Jumper “OPT 1”
J5
must be cut if a module is installed in this position
Batteries
Optional VoltmeterConnection
J7
J8
Cross Zone
Supervisory
Ground Fault LEDBattery Fail LED
Note:
Optional 4XLM module for an RZA-4X Annunciator mu st be inst al le d on J7 and J8
4XTM and 4XZM module s can be in sta ll ed in ei th er location.
Delay Timer
Figure 10 Optional Panel Modules
Abort Option
Abort Option
Delay Timer
Micro Fail LED
*Jumper “OPT 2” must be cut if a module is installed in this position
only
.
4XRP102a.cdr
The PDRP-1002 PN 51135: A 03/11/99 21
3 Installation Procedure
Installing Option Modules
Installing Option Modules
Insert the two stand-offs (provided) into the holes located on the right-side edge of the main board. Carefully align the pins on the main board with J1 and/or J2 on the option board. Insert screw through the option board until it is secured on the stand-offs. Affix the terminal identification labels provided with the option modules as shown below.
(Part # 42050)
Stand-offs)
Option Board (4XZM shown)
Main Board
4XSTNOFF.cdr
4XOPTNBD.cdr
Figure 11 Installing Option Modules.
22 The PDRP-1002 PN 51135:A 03/11 / 99
Transmitter Module - 4XTM (NOTIFIER)
Transmitter Module - 4XTM (NOTIFIER)
Polarities shown in activated positions. The wiring of this module must follow the requirements as specified in the “General” section, “
Requirements.
3 Installation Procedure
UL Power Limited Wiring
1
2
3
4
5
6
7
TBL Jumper
Disconnect LED
4XTBa.cdr
Disconnect Switch
+
Remote Alarm
}
-
+
Remote Trouble
}
-
No Connection
+
Municipal Box*
}
-
Power Limited Circuit
Non-Power Limited Circui
* Dummy load terminals 6 and 7 (4.7K, 1/4 W resistor) if Municipal Box is not connected.
Push the disconnect switch down to prevent unwanted activation of the Municipal Box and Remote Station Outputs during testing of the control panel. The Disconnect LED will remain illuminated while the Municipal Box is disconnected. The System Trouble LED will indicate disconnected and/or Open Circuit conditions on the Municipal box.
Cutting the TBL jumper will allow the alarm reverse polarity circuit to open on tr ouble, if no alarm exists
Note: Remote Alarm, Remote Trouble, and Municipal Box wiring can leave the building.
.
The PDRP-1002 PN 51135: A 03/11/99 23
3 Installation Procedure
Zone Relay Module - 4XZM (NOTIFIER)
Zone Relay Module - 4XZM (NOTIFIER)
Non-power li mited and po w er limited wiring mu st h ave a minimum distance of 0.25 i n. (6.35 mm) wire to wire. If this module is used to drive non-power limited and power limited circuits, please follow the instructions below.
Relay #1 through #4 will activa te w it h Output #1 through #4 and remain latched unless jumper “LATCH” is cut.
1 NO 2 NC
3 C
4 NO 5 NC 6 C 7 NO 8 NC 9 C
10 NO 11 NC 12 C
13 NO
14 NC 15 C 16 NO 17 NC 18 C
4XZMA.cdr
Use Disable switch to disconnect the relays.
Cut jumper fo r no n -latching (s ilenceable) r elay operati o n.
Relay #1
Relay #2
Relay #3
Relay #4
Alarm
Trouble
1) Skip a set of dry contacts to maintain the 0.25 in (6.35 mm) required space between power limited and non-power limited circuits. The wiring of this module must follow the requirements as specified in the “
Wiring Requirements
.”
General
” section, “
UL P ower Limited
OR
2) If this module is needed to drive power limited and non-power limited relays that are next to each other, refer to the figure below showing a typical connection.
Relay #1
Relay #2
Relay #3
Relay #4
Note: Refer to the Protected Premises Unit label, located on the door of the control panel, to indicate if any dry contacts are t o be use d as non-power limited dry contacts.
NO NC C
NO NC C
NO NC C
NO NC C
Power Limited Circuit
Power Limited Circuit
No Connection
Non-power Limited Circuit
Non-power Limited Circuit
4XZMptl.cdr
24 The PDRP-1002 PN 51135:A 03/11 / 99
LED Interface Module - 4XLM (NOTIFIER)
LED Interface Module - 4XLM (NOTIFIER)
The wiring of this module must follow the requirements as specified in section”
Requirements
.”
3 Installation Procedure
UL Power Limited Wiring
1 +24V 2 Out#1 3 Out#2 4 Out#3 5 Out#4 6 System Trouble 7 Sound 8 Resound
4XLMa.cdr
Front View
Connect to corresponding terminals of RZA-4X Remote Annunciator.
RZA4XBX.cdr
RZA4Xfr.cdr
Side View
Single-gang Box
Note: Make wiring connections with system power off. Maximum wire impedance is 50 ohms per wiring connection .
Figure 12 LED Interface Module - 4XLM
The PDRP-1002 PN 51135: A 03/11/99 25
3 Installation Procedure

Setting Mode of Operation

DIP Switch
The DIP switch is located at the bottom of the PDRP-1002/PDRP-1002E main board. To set a switch to the “ON” position, slide the switch up until it stops. The flush­surface switches are designed to pre v ent accidentally changing a switch setting and may therefore require use of a pen or screwdriver to set them.
O
123456
N
DIP Switch
4XRPDIPS.cdr
Battery Fail
LED
Ground Fault LED
DIP Switches
Switch 1: CROSS ZONE Switch 2: SUPERVISORY
Note: The Reset key must be depressed af te r any switch configuration has been made.
O
123456
N
Micro Fail LED
Switch 3: DELAY TIMER
Switch 4: DELAY TIMER Switch 5: ABORT OPTION
Switch 6: ABORT OPTION
Cross Zone
Select the desired mode of operation and set SW1 DIP switch 1.
Switch 1 OFF ON
Output 1
Zone 1
either
is activated by an alarm on
Zone 2
or
.
Output 1
(Pre-discharge alarm) is activated by the first alarmed zone in the system. Initiation of an alarm on the other zone will shut this output off.
Output 2
either
is activated by an alarm on
Zone 1
or
Zone 2
. Output 2 will pulse at 60 ppm while timer is running or frozen by abor t. Output 2 will sound steadily upon release (time out).
Outputs 3 and 4
will be activated when the timer expires (provided that
Output 2
occur on both
is activated when alarm s
Zone 1
and
Zone 2
Output 2 will pulse at 60 ppm while timer is running or frozen by abort. Output 2 will sound st eadily upon release (time out).
.
Output 4 is functioning as a releasing circuit - set via DIP Switch 2).
Timer
The alarm occurs on either
Zone 2
Note: Outputs 1 and 2 refer to Notification Appliance Circuits. Output 3 refers to a releasing circuit. Output 4 is determined by setting switch 2. Zones 1 and 2 re fe r to In it ia ting D evice Cir cuits.
26 The PDRP-1002 PN 51135:A 03/11 / 99
will start whenever an
Zone 1
.
or
Timer will start
The occur on both
Zone 1
when alarms
Zone 2
and
.
Output 4 Supervisory/Releasing Service
Output 4 Supervisory/Releasing Service
Set the function of Output 4 via SW1 DIP switch 2.
Switch 2 OFF ON
3 Installation Procedure
Output 4
solenoid releasing circuit. This circuit will be a non-power limited circuit in this mode.
will function as a
Output 4 will function as a supervisory input circuit. A short condition on this circ uit will illuminate the Supervisory LED and sound the supervisory ton e on the piezo. An open condition generates a circuit trouble condition. This circuit will function as a power limited circuit in this mode.
Timer
Select the desired Timer setting and set SW1 DIP switches 3 and 4 per the appropriate column.
No Delay* 10 Seconds 20 Seconds 30 Seconds
Switch 3 OFF OFF ON ON Switch 4 OFF ON OFF ON
*Abort switch is inoperative when no delay is selected.
Abort Function
Select the desired abort funct ions and set SW 1 DIP switc hes 5 and 6 per the appr opriate column.
Switch 1 OFF OFF ON ON Switch 2 OFF ON OFF ON
Standard UL-type delay
timer which continues to count down upon ABORT , and stops and holds at 10 seconds until release of the ABORT switch. Upon release of the ABORT switch, the timer resumes the countdown at 10 seconds.
These modes are the onl y on es t hat comply with UL Standard 864
Note: ABORT timer will not operate when timer is set for “NO DELAY”.
IRI-type delay timer
which functions the same as the UL-type timer with the except ion that the ABORT will function only if pressed and held before 2nd zone goes into alarm.
NYC-type delay timer.
Pressing ABORT, once an alarm exists, changes timer value to the time selected via DIP Switches 3 and 4 plus 90 seconds. The timer will not start as long as the ABORT switch is held. SYSTEM RESET restores timer to original times selected via DIP Switches 3 and
4. Successive ABORTS will add 90 seconds to selected timer value.
Local Jurisdiction delay timer.
the timer has started, pressing ABORT restores timer to its full time as s e t o n DIP Switches 3 and
4. The timer will not start as long as ABORT is held. Release of the ABORT switch continues the countdo wn, where as pressing ABORT again will restore the timer to its full value.
Once
The PDRP-1002 PN 51135: A 03/11/99 27

Appendix A: Power Calculations

Appendix A: Power Calculations
Standby Battery Requirements
The Standby Battery Current figure obtained in the following table (Table 1) represents the amount of current that must be supplied by the secondary power source (batteries) to sustain control panel operation for one hour.
Standby Battery Requirements
Basic Contro l Panel
Control panel with AC power off, System Trouble LED and audible trouble sounder on.
If using a 4XZM Zone Relay Module1 [ ] X 8 mA =
f using a 4XTM Transmitter Module, add 11 mA
If using the Reverse Polarity Alarm output, add 5 mA
If using the Reverse Polarity Trouble output, add 5 mA
If using a 4XLM/RZA-4X Driver/Annunciator combination:
1
[ ] X 19 mA = If using a 4XMM Meter Module, add 1 mA
If using the Noti•Fire 911AC DACT, add 30 mA
Number
in use
(see Appendix B for data)
a. Two-wire detector he ads
Device
Current
X =
Total
Current
88 mA
b. Four-wire detector heads
c. End of Line Relays
d. Add lines a, b, & c for
X =
X 25.0 mA =
Place subtotal here
Add last column for Standby Battery Current : and continue to next table (Table 2)
Table 1 Standby Battery Requirements
Note: The control panel will support the installation of one or two optional modules, inc lu ding two of the same type of module.
28 The PDRP-1002 PN 51135:A 03/11 / 99
Ampere-Hour Calculations
Appendix A: Power Calculations
Ampere-Hour Calculations
Standby Battery Current
Convert the total from Table 1 to amps and enter here
amps X
Enter 0.25 for 5 minutes in alarm or 0.5 for 10 minutes in alarm
Add Standby and A larm amp/h ours
Select a battery with an equal or greater amp/hour rating than the f igur e obtained in
Table 2. Batteries must be lead-acid type.
PS-1270 12 volt, 7 amp/hour (two required) PS-12120 12-volt, 12 amp/hour (two required)
StandbyTime
24, 60, or 90 hours
hours =
+
=
Table 2 Ampere-Hour Calcula t ions
Standby amp/hours
Alarm amp/hours
Total amp/ hours needed
Notes:
1. Alarm amp-hours assumes a maximum system draw of 3 amps in alarm for 5 minutes (0 .25 amp/hour) or for 10 minutes (0.5 amp/hour)
2. NFPA 72 Central Station and Local and Propri etary Fire A larm S ystems requir e 24 hours of standby.
3. NFPA 72 Auxiliary and Remote Station Fire Alarm Systems require 60 hours of standby.
4. Factory Mutual Systems require 90 hours of standby.
5. The battery charger in this panel will charge a maximum of 15 amp/hours of batteries within 48 hours (7 amp/ hour mini mum). Batteries larger than 12 amp/ hour will require a UL listed battery cabinet (e.g. NOTIFIER BB-17).
The PDRP-1002 PN 51135: A 03/11/99 29

Appendix B: Device Compatibility

Appendix B: Device Compatibility
FM-Approved Releasing Devices
Smoke Detector/Base Detector Type
System Sensor 2424 Photoelectric 0.10 41 System Sensor 2424TH Photoelectric 0.10 41 System Sensor 2451 Photoelectric 0.10 39 System Sensor 2451TH (with/B402B Base) Photoelectric 0.10 39 System Sensor 1424 Ionization 0.10 41 System Sensor 1451 (w/B402B Base) Ionization 0.10 39 System Sensor 2412 Photoelectric 0.12 77 System Sensor 2412AT Photoelectric 0.12 58 System Sensor 2412TH Photoelectric 0.12 77 System Sensor 2312/24TB Photoelectric 0.12 50 System Sensor B112LP Base System Sensor B114LP Base System Senso r B404B Base System Sensor 6424 Projected Beam 10 28.4 System Sensor DH400ACDCI Ionization Duct 25 95
Max Standby Current (mA)
see note see note see note see note
Max Alarm Current (mA)
39 75
System Sensor DH 40 0ACDCP Photoelectric Duct 25 95 System Sensor 1112/24 Ionization 0.05 50 System Sensor 2112/24 Photoelectric 0.05 50 System Sensor 2112/24B Photoelectric 0.05 65 System Sensor 21 12 /2 4T Photoelectric w/13 5°
Thermal
System Sensor 2112/24TSRB Photoelec tr ic w/135°
Thermal Supervisory Relay
Note: Contact manufacturer for currents.
0.05 50
15 45
Table 3 UL Listed Four-Wire Smoke Detectors
FM-Approved Releasing Devices
(System Sensor’s PDRP-1002/PDRP-1002E)
Solenoid Group [A]
Skinner solenoid valve Model LV2LBX25, 24 VDC, 11 Watts, 458 mA, 1/2 in. NPS, 5/ 8 in. orifice.
Solenoid Group [B] These valves are interchangeable
ASCO solenoid valve Model T8210A107, 24 VDC, 16.8 Watts, 700 mA, 1/2 in. NPS, 5/8 in. orifice.
.
ASCO solenoid valve Model R8210A107, 24 VDC, 16.8 Watts, 700 mA, 1/2 in. NPS, 5/8 in. orifice.
ASCO solenoid valve Model 8210A107, 24 VDC, 16.8 Watts, 700 mA, 1/2 in. NPS, 5/
30 The PDRP-1002 PN 51135:A 03/11 / 99
FM-Approved Releasing Devices
8 in. orifice.
Solenoid Group [C]
Star Sprinkler Corp. Solenoid P/N 5550, 24 VDC, part of Model D deluge valve. Kidde-Fenwal Electric Control Head P/N 890181; 24V, 2.0 Amps Kidde-Fenwal Electric Control Head P/N 899175; 24V, 2.0 Amps Kidde-Fenwal Electric Control Head Stackable (XP) P/N 48650001; 24V, 0.2 Amps Kidde-Fenwal Electric and Cable Op Control Head (XP) P/N 897494; 24V, 1.5 Amps,
33 Watts
Refer to the FM approval guide for automatic water control valves which are compatible with solenoids listed above.
Appendix B: Device Compatibility
Model Type Current (mA)
FM980-24 Floor Mount, single 68 FM996-24 Wall Mount Surface Wiring 68 FM998-24 Wall Mount Concealed Wiring 68
Table 4 24 VDC Door Holders
Vendor Model Current(mA)
System Sensor A77-716B 20 Air Products & Controls, LTD MR-101/C
MR-201/C
15 35
Table 5 UL Listed 24 VDC Relays
The PDRP-1002 PN 51135: A 03/11/99 31
Appendix B: Device Compatibility
FM-Approved Releasing Devices
SYSTEM SENSOR
System Sensor MA-12/24D Electronic Sounder 24VDC 73 46 System Sensor SS24 Strobe 24VDC System Sensor SS24LO Strobe 24VDC 45 25 System Sensor SS24LOC Ceiling Strobe (SS24LOBC - beige) 24VDC 45 25 System Sensor SS24M Strobe 24VDC 125 75 System Sensor SS24MC Ceiling Strobe 24VDC 125 75 System Sensor MASS24D Electronic Sounder/Strobe 24VDC 118 71 System Sensor MASS24LO Electronic Sounder/Strobe 24VDC 118 71 System Sensor MASS24LOC Electronic Ceiling Sounder/Strobe 24VDC 118 71 System Sensor MASS24LOLA Electronic Sounder/Strobe with Fuego lens 24VDC 118 71 System Sensor MASS24M Electronic Sounder/Stro be 24VDC 198 121 System Sensor MASS24MC Electronic Ceiling Sounder/Strobe 24VDC 198 121 System Sensor PA400R Sounder 24VDC System Sensor PS24LO Add-on Strobe 24VDC 45 25
Rated Voltage²
FWR DCFiltered
DC
note 5
note 5
30
15
System Sensor SS24 15ADA Signaling Strobe 24VDC 90 75 System Sensor SS2475ADA Signaling Strobe 24VDC 200 170 System Sensor SS24110ADA Signaling Strobe 24VDC 245 210 System Sensor SS241575ADA Signaling Strobe 24 VDC 120 93 System Sensor SS24 15ADAS Signaling Strobe with Synch. Circuit 24 VDC 125 10 6 System Sensor SS241575ADAS Signaling Strobe with Synch. Circuit 24 VDC 180 115 System Sensor MASS2415ADA Sounder/Signaling Strobe 24VDC 163 121 System Sensor MASS2475ADA Sounder/Signaling Strobe 24VDC 273 216 System Sensor MASS 24110ADA Sounder/Signaling Strobe 24VDC 318 256 System Sensor MASS 241575ADA Sounder/Signali ng Strobe 24 VDC 193 139 System Sensor MASS 2415ADAS Sounder/Signaling Strobe w/ Synch. Ckt. 24 VDC 163 121 System Sensor MASS241575ADAS Sounder/Signaling Strobe w/ Synch. Ckt. 24 VDC 193 139 System Sensor PS24 15ADA Mini-Sounder/Strobe 24VDC 110 90 System Sensor PS24 75ADA Mini-Sounder/Strobe 24VDC 135 108 System Sensor PS241575ADA Mini-Sounder/Strobe 24VDC 135 108 System Sensor PS24110ADA Mini-Sounder/Strobe 24VDC 240 225¥ System Sensor SP1R2415ADA Speaker/Signaling Strobe 24VDC 90 75 System Sensor SP1R2475ADA Speaker/Signaling Strobe 24VDC 200 170 System Sensor SP1R24110ADA Speaker/Signaling Strobe 24VDC 245 210
32 The PDRP-1002 PN 51135:A 03/11 / 99
FM-Approved Releasing Devices
System Sensor SP1R 241575ADA Speaker/Signaling Strobe 24 VDC 120 93 System Sensor V4R2415ADA Speaker/Signaling Stro be 24VDC 90 75 System Sensor V4R2475ADA Speaker/Signaling Strobe 24VDC 200 170 System Sensor V4R24110ADA Speaker/Signaling Strobe 24VDC 245 210 System Sensor V4R241575ADA Speaker/Signaling Strobe 24 VDC 120 93 System Sensor SP100W24LOC Ceiling Speaker/Stro be, 8" round grille 24VDC 45 25 System Sensor SP101R24LO Speaker/Strobe, 5" square grille 24VDC 45 25 System Sensor SP101R24M Speaker/Strobe, 5" square grille 24VDC 125 75 System Sensor SP100W24MC Ceiling Speaker/Strobe, 8" round grille 24VDC 125 75
Appendix B: Device Compatibility
System Sensor MA12/24EH Multi Alert Horn with Mechanical Tone 12VDC/
24VDC System Sensor MAEH24LO Multi Alert Horn with Mechanical Tone/Strobe 24VDC 109 68 System Sensor MAEH24LOC Multi Alert Horn with Mechanical Tone/Strobe 24VDC 109 68 System Sensor MAEH24LOLA Multi Alert Horn with Mechanical Tone/Strobe 24VDC 153 96 System Sensor MAEH24M Multi Alert Horn with Mechanical Tone/Strobe 24VDC 189 118 System Sensor MAEH24MC Multi Alert Horn with Mechanical Tone/Strobe 24VDC 189 118 System Sensor MAEH1215ADA Multi Alert Horn with Mechanical Tone/Strobe 12VDC 240 191 System Sensor MAEH121575ADA Multi Alert Horn with Mechanical Tone/Strobe 12VDC 310 246 System Sensor MAEH2415ADA Multi Alert Horn with Mechanical Tone/Strobe 24VDC 278 216 System Sensor MAEH2475ADA Multi Alert Horn with Mechanical Tone/Strobe 24VDC 273 216 System Sensor MAEH241575ADA Multi Alert Horn with Mechanical Tone/Strobe 24VDC 343 271 System Sensor MAEH24110ADA Multi Alert Horn with Mechanical Tone/Strobe 24VDC 318 256 System Sensor MAEH2415ADAS Multi Alert Horn with Mechanical Tone/Strobe 24VDC 198 152 System Sensor MAEH241575ADAS Multi Alert Horn with Mechanical T one/Strobe 24VDC 253 241 System Sensor H12 Spect rAlert Horn 12VDC 25 14
20/64 38/43
System Sensor H42 SpectrAlert Horn3 24VDC 42 37 System Sensor S1215 SpectrAlert Strobe 12VDC 159 133 System Sensor S121575 SpectrAlert Strobe 12VDC 182 168 System Sensor S2415 SpectrAlert Strobe3 24VDC 142 83 System Sensor S241575 SpectrAlert Strobe3 24VDC 132 76 System Sensor S2475 SpectrAlert Strobe3 24VDC 170 145 System Sensor S24110 SpectrAlert Strobe3 24VDC 220 169 System Sensor P1215 SpectrAlert Horn/Strobe 12VDC 173 144 System Sensor P121575 SpectrAlert Horn/Strobe 12VDC 196 179 System Sensor P2415 SpectrAlert Horn/Strobe3 24VDC 165 94 System Sensor P241575 SpectrAlert Horn/Strobe3 24VDC 177 111
The PDRP-1002 PN 51135: A 03/11/99 33
Appendix B: Device Compatibility
FM-Approved Releasing Devices
System Sensor P2475 SpectrAlert Horn/Strobe3 24VDC 215 180 System Sensor P24110 SpectrAlert Strobe3 24VDC 265 214 System Sensor RP1215ADAARetrofit Strobe Plate 12VDC 200 170 System Sensor RP121575ADAARetrofit Strobe Plate 12VDC 240 255 System Sensor RP241 5ADAARetrofit Strobe Plate 24VDC 90 75 System Sensor RP241575ADAARetrofit Strobe Plate 24VDC 120 93 System Sensor RP2475ADAARetrofit Strobe Plate 24VDC 200 170 System Sensor RP24110ADAARetrofit Strobe Plate 24VDC 245 210 System Sensor H24 Spect rAlert 24VDC 42 37 System Sensor S2415 SpectrAlertStrobe3 24VDC 142 83 System Sensor S241575 SpectrAlert Strobe3 24VDC 132 76 System Sensor S2475 SpectrAlert Strobe3 24VDC 170 145 System Sensor S24110 SpectrAlert Strobe3 24VDC 220 169 System Sensor S2415 SpectrAlert Horn/Strobe3 24VDC 165 94 System Sensor S241575 SpectrAlert Horn/Strobe3 24VDC 177 111 System Sensor S2475 SpectrAlert Horn/Strobe3 24VDC 215 180 System Sensor P24110 SpectrAlert Horn/Strobe3 24VDC 265 214 System Sensor S2415 SpectrAlertStrobe3 24VDC 142 83 System Sensor S241575 SpectrAlert Strobe3 24VDC 132 76
Note:
1) Control panels suppling Special Application (FWR, Filtered) power must use the notification appliances, relays or door holders listed in this table.
2) All currents are in Millamperes and worst case average.
3) Nominal Oper ating voltage.
4) Refer to Installation Instruct io ns for m o re inf ormation.
5) Contact manufacturer for current s.
Table 6 UL Listed Notification Appliances
34 The PDRP-1002 PN 51135:A 03/11 / 99
FM-Approved Releasing Devices
Appendix B: Device Compatibility
Number of Detectors Per Zone
Model Det. IDDetector Type Base Model Base
ID
System Sensor 1400 A Ionization n/a n/a 10 0 20 System Sensor 1451 A Ionization B401B / B406B A 120 15 / 1 System Sensor 1851DH A Ionization DH1851DC A 120 15 System Sensor 2400 A Photoelectric n/a n/a 120 15 System Sensor 2400AIT A Photo / Isolated
Thermal / Horn System Sensor 2400AT A Photo / Thermal / Horn n/a n/a 120 1 System Sensor 2400TH A Phot o / Thermal n/a n/a 120 15 System Sensor 2451 A Phot oelectric B401B / B406B A 120 15 / 1 System Sensor 2451TH A Phot o / Thermal B401B / B406B A 120 15 / 1 System Sensor 2851DH A Photoelectric DH2851DC A 120 15 System Sensor 1451DH A I onization DH-400 A 120 15 System Sensor 2451 A Photoelectric DH-400 A 120 15 System Sensor 2300T A Photo / Thermal n/a n/a 120 15
n/a n/a 120 1
Standby Current (uA)
PDRP-1002/ PDRP-1002E
System Sensor 1800 A Ionization n/a n/a 100 n/a System Sensor 1851B A Ionization B101B A 120 n/a System Sensor 1851B A Ionization B107B A 120 n/a System Sensor 2800 A Photoelectric n/a n/a 120 n/a System Sensor 2800TH A Phot o / Thermal n/a n/a 120 n/a System Sensor 2851B A Photoelectric B101B A 120 n/a System Sensor 2851B A Photoelectric B107B A 120 n/a System Sensor 2851B TH A Photo / Thermal B101B A 120 n/a System Sensor 2851B TH A Photo / Thermal B107B A 120 n/a System Sensor 1151 A Ionnization B401 / B110LP /
B116LP
System Sensor 2151 A Photoelectric B401 / B110LP /
B116LP
A 120 15 / 15 / 1
A 120 15 / 15 / 1
Table 7 UL Listed, Compatible Two-Wire Smoke Detectors for Notifier Control Panels
The PDRP-1002 PN 51135: A 03/11/99 35

Appendix C: NFPA Standard-Specific Requirements

FM-Approved Releasing Devices
Appendix C: NFPA Standard-Specific Requirements
The PDRP-1002/PDRP-1002E has been desig ned for use in commercial, indus trial, and institutional applications and meets the requirements for service under the National Fire Protection Association (NFPA) Standards outlined in this appendix. The minimum system components required for compliance with the appropriate NFPA standards are listed below.
PDRP-1002/PDRP-1002E Control Panel
(backbox and door), main supply transformer and power supply.
Batteries Initiating Devices Notification Appliances
Appliance Circuits .
Releasing Devices
The following additional equipment is needed for compliance with the NFPA standards listed below.
NFPA 72 Signaling Systems for Central Station Service (Protected Premises Unit)
NOTI•FIRE 911AC DACT* - for connection to a compatible listed Central Station DA CR or Protected Premises Receiving Unit. This unit must be installed as outlined in Figure 13.
NFPA 72 Auxiliary Fire Alarm System
4XTM Transmitter Module for connection to a compatible listed Local Energy Municipal Box. This unit must be installed as outlined in Figure 15.
NFPA 72 Remote Station Fire Alarm System
4XTM Transmitter Module for connection to Fire•Lite RS82-9 Remote Station Receiver. See Figure 16 for installation instructions.
(refer to Appendix A for Standby Power Requirements).
- connected to one of the control panel’s Initiating Device Circuits.
- connected to one of the control panel’s Notification
- connected on one of the control panel’s Releasing Circuits.
containing the main control board, cabinet
OR NOTI•FIRE 911AC DACT* - For connection to a compatible listed remote station
DACR. This unit must be installed as outlined in Figure 13.
*Applications which require the NOTI•FIRE 911AC are not FM approved
.
36 The PDRP-1002 PN 51135:A 03/11 / 99
NFPA 72 Signaling Systems for Central Station Service
NFPA 72 Signaling Systems for Central Station Service
(Protecte d Premises Unit) and Remote Station Fire Ala rm Sys te m ( Protected Pr em is es Unit)
NOTI•FIRE 911 AC D ACT* - for connection to a Central Station Receiver or Protected Premises Receiving Unit. This unit must be installed as illustrated below. For additional information on the 911AC, refer to document 74-06200-005.
All connections between the FACP and 911AC must be in conduit, less than 20 ft (609.6cm) in length in the same room. If the NOTI•FIRE 911AC is not mounted in the PDRP-1002/PDRP-1002E backbox all connections must be in conduit, less than 20 ft. (609.6 cm) in length in the same room.
*This application using the NOTI•FIRE 91 1AC is not FM approved.
Note: For 911AC
The Maximum standby load shall be 125 mA.
The Standby by Battery Requirement: 24VDC, 7Amp-Hour-Max.
The PDRP-1002/PDRP-1002E is not suitabl e fo r transm ission of a supe rvi sory sig na l to the DACT.
Note: The PDRP-1002/ PDRP-1002E is not suitable for transmission of a supervisory signal to th e DACT
To AC Power
Alarm
Appendix C: NFPA Standard-Specific Requirements
NOTE on STD DACT:
Place jumper over pins 2 and 3, marked DACT, when employing a DACT. This di rect s the c o ntr ol pane l
1 2
3
4
5
6 7 8 9 10 11 12
1
12VAC, 20VA, 60Hz or +24VDC
2
12VAC, 20VA, 60Hz or -24VDC
3
(Refer to manual) BATTERY -
4
BATTERY +
5
INITIATING A1 -
6
INITIATING A2 -
7
INITIATING B1 +
8
INITIATING B2 +
9
SUPE R V IS O R Y H I
10
SUPE R V IS O R Y LO
11
TROUBLE RELAY NC
12
TROUBLE RELAY COM
13
TROUBLE RELAY NO
14
ALARM RELAY NC
15
ALARM RELAY COM
16
ALARM RELAY NO
17
Digital Alarm Co mmunicator Transmitter Listed for Central Station or Remote Station Service.
Slide Cover Back to Access Programming Jack and Relays
- 12 VDC Sealed R echa rge able + Battery
+
-
PS1270
12Volt
7AH Battery
Alternate RJ31X
Primary RJ31X
Telco J a c k
Telco J a c k
to transmit all trouble conditions except AC LOSS.
To Central Station
JP-1
Motherboard 911AC
Alarm
normally open contacts
Trouble
normally open
RP911AC.CD
contacts
Figure 13 NFPA 72 Signaling Systems for Central Station Service
TB3-1 6 and 7 TB3-3 8 and 9
TB3-4 10 TB3-6 11
STDDACT
The PDRP-1002 PN 51135: A 03/11/99 37
Appendix C: NFPA Standard-Specific Requirements
Using the MS-5012 as a DACT
1) Reference the MS-5012 manual for additional information.
2) Program the MS-5012 for slave applications.
3) The PDRP-1002/PDRP-1002E is not suitable for transmission of a supervisory signal to the DACT.
Secondary
Modular Cable P/N MCBL-6
Phone Line
Primary Phone Line
NFPA 72 Signaling Systems for Central Station Service
120 VAC
HOT Neutral
Ground
Yellow
Yellow
Black
White
Green
AC Wiring for DACT/FACP must be connected to the s a me circuit.
Red
Black
MS-5012
J2
AC POWER ALARM
1
23
5
4
7
8
A
OB
TROUBLE
SUPERVISORY
6 9
12VDC Battery 2-7AH
Alarm
TB2
J3
Trouble
F E
1st
D
EVENT
ENTER
C
STORE
TB3
Motherboard MS-5012
TB3-1 TB2-2
Alarm
TB3-3 TB2-1
1 2 3 4 5 6
TB3
MS5012X2.CDR
PDRP-1002/PDRP-1002E
Trouble
38 The PDRP-1002 PN 51135:A 03/11 / 99
TB3-4 TB2-4 TB3-6 TB2-3
Figure 14 Using the MS-5012 as a DACT
NFPA 72 Auxiliary Fire Alarm System
NFPA 72 Auxiliary Fire Alarm System
All connections are power limited and supervised. This application is not suitable for separate transmission of sprinkler supervisory or trouble conditions.
Note: Maximum loop resistan ce allowed for wiri ng from control panel to Municipa l Bo x is 3 ohm s.
Appendix C: NFPA Standard-Specific Requirements
4XTB
4XTM (NOTIFIER)
Transmitter Module (activated polarities
shown)
+
Municipal Box Circuit
-
-
+
6 7
Figure 15 NFPA 72 Auxiliary Fire Alarm System
FIRE
AUXPROSS.CDR
Gamewell
Model M34-56
Local Energy
Municipal Box
The PDRP-1002 PN 51135: A 03/11/99 39
Appendix C: NFPA Standard-Specific Requirements
NFPA 72 Remote Station Fire Alarm System
Intended for connection to a polarity reversal circuit of a remote station receiving unit having compatible ratings. All connections are power limited and supervised with the exception of the reverse polarity loop. Supervision of the loop is the responsibility of the receiver.
NFPA 72 Remote Station Fire Alarm System
DRY
SUPPLEMENTARY
CONTACTS,
RATED
3A, 120 VAC
RESISTIVE 3A, 30 VDC RESISTIVE
REMOTE STATION MASTER BOARD (RSM-9)
N.C.2 N.O.2 POLE 2 N.C.1
N.O.1 POLE 1
A.C. CKT BREAKER 120 VAC
1.2 AMPS
9
10
SIGNALING
11
RELAY FOR BELLS AND
12
1
DRY
13
CONTACTS
14
CONTROL CARD (RSC) CIRCUIT SIDE
ZONE CARD(RSZ) CIRCUIT SIDE
OPTIONAL ZONE CARD (RSZ) CIRCUIT SIDE
OPTIONAL ZONE CARD (RSZ) CIRCUIT SIDE
OPTIONAL ZONE CARD (RSZ) CIRCUIT SIDE
OPTIONAL ZONE CARD (RSZ) CIRCUIT SIDE
OPTIONAL ZONE CARD (RSZ) CIRCUIT SIDE
OPTIONAL ZONE CARD (RSZ) CIRCUIT SIDE
OPTIONAL ZONE CARD (RSZ) CIRCUIT SIDE
OPTIONAL ZONE CARD (RSZ) CIRCUIT SIDE
K | | | | | | | | | | K
PRESS TO
RESET BATTERY CKT FUSE 8 AG 5 A 125 V
FILTER
CAP
--
-­K
--
--
--
K
2
8 7 6 5
BATT CONN
4 3 2
2 1
1 2 1
2
2 1
1 2 1 2
2 1
1 2 1 2 1 2
2 1
1
1
GROUNDING TERMINAL
N/C
BELL or HORN
} }
}
}
}
} }
120 VAC 1.2 A
}
50-60 Hz INPUT
+
-
H
10 K ELR
ALARM SIGNAL INPUT 3 ALARM SIGNAL INPUT 4 ALARM SIGNAL INPUT 5 ALARM SIGNAL INPUT 6
ALARM SIGNAL INPUT 7
ALARM SIGNAL INPUT 8
ALARM SIGNAL INPUT 9
Fire•Lite
RS82-9
Remote Station
Receiver
UL listed
-
+
-
+
Recommended Types: ELPOWER EP 1250C
+
POWER SONIC PS 1245
Power Transformer
1
Remote Alarm
2 3
Remote Trouble
4
POWER SONIC PS 1260 POWER SONIC PS 1265 YUASA NPG-12 or equivalent
-
MAXIMUM BATTERY SIZE
6.0 X 2.6 X 4.1 in. (15.24 x 6.6 x10.41
4XTM (NOTIFIER)
Transmitter Module
(activated polarities shown)
REMPROSS.CDR
Figure 16 NFPA 72 Remote Station Fire Alarm System
40 The PDRP-1002 PN 51135:A 03/11 / 99
NFPA 72 Remote Station Fire Alarm System
Appendix C: NFPA Standard-Specific Requirements

Troubleshooting Table

SYMPTOM PROBLEM SOLUTION
1. Check TB2 for proper connections. (TB3 for 4XB panels)
2. Remove all field wiring and install dummy ELR at output circuit. Check for supervisory voltage across it. (Normal -2.3 V). If problem persists, replace circuit board.
3. Removed dummy ELR, reconnect field wiring and measure voltage across output; (trouble -5V, short OV).
4. Check for ELR at last device.
5. Check field wiring.
1. Check TB4 for proper connections.
2. Remove field wiring for zone in trouble and install dummy ELR (4.7K for 24V; 2.2K for 12V). If problem persists, replace circuit board.
3. Check for ELR at last device.
4. Check field wiring.
Check battery connections
1. Remove batteries, check voltage across charger output (17 to 19V for 24V; 8-10V for 12V), otherwise replace circuit board.
2. Reconnect batteries, measure battery voltage at battery terminals. If voltage is less than 85% of rated voltage, allow them to charge for 48 hours.
3. If problem persists, replace batteries.
1. Remove field wiring from main panel and optional module(s) (if installed). Install dummy ELR (4.7K for 24V; 2.2K for 12V).
2. Remove both battery leads.
3. If trouble clears, connect one circuit at a time to pinpoint the problem.
4. If trouble doesn’t clear, replace circuit board.
Install optional module(s) or replace jumper if module(s) is not used.
1. Install dummy load if Municipal Box option isn’t used.
2. Check Municipal Box wiring. Remove field wiring and install ELR. If trouble
clears, look for faulty or incorrectly wired devices. Cut associated jumper OPT1 or OPT2.
1. Make sure module is properly installed.
2. Move disable switch SW1 on 4XZM to the left.
1. Make sure that 4XLM module is installed on J7 and J8.
2. Check field wiring.
Hit system reset. Check incoming power (TB5 ). (TB1 for 4XB
panels)
AC Power LED on
AC Power LED off
Circuit trouble LED on Noti fication appliance circuit trouble
Any of the right column yellow LEDs flashing
System trouble LED on
Any of the right column red LEDs on Short on initiating circuit wiring Disconnecting Municipal Box switch on 4XTM
does not create a trouble 4XZM: associated LED does not activate for alarm,
trouble or supervisory conditions RZA-4X piezo doesn’t sound for alarm, trouble or
supervisory conditions Micro Fail yellow LED on Microprocessor damaged. Replace circuit board. All RZA-4X LEDs stay on
System trouble LED on
Micro Fail yellow LED on Microprocessor damaged Replace circuit board.
Any of the right column yellow LEDs steady on
Power trouble LED on
Yellow LED on 4XTM on 4XTM 1. Move Municipal Box disconnect switch SW1 up
Initiating zone open circuit trouble
Zone Disable Check installation manual.
Missing or Disconnected
Battery trouble Batt yellow LED on
Ground fault trouble Earth yellow LED on
OPT1, OPT2 jumper cut
Municipal Box open circuit
Jumper for optional modules isn’t cut.
Optional module trouble
4XLM
Power wasn’t removed prior to installation.
Loss of main power Damaged circuit breaker Replace circuit board.
Low or damage battery
Table 8 Trouble Shooting Table
The PDRP-1002 PN 51135: A 03/11/99 41
Appendix C: NFPA Standard-Specific Requirements
NFPA 72 Remote Station Fire Alarm System
Notes
42 The PDRP-1002 PN 51135:A 03/11 / 99
NFPA 72 Remote Station Fire Alarm System
Appendix C: NFPA Standard-Specific Requirements
Notes
The PDRP-1002 PN 51135: A 03/11/99 43
Appendix C: NFPA Standard-Specific Requirements
Limited Warranty
NFPA 72 Remote Station Fire Alarm System
System Sensor
®
warrants its products to be free from defects in materials and workmanship for eighteen ( 18) months from the date of manufacture, under normal use and serv ice. Products are date stam ped at time of manufacture. The sole and exclusive obligation of
System Sensor
®
is to repair or r eplace, at is option, free of charge for part s and labor, any part which is d efective in materials or workmansh ip under normal use and service. For products not under
System Sensor
manufacturing date-stamp c ontrol, the warranty is ei ghteen (18) months from date of original purcha se by
System Sensor
®
distributor unle ss the installation in structions or catalog sets forth a s horter period, in which case the shorter per iod shall apply. This warranty is void if the product is altered, repa ired or serviced by anyone other
System Sensor
than
®
or its authorized di stributors or if there is a failure to maintain
the products and systems in which they operate in proper and workable manner. In
®
case of defect, phone System Sensor
Repair Department, RA #_____________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure.
This writing con stitutes the only warranty made by its products.
System Sensor
®
does not represent that its produc ts will prevent any
System Sensor
®
with respect to
loss by fire or other wise, or th at its p ro duc ts will in all cases provide the pr ot ec tion for which they are installe d or intended. Buyer acknowledges t hat
System Sensor
®
is not an insurer and as sumes no risk for loss or dam ages or the cost of a ny inconve­nience, transportation, damage, misuse, abuse, accident or similar incident.
SYSTEM SENSOR
®
GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER NO CIRCUMSTANCES SHALL
SYSTEM SENSOR
®
BE LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR INABILITY TO USE
SYSTEM SENSOR
®
PRODUCTS. FURTHERMORE,
SYSTEM SENSOR
®
SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF ITS PRODUCTS.
®
This warranty replaces all previous warranties and is the only warranty made by
System Sensor
®
. No increase or alteration, written or verbal, of the obligation of this
warranty is authorized.
System Sensor 3825 Ohio Avenue, St. Charles, IL 60174 1-800-SENSOR2 Fax: 630-377-6495
44 The PDRP-1002 PN 51135:A 03/11 / 99
Loading...