System Sensor PDRP-1002 User Manual

System Sensor 3825 Ohio Avenue St. Charles, IL 60174 1-800-SENSOR2 Fax: 630-377-6495
The PDRP-1002/PDRP-1002E Agent Release Control System
Manual
Document 51135
I56-1358-00
03/11/99 Revision:
PN 51135:A ECN 99-017
A
Installation Precautions
g
d
u
n
s
e
t
d
s
o
I o
n
o
b
o
s
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING
fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION
ensure proper system operation, this product must be tested in accordance with NFPA 72-1993 Chapter 7 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices must also be tested and proper system operation verified.
This system
32-120 30
and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a nominal
room temperature of 15-27
Verify that wire sizes are adequate
devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
- Sever al different sources of power can be connected to the
- System Reacceptance Test after Software Changes: To
O
meets NFPA requirements for operation at 0-49
O
F and at a relative humidity of 85% RH (non-condensing) at
O
C/86O F. However, the useful life of the system's standby batteries
O
C/60-80O F.
for all initiating device loops. Most
C/
Fire Alarm System Limitati on s
An automatic fire alarm system
detectors, heat detectors, manual pull stations, audible warning devices and a fire alarm control with remote notification capability can provide early warning of a developing fire. Such a system, howev er, does not assure protection against property damage or loss of life resulting from a fire.
Any fire alarm system may fail for a variety of reasons: Smoke detectors
detectors such as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second floor detector , for example, may not sense a first floor or basement fire. Furthermore, all types of smoke detectors - both ionization and photoelectric types, have sensing limitations. No type of smoke detector can sense every kind of fire caused by carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with matches, or arson.
IMPORTANT!
the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling and /or power. If
detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire.
may not sense fire where smoke cannot reach the
Smoke detectors must be installed in the same room as
- typically made up of smoke
FCC Warning
Like all solid state electronic devices
erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightnin transients and interferences, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommende due to an increased susceptibility to nearby lightning strikes. Cons with the Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries
circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies
or punching of the enclosure. When possible, make all cable entrie from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer and printed circuit board location.
Do not tighten screw terminals
may damage threads, resulting in reduced terminal contact pressur and difficulty with screw terminal removal.
This system
yourself with a proper wrist strap before handling any circuits so tha static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions
programming manuals. These instructions must be followed to avoi damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.
While installing a fire alarm system may make lower insurance rates possible, it is not a substitute for fire insurance!
Audible warning devices
devices are located on the other side of closed or partly open doors are located on another floor of a building.
A fire alarm system will
AC power f ails, the system will operate from standby batteries only f a specified time.
Rate-of-Rise heat detectors
over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist.
Equipment used in the system
with the control panel. It is essential to use only equipment listed fo service with your control panel.
T
elephone lines
central monitoring station may be out of service or temporarily disabled.
The most common cause
inadequate maintenance. All devices and system wiring should be tested and maintained by professional fire alarm installers following written procedures supplied with each device. System inspection a testing should be scheduled monthly or as required by National and/ local fire codes. Adequate written records of all inspections should kept.
contains static-sensitive components Always ground
in the installation, operating and
such as bells may not alert people if the
not operate without any electrical power.
may be subject to reduced sensitivity
needed to transmit alarm signals from a premise to
of fire alarm malfunctions, however, is
, this system may operate
prior to removing or inserting
prior to any drilling, filing, reami
more than 9 in-lbs. Over tightenin
may not be technically compatible
WARNING:
frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications, It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense.
This equipment generates, uses and can radiate radio
2 The PDRP-1002 PN 51135:A 03/11 / 99
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiati noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectrique depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
The PDRP-1002 PN 51135: A 03/11/99 3
4 The PDRP-1002 PN 51135:A 03/11 / 99

NFPA Standards

This control panel complies with the following NFPA standards: NFPA 12 CO
NFPA 12A Halon 1301 Extinguishing Systems NFPA 12B Halon 1211 Extinguishing Systems NFPA 72 Central Statio n Signaling Systems (Automatic, M a nual, and Waterflow). Protected Premises Unit (Requires NOTI•FIRE 911AC DACT or MS-5012 Slave Communicat or)* NFPA 72 Local (Automatic, Manual, Waterflow and Sprinkler Supervisory) Fire Alarm Systems NFPA 72 Auxiliary (Automatic, Manual, and Waterflow) Fire Alarm Systems. (Requires 4XTM) NFPA 72 Remote Station (Automatic, Manual, and Waterflow) Fire Alarm Systems. Requires 4XTM, NOTI•FIRE 911AC DACT* NFPA 2001 Clean Agent Fire Extinguish in g Sys te m s
*Applications which require the NOTI•FIRE 911AC are not FM approved.

Additional Information

Before proceeding, the installer should be familiar with the following documents and standards:
NFPA Standards:
NFPA 12 CO2 Fire Extinguishing Systems NFPA 12A Halon 1301 Fire Ext inguishing Systems
NFPA 12B Halon 1211 Fire Extinguishing Systems NFPA 72 Installation, Maintenance and Use of Central Station Signaling Systems NFPA 72 Local, Auxiliary, Remote Station and Proprietary Fire Alarm Systems NFPA 72 Automatic Fire Detectors NFPA 72 Installation, Maintenance and Use of Notification Appliances for Fire Alarm Systems NFPA 72 Testing Procedures for Signaling Systems NFPA 2001 Clean Agent Fire Extinguish in g Sys te m s
Extinguishing Systems (High Pressure Only)
2
Underwriters Laboratories Documents:
UL 38 Manual Actuated Signaling Boxes UL 217 Smoke Detectors, Single and Multiple Station UL 228 Door Closers - Holders for Fire Alarm Systems UL 268 Smoke Detectors for Fire Alarm Systems UL 268A Smoke De te c t o r s for D uc t Ap plications UL 346 Waterflow Indicators for Fire Alarm systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Alarm Systems UL 864 Standard for Control Units for Fire Alarm Systems UL 1481 Power Supplies for Fire Alarm Systems UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for the Hearing Impaired CAN/ULC-S524-M91 Standard for Installation of Fire Alarm Systems CAN/ULC-S527-M87 Standard for Control Units for Fire Alarm Systems
Other:
NEC Article 300 Wiring Methods NEC Article 760 Fire Alarm Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction Notifier Device Compatibility Document, 15378 ADA Americans with Disabilities Act
The PDRP-1002 PN 51135: A 03/11/99 5

1 The PDRP-1002/PDRP-1002E

1 The PDRP-1002/PDRP-1002E

Features

Microprocessor-controlled
Power-limited on all circuits except Municipal Box output
Alarm and trouble resound
Four Class A (Style D)/Class B (Style B) Initiating Device Circuits
Two Class A (Style Z)/Class B (Style Y) Notification Appliance circuits
Two Class B (Style Y) Release Circuits
General alarm and trouble relays
Optional module for 4 zone/function relays (4XZM)
Optional transmitter module (4XTM). Complies with NFPA 72 Auxiliary and Remote Station Fire Alarm systems
Optional volt/amp meter module (4XMM)
Optional supervised remote annunciator (RZA-4X)
Requires LED Interface Module (4XLM)
Optional digital communicator (NOTI•FIRE 911AC)*
Complies with NFPA 72 Central Station and Remote Station Fire Alarm Systems
Supervisory Input Option
Delay timer (adjustable)
Three abort function options
Designed for suppression standards NFPA 12, 12A and 12B
Disable/enable controls per initiating zone
Last Event Recall
Battery/Earth fault supervision
Fuse protection on all Notification/Release Circuits
RMS regulated output power, 2.25 amps
7 amp/hour to 15 amp/hour battery options, up to 90 hours standby
Resettable and non-resettable regulated power outputs
Extensive transient protection
Watchdog timer to supervise microprocessor
Output circuits protected against false activations
Slide-in zone identification labels
Steel cabinet 14.5 in (368.3 mm) wid e b y 16 i n ( 406. 4 mm) high b y 5 in (127 m m) deep
Dead-front dress panel option (DP-4X)
Trim ring for flush mount between 16 in (406.4 mm) center studs (TR-4XR)
Abort and manual release circuits
Cross-zone option
Input Circuits
Applications which require the NOTI•FIRE 911AC are not FM approved
*
.

Circuits

Input Circuits
Detector Zone 1, Class A (Style D)/Class B (Style B) Detector Zone 2, Class A (Style D)/Class B (Style B) Abort, Class A (Style D)/Class B (Style B) Manual Release, Class A (Style D)/Class B (Style B)
Output circuits (optional auxiliary relays track these four circuits)
Notification Appliance Circuit 1, Class A(Style Z)/Class B (Style Y) Notification appliance Circuit 2, Class A(Style Z)/Class B (Style Y) Releasing Circuit 1, Class B (Style Y) Releasing Circuit 2, Class B (Style Y)/Supervis ory Input, Class B (Style B)
6 The PDRP-1002 PN 51135:A 03/11 / 99
Front Panel Control Switches
1 The PDRP-1002/PDRP-1002E
Front Panel Control Switches
Switch 1 Tone Silence Switch 2 Alarm Silence Switch 3 Alarm Activate Switch 4 System Reset
Ground
Neutral
Hot
Transformer
J1
TB5
J2
Optional Ammeter Connection
J9
Batteries
­+
Optional
J3
VoltmeterConnection
+24VU
+ -
+ -
TB1
AC Circuit Breaker
24 VVU
RMS-REGULATED
24 VR
+24VR
Notification Appliance
Circuits
Class A (Style Z) Class B (Style Y)
1234
24 VNR
REGULATED
REGULATED
NON-RESETTABLE
RESETTABLE
+24VNR
B+ A+ A- B-
+ -
B+ A+ A- B-
Releasing
Circuits
B+ B-
B+ B-
Relays
TroubleAlarm
Contacts Contacts
NO NC C NO NC C
Initiating Device
Circuits
Class A (Style D) Class B (Style B)
Abort
Switch
Manual Release
1234
B+ A+ A- B-
B+ A+ A- B-
B+ A+ A- B-B+ A+ A- B-
TB4
TB2
TB3
JP 1
NO DACT
DACT
SUPV 2
4XTM
GEN ALM2
or
4XLM
or
4XZM
*Jumper “OPT 1” must be cut if a module is installed in this position
OPT 1
*
4XTM
or
4XLM
or
4XZM
*Jumper “OPT 2” must be cut if a module is installed in this position
O
123456
Cross Zone
Supervisory
Delay Timer
N
SW1
Abort Option
Abort Option
Delay Timer
Micro Fail LED
BATT
EARTH
Ground Fault LEDBattery Fail LED
Figure 1 PDRP-1002/P DRP-1002E Installatio n Di agram
The PDRP-1002 PN 51135: A 03/11/99 7
OPT 2
*
4XRP1002.cdr
1 The PDRP-1002/PDRP-1002E
4XTM.cdr
4XLM.cdr

Optional Boards

The PDRP-1002/PDRP-1002E has mounting slots for two option boards. Any two of the three option modules may be installed.
Transmitter Module (4XTM - NOTIFIER)
The Transmitter Module provides a supervised output for local energy municipal box transmitter (for NFPA 72 Auxiliary Fire Alarm System) and alarm and trouble reverse polarity circuits (for NFPA 72 Remote Statio n Fi re Alarm System). Also included is a DISABLE switch and disable trouble LED.
As a jumper option, the alarm reverse polarity circuit will open on trouble if no alarm exists.
LED Interface Module (4XLM - NOTIFIER)
The LED Interface Module supports the RZA-4X Remote Annunciator module. Annu nciator wi ring is superv ised for open conditions by this module. The Annunciator Driver Module mounts to the main board, occupying on e of the two option connectors.
Transmitter Module (4XTM - NOTIFIER)
Zone Relay Module (4XZM - NOTIFIER)
The Zone Relay module provides Form-C contacts for the following:
As a jumper option, the first four relays described below can be made silenceable.
DIP 1=OFF Either Zone
Alarm Detected First Alarm Alarm Detected First Alarm Alarm Detected Second Alarm Alarm Detected Second Alarm Release 1 Release 1 Release Release Release 2 Release 2 Not Used Not Used
8 The PDRP-1002 PN 51135:A 03/11 / 99
DIP 1=ON Cross Zone
If Supervisory (DIP 2=ON) Either Zone Cross Zone
4XZM.cdr
Transmitter Module (4XTM - NOTIFIER)
RZA4Xfr.cdr
voltmter.cdr
Transmitter Module (4XTM - NOTIFIER)
For Local Energy Municipal Box service (NFPA 72 Auxiliary Fire Alarm System) Supervisory current: 5.0 mA Trip current: 0.35 amps. (Subtracted from Notification Appliance power) Coil Voltage: 3.65 VDC Coil resistance: 14.6 ohms Maximum allowable wire resistance between panel and trip coil: 3 ohms Municipal Box wiring can leave the building
For Remote Station service (NFPA 72 Remote Station Fire Alarm System):
Maximum load for each circuit: 10mA Reverse polarity output voltage: 24 VDC Remote Alarm and Remote Trouble wiring can leave the b uilding
LED Interface Module (4XLM - NOTIFIER)
Maximum voltage/current, each output: 27.6V/8mA
Note: Outputs are power limited
Zone Relay Module (4XZM - NOTIFIER)
Dry Form-C contacts rated: 2.0 amps @ 30VDC (resistive), 0.5 amps @ 30 VAC (resistive)
1 The PDRP-1002/PDRP-1002E

Remote Annunciator

Optional Meters

Remote Annunciator (RZA-4X - NOTIFIER)
The Remote Annunciator mounts on a standard single­gang box, and provides LED indication of the same functions as the zone relay module. For example with DIP 1=ON and DIP 2=OFF:
One Zone in Alarm (red)
Two Zones in Alarm (red)
Releasing Circuit 1 (red)
Releasing Circuit 2 (red)
System Trouble (yellow)
A Local Trouble Sounder and Silence Switch are also provided. All LED wiring is supervised for open conditions. Any open condition will cause the System Trouble LED to illuminate.
Note: The Remote Annunc iator requir es the use of an LED Interface m od ule (4XLM).
Voltage, Current Meters (4XMM - NOTIFIER)
The Meter Module provides a voltmeter to measure the voltage across the batteries and an ammeter to measure the charging current to the batteries. The meters are provided as an assembly that mounts to the lower left­hand corner of the cabinet.
20
10
DC VOLTS
0
30
5
0
5
DC AMPERES
The PDRP-1002 PN 51135: A 03/11/99 9
1 The PDRP-1002/PDRP-1002E
AC Circuit Breaker
Acctbrkr.cdr

Specifications

AC Power
For the PDRP-1002: 120 VAC, 50/60 Hz, 1.2 amps For the PDRP-1002E: 220/240 VAC, 50 Hz, 0.6 amps Wire size: minimu m #14 AWG with 600V insulation
Battery (lead acid only)
Maximum Charging Circuit: 27.6V, 1.5 amps Maximum Battery Capacity: 15 AH. (Batteries larger than 12 AH require NOTIFIER #BB-17 or other UL listed external battery cabinet.)
Initiating Device Circuits
Power-limited circuitry Operation: Class A (Style D)/Class B (Style B) Normal Operating Voltage: 24 VDC (ripple = 1.0V peak-to-peak) Alarm current: 15 mA minimum Short circuit current: 40 mA maximum Maximum detector current in standby: 2 mA (max) per zone Maximum loop resistance: 200 ohms End-of-line resistor: 4.7K, 1/2-Watt (NOTIFIER part # 71252, UL listed) Detector loop current is sufficient to ensure operation of one alarmed detector per zone. Supervisory current: 5 mA (including end-of-line resistor)
AC Power
Notification Appliance and Releasing Circuits
Power-limited circuitry Maximum allowable voltage drop due to wiring: 2 VDC Normal Operating Voltage: 24 VDC Total current available to all external devices: 2.25 amps
Maximum signaling current per circuit: 1.5 amps End-of-line resistor: 4.7K, 1/2-Watt (NOTIFIER part # 71252, UL listed)
Alarm and Trouble Relays
Dry Form-C contacts rated: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive). All relays must be connected to a power limited power supply.
Four-wire Smoke Detector Power
Up to 200 mA is available for powering 4-wire smoke detectors. Maximum ripple voltage: 1.0 V p/p
Non-resettable Power
Total DC current available from this output is up to 200 mA (subtracted from 4-wire smoke power). Maximum ripple voltage: 1.0 V p/p
RMS Regulated Power
Total DC current available for powering external devices is 0.5 amp (subtracted from
2.25 amps available to notification appliance circuits).
Maximum ripple voltage: 100 mV p/p
Note: For device compatibility, refer to Device Compatibility Chart.
10 The PDRP-1002 PN 51135:A 03/11 / 99
RMS Regulated Power
Door = 16.125 in. (409.58 mm) Backbox = 16 in. (406.4 mm)
Door = 14.625 in. (371.48 mm) Backbox = 14.5 in. (368.3 mm)
1 The PDRP-1002/PDRP-1002E
Cabinet = 5.375 in. (136.53 mm) Backbox = 4.750 in. (120.65 mm)
TR-4XR RUBY RD STEEL 16 GA.
14.594 in. (370.69 mm)
Optional Trim Ring
TR-4XR
Figure 2 Cabinet Dimensions
1.5 in (38.1 mm)
16.094 in. (408.79 mm)
RPCABDIM.cdr
The PDRP-1002 PN 51135: A 03/11/99 11

2 System Operation

2 System Operation
WARNING:When used for CO2 releasing applications, observe proper precautions as stated in NFPA 12. Do not enter the protected space unless physical
!
lockout and other safety procedures are fully completed. Do not use software disable functions in the panel as lockout.

System Status LEDs

Alarm, Trouble and Supe rvisory LEDs will flash on and off until the event(s) has been acknowledged (TONE or ALARM SILENCE), at which point the LED will illuminate steadily.
AC POWER
Green LED that illuminates steadily to indicate presence of AC power.
SYSTEM ALARM
Red LED that flashes when an alarm occurs.
RELEASE
Red LED that illuminates steadily when release occurs.
RMS Regulated Power
SUPERVISOR Y
Yellow LED that flashes upon activation of a supervisory device (such as tamper switch) on Output 4 if selected (see “Setting Mode of Operation” in Section 3 of this manual).
SYSTEM TROUBLE
BATT
EARTH
MICRO
FAIL
Yellow LED that flashes for any trouble condition, including those associated with option boards.
CIRCUIT TROUBLE
Yellow LED that flashes for trouble conditions on output circuits (notification and releasing circuits).
ALARM SILENCED
Yellow LED that illuminates steadily when the ALARM SILENCE switch has been pushed after an alarm.
POW ER TROUBLE
Yellow LED that flashes for low or disconnected batteries and earth fault conditions.
BA TT
Yellow LED that illuminates steadily on mother boar d when battery is low or not detected (not visible through door).
EARTH
Yellow LED that illuminates steadily on mother boar d during a ground fault condition (not visible through door)
4Xoper2.cdr
MICRO FAIL
Yellow LED that illuminates on motherboard when watchdog timer de tects microprocessor failure (no t visi b le throu gh doo r)
12 The PDRP-1002 PN 51135:A 03/11 / 99
RMS Regulated Power

Control Switches

2 System Operation
Tone Silence
Acknowledge alarms, troubles and supervisories. The panel has alarm and trouble resound with LED flash of new conditions. The flashing trouble LED(s) illuminate steadily on TONE SILENCE and the piezo sounder silences. A second trouble will resound the piezo. The piezo has three sounds for alarm, trouble, and supervisory. Trouble cond i tio ns are self- res to ring . Alar ms latch and require RESET to clear.
Alarm Silence
Acknowledge for alarms and supervisories. The ALARM SILENCE switch will silence the local piezo, change any flashing alarm LEDs to steady, and turn off the notification circuits (not the releasing circuits). The “ALARM SILENCED” LED will illuminate. Alarm silence is a latching function and requires a RESET to clear.
Alarm Activate
The ALARM A CTIVATE switch may be used to activate Notification Appliance Circuits. ALARM ACTIVATE also activates the System Alarm relay. ALARM Activate is a latching function. Pressing ALARM SILENCE silences the notification circuits and System Alarm Relay and lights the Alarm Silenced LED. Pressing RESET returns the system to normal.
System Reset
The RESET switch breaks power to all initiating circuits, 4-wire smoke power and option boards and will clear any activated output circuits. If any alarms or troubles still exist after reset, they will reacti vate th e panel. Holding RESET down will perform a LAMP TEST function and will activate the piezo sounder.
4XPTL.cdr

Zone Status LEDs

The alarm and/or trouble LED(s) will flash until the event(s) has been acknowledged (TONE or ALARM SILENCE), at which point the LED(s) will illuminate steadily.
ABORT TROUBLE LED
MANUAL RELEASE TROUBLE LED
The PDRP-1002 PN 51135: A 03/11/99 13
ALARM LED
TROUBLE LE D
ALARM LED
TROUBLE LE D
ABORT LED
MANUAL RELEASE
Zone 1
Zone 2
Abort
Manual Release
2 System Operation

Supervisory

Zone Disable

RMS Regulated Power
Output circuit #4 is used as an input for monitoring supervisory devices such as valve tamper switches (note that SW1 DIP switch #2 must be set “ON” -- see section “Setting Mode of Operation”) By setting Switch short circuit on this input (activation of a N.O. contact) will cause the supervisory LED to flash. The piezo sounder will generate a unique sound. TONE SILENCE will silence the piezo and cause the LED to illuminate steadily. Supervisory signals latch and require RESET to clear . An open circuit will be reported as a circuit trouble.
If a zone has been disabled, an alarm that occurs on that zone will flash the red zone LED, but not the p iez o or any output circuit.
If both power sources are removed from the system, all zones will be re-enabled upon restoration of power. Disable status will be lost .
The Zone Disable routine m akes use of the four panel switches as follows:
1. Press and hold in the TONE
SILENCE switch.

Last Event Recall

2. With the TONE SILENCE switch
held in, press (in sequence) the ALARM SILENCE switch, the ALARM ACTIVATE switch, and then the RESET switch.
3. The Zone 1 Alarm LED will flash.
4. To disable Zone 1, press the RESET switch. The Zone 1 yellow LED will light to
show that the zone is disabled.
Note: The RESET switch toggles disable status for the selected zone.
5. To select the next zone, press the ALARM SILENCE switch.
6. To select the previous zone, press the ALARM ACTIVATE switch.
7. When disable selections are complete, release the TONE SILENCE switch.
If any zone has been disabled, the trouble relay will activate and System Trouble LED will flash.
Last Event Recall allows the user to display the previous panel status. The last event recall uses the four panel switches as follows:
1. Press and hold in the TONE SILENCE switch.
4XPTL.cdr
2. With the TONE SILENCE switch held in, press (in sequence) the RESET switch,
the ALARM ACTIVATE switch, and then the ALARM SILENCE switch.
3. Last Event is displayed.
4. Release the TONE SILENCE switch to return to normal operation.
Note: To clear the last event buffer, press RESET twice.
14 The PDRP-1002 PN 51135:A 03/11 / 99
Loading...
+ 30 hidden pages