System Sensor PS24LO, PS24LOA, PS24LOW, PS24LOWA, PS24M Installation And Maintenance Instructions Manual

...
INSTALLATION AND MAINTENANCE INSTRUCTIONS
F
I R E
60% 60%
100%100%
100% (REF)
7%
60% 60%
7%
PA400*, PS12LO(W), PS12M(W), PS24LO(W)*, and PS24M(W)* Electronic Mini-Sounders and
1-800-SENSOR2, FAX: 630-377-6495
A Division of Pittway
Optional Strobes
*ULC models add suffix “A”; available in 24VDC only
Specifications
PA400 Sounder
Operating Voltage: 9.6VDC (absolute min.) to 33VDC (absolute max.) Current Drain: 12 mA at 12 volts
15 mA at 24 volts
Temperature Range: -10
Sound Output: Greater than 90 dBA measured in anechoic room at 10 feet, 24 volts.
PS12/24 Strobe
PS12LO(W) PS12M PS24LO(W) PS24M(W) PS24LOA(W) PS24MA(W) Panel Voltage 12–17 VDC 12–17 VDC 22.5 - 30 VDC 22.5 - 30 VDC 22.5 - 30 VDC 22.5 - 30 VDC Max. Current Drain @
Listed Panel Voltage Min. Light Output @
100% Viewing Angle (See Fig 2)
50 mA 180 mA 25 mA 75 mA 50 mA 180 mA
1.5 candela 15 candela 1.5 candela 15 candela 1.5 candela 15 candela
Temperature Range: 0°C to 49°C (32°F to 120°F) Under no circumstances can the PS24 voltage exceed 33VDC or be less than 18VDC.
Under no circumstances can the PS12 voltage exceed 18.7VDC or be less than 9.6VDC. To calculate battery requirements, use current values shown above. However, note that there is an in-rush current associated with strobe power-up. The information in Figures 3 and 4 is useful when selecting fuse values. As Figure 3 shows, 12V strobe in-rush current typically peaks at 3A and drops to nominal in 600 current typically peaks at 7.0A and drops to nominal in 800
Figure 3. 12 volt strobe in-rush current:
1A/div
o
C to +60oC (14oF to 140oF)
0°C to 49°C (32°F to 120°F) with strobe added
See Figure 1 for other voltages. 82 dBA minimum measured in UL reverbarant room (75 dBA minimum with strobe)
Figure 1: Figure 2:
MODEL
µ
S.
92
91
90
89
dBA output
88
87
86
10 12 14 16 18 20 22
Voltage
µ
S. In a 24V strobe (Figure 4), in-rush
Figure 4. 24 volt strobe in-rush current:
1A/div
200
µ
S/div
General Information
The National Fire Protection Association has published codes, standards, and recommended practices for the installation and use of the above appliances. Therefore, the installer must be fa­miliar with these requirements, with local codes, and any special requirements of the authority having jurisdiction.
Model PA400
The PA400W (white) and PA400R (red) Piezo Alert electronic sounder and optional supplementary signal strobes are intended to be connected to the alarm indicating circuit of a UL-listed 12 or 24 VDC fire alarm control panel. The models PS12 and PS24 op­tional strobe additions to the PA400 require a 12 VDC or 24 VDC
Technical Manuals Online! - http://www.tech-man.com
200
µ
S/div
panel, respectively and are able to operate from a full-wave recti­fied, unfiltered supply.
Installation Notes
The wiring must be in compliance with all codes and must not be of such length or wire size that would cause the appliance to op­erate outside of its published specifications. The appliances must also be tested after installation in accordance with the control panel manufacturer’s test procedure. NOTE: Do not loop wires under terminal screws. Wires
connecting the device to the panel must be broken at the device screw terminal in order to maintain electrical supervision.
1 I56-305-07
Mounting
PA400 Sounders
1. The PA400 is intended for mounting to a standard 2-1/2" deep single-gang box which allows sufficient clearance for conduit entrance.
2. The PA400 is compatible with DC line supervision. The Piezo Alert is polarized and has terminals marked with polarity. Ap­ply positive supply voltage to the (+) terminal and negative supply voltage to the (–) terminal. (See Figure 5.)
3. Mount the appliance to the electrical outlet box using the two mounting screws supplied.
4. Field repair of the PA400 should not be attempted. Return to factory for repair or replacement.
PS12 or PS24 Strobes
These optional strobes are interconnected to the PA400 by first re­moving the two mounting screws from the sounder. Use a small screwdriver to punch out the skinned-over areas as indicated in Figure 6. Install the adapter plate on top of the sounder and screw the combined sounder and adapter plate to the electrical outlet box. Make sure field wiring terminals are oriented in the upward position when mounted in the outlet box. Next, slide the strobe directly into the slots in the plates. The positive solder lug may be colored red or marked with a plus sign (+). This lug must be in the slot closest to the field wiring terminals. Grasp the catch area on each end of the strobe and squeeze while applying inward force. Make sure the strobe catches fully engage the slots in the adapter plate and that no gap appears at the interface between the strobe and adapter plate.
Figure 5:
From
control
panel
or
previous
To
EOL
or
Next
Device
device*
*NOTE: Shown with control panel in alarm. Panel polarity reversed in supervisory condition.
A78-1315-00.
Figure 6:
A78-1314-01
The Limitations of Sounders and Strobes
System Sensor’s sounder and signal strobe is designed to provide fire and security hazard warning.
The strobe is for supplementary signaling use only. The sounder or sounder/strobe combination will not work without power. The sounder or sounder/strobe gets its power from the fire or se-
curity panel monitoring the alarm system. If power is cut off for any rea­son, the sounder or sounder/strobe combination will not provide the desired audible or visual warning. The sounder may not be heard. The loudness of the sounder meets or exceeds current Underwriters Laboratories’ standards. however, the sounder may not alert a sound sleeper or one who has recently used drugs or has been drinking alcoholic beverages. The sounder may not be heard if it is placed in an area which is isolated by a closed door, or if it is located on a different floor from the person in hazard or if placed too far away to be heard over the ambient noise such as traffic, air conditioners, machin-
Three-Year Limited Warranty
System Sensor warrants its enclosed sounder/strobe to be free from de­fects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this sounder/strobe. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the sounder/strobe which is found to be defective in materials or work­manship under normal use and service during the three year period com­mencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Repair Depart-
A78-1778-00
WARNING
ery, or music appliances that may prevent alert persons from hearing the alarm. The sounder may not be heard by persons who are hearing im-
paired. The signal strobe may not be seen. The electronic visual warning signal
meets or exceeds current Underwriters Laboratories’ standard 1638. The visual warning signal is suitable for direct viewing and must be installed within an area where it can be seen by building occupants. The strobe must not be installed in direct sunlight or areas of high light intensity where the visual flash might be disregarded or not seen. The strobe may
not be seen by the visually impaired. The signal strobe may cause seizures. Individuals who have a positive
photic response to visual stimuli with seizures, such as epileptics, should avoid prolonged exposure to environments in which strobe signals, in­cluding this strobe, are activated.
ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifica­tions, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or conse­quential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
Technical Manuals Online! - http://www.tech-man.com
2 I56-305-07
© System Sensor 1996
INSTALLATION AND MAINTENANCE INSTRUCTIONS
PS12/24ADA Series Strobes with Mini-sounder for Fire Protective Signaling Systems
Table 1. PS12/24ADA Series Electrical Ratings
Model
PS24110ADA PS24110ADAW
PS2475ADA PS2475ADAW
PS2415ADA PS2415ADAW
PS1215ADA PS1215ADAW
PS241575ADA PS241575ADAW
PS121575ADA PS121575ADAW
Supply Voltage Range
20-30V 225
20-30V 185
20-30V 90
12-17V 182
20-30V 108
12-17V 240
* Horn current is 12mA@12VDC, 15mA@24VDC
Operating Current from Regulated Supply Operating Current from
Average
Operating
Current
Horn/
Strobe*
Average
Operating
Current
Strobe 
Only
210
170
75
170
93
225
Current
Peak
Peak
Inrush
Current
(mA)
10.5V/17V
Current
(mA in
access of
Peak)
(mA)
20/30V
470/500 0
385/400 0
160/180 0
360/380 0
210/220 0
510/560 0
Average
Operating
Current
(mArms)
Horn/Strobe*
260
215
105
212
135
285
Full-Wave Rectified Unfiltered Supply
Average
Operating
Current
(mArms)
Strobe Only
245
200
90
220
120
270
Peak Current
Peak Current
(mA) 20Vrms/ 30Vrms
400/500
320/370
275/290
275/290
10.5Vrms/ 17Vrms
330/380
500/530
(mA)
Inrush Current
(Amps in
excess
of Peak)
0.08
0.04
0.02
0.02
1
0.02
A Division of Pittway
1-800-SENSOR2, FAX: 630-377-6495
NOTE: In-rush current du-
ration is less than 20 microseconds (0.00002 seconds).
NOTICE: This manual should be left with the owner/user of this equipment.
General Description
The National Fire Protection Association has published standards and recommended practices for the installation and use of the above appliances. It is recommended that the installer be familiar with these requirements, with local codes, and any special requirements of the local fire authority having jurisdiction. The Piezo electronic sounder and signaling strobe are intended to be connected to the alarm indicating circuit of a UL-listed fire alarm control panel. Both are compatible with DC line supervision. The electronic sounder can be connected to either 12 or 24 VDC panels. Models PS2415ADA, PS2475ADA, PS24110ADA, and PS241575ADA require 24 volt panels. Models PS1215ADA and PS121575ADA require 12 volt panels. Panels may have full-
Figure 1. Vertical and horizontal light distsribution:
wave rectified, unfiltered power supplies. The strobes produce one flash per second (nominal) with continuous nominal voltage applied.
The sounder/strobe strobe is rated for 0° to 49° C and is NOT suitable for outdoor use.
The rated light output of the PS2415ADA, PS1215ADA, PS241575ADA, and PS121575ADA is 15 cd (See Figure 1).
The rated light output of the PS2475ADA is 75 cd (See Figure 1).
The rated light output of the PS24110ADA is 110 cd (See Figure 1).
NOTE: The 15/75 cd strobe has been measured to be 75 cd
@ 0° viewing angle.
Percent of
45˚
90˚ –90˚
–45˚
LIGHT
Degrees Rating 0 100
5 - 25 90 30 - 45 75 50 55 55 45 60 40 65 35 70 35 75 30 80 30 85 25 90 25
D900-08-00 1 I56-732-04
Technical Manuals Online! - http://www.tech-man.com
Greater than 90 dBA measured in anechoic room at 10 feet, 24 volts (see Figure 2 for other voltages); 79 dBA minimum measured in UL reverberant room @ 12V and 82 dBA @ 24V.
Figure 2:
90
89
NOTE: All models can be powered using full wave recti-
fied unfiltered supplies. Under no circumstances can PS24ADA series devices input voltage exceed 33 VDC or be less than 16 VDC (16-33Vrms for full­wave rectified, unfiltered supplies). Under no cir­cumstances can a PS12ADA series device input voltage exceed 18.7 VDC or be less than 9.6 VDC (9.6 - 18.7Vrms for full-wave rectified, unfiltered supplies).
Installation
A. General:
Phillips head screws are used to attach PS12/24ADA to semi-flush plate or the electrical outlet box. Slotted head screws are used to attach semi-flush plate to outlet box. See Figures 3 and 4 for wiring methods.
NOTE: Do not loop wires under the terminal screw. Wires
connecting the device to the panel must be broken at the device terminal connection in order to maintain electrical supervision.
The PS12/24ADA is designed for wall mounting ONLY.
It is intended for mounting to a standard 2-1/2" deep single gang box which allows sufficient clearance for conduit entrance.
88
87
dBA output
86
85
84
10 12 14 16 18 2 0 22
Voltage
All strobes must be mounted so that the top of the lens is 24 inches (61cm) below ceilings or as required by the authority having jurisdiction.
B. Sounder/Strobe combination mounting:
1. Surface Mount: (See Figure 5)
2. Semi-Flush Mount: (See Figures 6 and 7)
3. Semi-Flush Mount with Plaster Ring or Double Gang Box: (See Figure 8)
Installation procedures must conform to all applicable codes and the requirements of the authority having jurisdiction.
NOTE: The rated output of the sounder is specified at 10
feet. It cannot be assumed that the output will meet the NFPA standard of 15 dB over ambient noise at all locations within a room. Additional sounders may be needed to ensure sound output level complies with NFPA requirements.
Figure 3. Operating horn and strobe in tandem:
From Control Panel or
Next
Device
Previous Device
Polarity shown in alarm condition. Polarity is reversed in supervisory condition.
D900-08-00 2 I56-732-04
EOL
A78-2663-00
Figure 4. Operating horn and strobe independently:
To
or
From Control Panel or Previous Device
Blk
Red
Cut and Remove for Independent Operation
Note: Remove paper
shield; cut and remove red and black wires between the horn and strobe.
When finished wiring, place paper shield back on unit.
Polarity shown in alarm condition. Polarity is reversed in supervisory condition.
Device
Technical Manuals Online! - http://www.tech-man.com
To
Next
A78-2664-00
C
C
D
D
C
C
Screw types used in Figures 5 – 8 below:
A=#6-32x1-1/2" Phillips Oval Head B=#8-32x5/8" Slotted Pan Head C=#6-32x5/8" Slotted Pan Head D=#8 Phillips Oval Head Sheet Metal
Figure 5. Surface mount to single gang box:
A
A
1) Complete Field Wiring (see Figure 3)
2) Screw PS12/24ADA to Outlet Box with A Screws
A78-2602-00
Figure 6. Semi-flush mount to single gang box:
A
A
A78-2604-00
1. Complete Field Wiring (See Figure 3)
2. Screw PS12/24ADA to Outlet Box with A Screws
Figure 7. Semi-flush mount to 4" box:
B
B
D
D
A78-2603-00
1. Screw Semi-Flush Plate to 4" Box with B Screws
2. Complete Field Wiring (See Figure 3)
3. Screw PS12/24ADA to Semi-Flush Plate with D Screws
D900-08-00 3 I56-732-04
Technical Manuals Online! - http://www.tech-man.com
Figure 8. Semi-flush mount with plaster ring or double gang box:
1. Screw Semi-Flush Plate to Box with C Screws
A78-2605-00
2. Complete Field Wiring (See Figure 3)
3. Screw PS12/24ADA to Semi-Flush Plate with D Screws
The Limitations of Sounder/Strobes
The Sounder and/or Strobe will not work without power. The sounder/ strobe gets its power from the fire/security panel monitoring the alarm system. If power is cut off for any reason, the sounder/strobe will not pro­vide the desired audio or visual warning.
The Sounder may not be heard. The loudness of the sounder meets (or exceeds) current Underwriters Laboratories’ standards. However, the sounder may not alert a sound sleeper or one who has recently used drugs or has been drinking alcoholic beverages. The Sounder may not be heard if it is placed on a different floor from the person in hazard or if placed too far away to be heard over the ambient noise such as traffic, air condition­ers, machinery or music appliances that may prevent alert persons from hearing the alarm. The Sounder may not be heard by persons who are
hearing impaired.
WARNING
must be installed within an area where it can be seen by building occu­pants. The strobe must not be installed in direct sunlight or areas of high light intensity (over 60 foot candles) where the visual flash might be disre­garded or not seen. The strobe may not be seen by the visually im-
paired.
The signal strobe may cause seizures. Individuals who have a positive
photic response to visual stimuli with seizures, such as epileptics, should avoid prolonged exposure to environments in which strobe signals, in­cluding this strobe, are activated.
System Sensor recommends that the Multi-Alert Sounder and Signal Strobe always be used in combination so that the risks from any of the above limitations are minimized.
The Signal Strobe may not be seen. The electronic visual warning signal that flashes at least once every three seconds meets or exceeds current Un­derwriters Laboratories’ standard 1971 and uses an extremely reliable xe­non flash tube. The visual warning signal is suitable for direct viewing and
Three-Year Limited Warranty
System Sensor warrants its sounder/strobe to be free from defects in mate­rials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this sounder/strobe. No agent, representative, dealer, or em­ployee of the Company has the authority to increase or alter the obliga­tions or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the sounder/strobe which is found to be defective in materials or workman­ship under normal use and service during the three year period commenc­ing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Repair Depart-
D900-08-00 4 I56-732-04
Technical Manuals Online! - http://www.tech-man.com
The signal strobe cannot operate from coded power supplies. Coded power supplies produce interrupted power. The strobe must have an unin­terrupted source of DC power in order to operate correctly.
ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifica­tions, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or conse­quential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
© System Sensor 1996
Loading...