System Sensor P2R, P2RHK, SpectrAlert Advance, P2RH, P2RK Installation And Maintenance Instructions Manual

...
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
Selectable Output Strobes, Horns, and Horn/Strobes
For use with the following models: P2R, P2RH, P2RK, P2RHK, P2W, P2WK, P2WH, P2WHK, P4R, P4RH, P4RK, P4W, P4WK, P4WHK, SR, SRH, SRK, SRHK, SW, SWK, SWH, SWHK, SW-CLR-ALERT, PC2R, PC2RH,PC2RK, PC2RHK, PC2W, PC2WK, PC2WH, PC2WHK, PC4R, PC4RH, PC4W, PC4WK, PC4WHK, SCR, SCRH, SCRK, SCRHK, SCW, SCWK, SCWH, SCWHK, SCW-CLR-ALERT, HR, HRK, HW, SR-P, SW-P, SRH-P, SWH-P,P2R-P, P2W-P, P2WH-P, P4W-P, SCW-P, PC2R-P, PC2W-P, PC2WH-P, SRK-P, SRHK-P, P2RK-P, P2RHK-P, SWK-P,
SWHK-P, P2WK-P, P2WHK-P, SR-SP, P2R-SP, PC2W-SP, SRK-R, SWK-R, SRHK-R, SWHK-R, P2RK-R, P2WK-R, P2RHK-R, P2WHK-R
NOTE: All -R models are specifically designed for use with the WTP Series of Weatherproof plates NOTE: When replacing outdoor units; device and back box must be replaced
PRODUCT SPECIFICATIONS
Operating Temperature: Standard Products 32°F to 120°F (0°C to 49°C)
K Series –40°F to 151°F
Humidity Range: Standard Products 10 to 93% Non-condensing
K Series Meets NEMA 4X requirements
Strobe Flash Rate: 1 flash per second
Nominal Voltage: Regulated 12VDC/FWR or regulated 24DC/FWR
Operating Voltage Range (includes fire alarm panels with built in sync): 8 to 17.5V (12V nominal) or 16 to 33V (24V nominal)
Operating Voltage with MDL Sync Module: 9 to 17.5V (12V nominal) or 17 to 33V (24V nominal)
Input terminal wire gauge: 12 to 18 AWG
NOTE : Strobes will operate at 12 V nominal for 15 & 15/75 candela settings only. Switching between ranges is automatic.
DIMENSIONS FOR PRODUCTS AND ACCESSORIES
WALL PRODUCTS LENGTH WIDTH DEPTH CEILING PRODUCTS DIAMETER DEPTH
Strobes and Horn/Strobes (including lens)
Horns
SA-WBB Weatherproof Back Box SA-WBBW Weatherproof Back Box
BBS-2 BBSW-2 Back Box Skirt
5.6˝ 4.7˝ 2.5˝
142 mm 119 mm 64 mm 173 mm 64 mm
5.6˝ 4.7˝ 1.3˝
142 mm 119 mm 33 mm 180 mm 51 mm
5.7˝ 5.1˝ 2.0˝
145 mm 130 mm 51 mm 180 mm 57 mm
5.0˝ 5.9˝ 2.2˝
130 mm 152 mm 57 mm
Strobes and Horn/Strobes (including lens)
SA-WBBC Weatherproof Back Box SA-WBBCW Weatherproof Back Box
BBSC-2 BBSCW-2 Back Box Skirt
NOTE: SA-WBB, SA-WBBW, SA-WBBC and SA-WBBCW dimensions do not include the two mounting tabs
800/736-7672, FAX: 630/377-6495
www.systemsensor.com
6.8˝ 2.5˝
7.1˝ 2.0˝
7.1˝ 2.2˝
I56-2769-015R
MOUNTING BOX OPTIONS
2-Wire Indoor Products 4-Wire Indoor Products K Series Products
4 × 4 × 11/2, Single Gang, Double Gang, 4˝ Octagon 4 × 4 × 11/2, Double Gang, 4˝ Octagon SA-WBB/W (wall), SA-WBBC/CW (ceiling)
NOTICE: This manual shall be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The SpectrAlert Advance series of notification appliances offers a wide range of horns, strobes, and horn/strobes, for wall and ceiling applications, indoors and outdoors. They are designed to be used in 12 or 24 volt, DC or FWR (full wave rectified) systems. These products are electrically backward compat­ible with the previous generation of SpectrAlert notification appliances. Horn/ strobe products are available in two versions. The 2-wire products fit systems where a single NAC controls both horn and strobe. The 4-wire products are in­tended for systems which have separate wiring circuits for the horn and strobe. All SpectrAlert Advance products are suitable for use in synchronized systems. The System Sensor MDL module may be used to provide synchronization.
K Series products are designed to be used over a wider range of temperatures and are suitable for use in wet locations.
Wall and ceiling products may be used interchangeably (wall products may be used on the ceiling and ceiling products may be used on the wall.)
FIRE ALARM SYSTEM CONSIDERATIONS
The National Fire Alarm Code, NFPA 72, requires that all horns, used for building evacuation produce temporal coded signals. Signals other than those used for evacuation purposes do not have to produce the temporal coded sig­nal. System Sensor recommends spacing notification appliances in compli­ance with NFPA 72.
LOOP DESIGN AND WIRING
The system designer must make sure that the total current drawn by the de­vices on the loop does not exceed the current capability of the panel supply, and that the last device on the circuit is operated within its rated voltage. The current draw information for making these calculations can be found in the tables within this manual. For convenience and accuracy, use the voltage drop calculator on the System Sensor website (www.systemsensor.com) or CD-ROM.
When calculating the voltage available to the last device, it is necessary to consider the voltage drop due to the resistance of the wire. The thicker the wire, the smaller the voltage drop. Wire resistance tables can be obtained from electrical handbooks. Note that if Class A wiring is installed, the wire length may be up to twice as long as it would be for circuits that are not fault tolerant.
NOTE: The total number of strobes on a single NAC must not exceed 40 for 24 volt applications or 12 for 12 volt applications. Loop resistance on a single NAC should not exceed 120 ohms for 24 volt and 30 ohms for 12 volt systems.
For 4-Wire installations, terminals 1, 2, and 3 connect to the strobe; terminals 4 and 5 connect to the horn. The horn and strobe circuits must be wired in­dependently, and each circuit must be terminated with the appropriate EOL device. Removal of a notification device will result in an open circuit indica­tion on the strobe loop.
D690-03-00 1 I56-2769-015R
FIGURE 1. WIRING 2-WIRE PRODUCTS:
INPUT
FACP OR PRIOR HORN
OUTPUT
HORN OR EOL
INPUT FROM FACP OR PRIOR DEVICE
+ –
FIGURE 2. WIRING 4-WIRE PRODUCTS:
OUTPUT TO NEXT DEVICE OR EOL
+ –
A0367-01
TABLE 1. STROBE CURRENT DRAW ( ) FOR S, SC, P4 & PC4 SERIES:
Standard Candela Range
mA
Candela
8–17.5 Volts 16–33 Volts
DC FWR DC FWR
15 123 128 66 71
15/75 142 148 77 81
30 NA NA 94 96 75 NA NA 158 153
95 NA NA 181 176 110 NA NA 202 195 115 NA NA 210 205
High Candela Range 135 NA NA 228 207
150 NA NA 246 220 177 NA NA 281 251 185 NA NA 286 258
FROM FACP OR PRIOR STROBE
+ – + –
INPUT FROM
OUTPUT TO NEXT
TO NEXT STROBE OR EOL
+ – + –
A0366-00
FIGURE 3. SHORTING SPRING:
SHORTING SPRING
A0368-00
NOTE: A shorting spring is provided between terminals 2 and 3 of the mount­ing plate to enable wiring checks after the system has been wired, but prior to installation of the final product. This spring will automatically disengage when the product is installed, to enable supervision of the final system.
CANDELA SELECTION
Adjust the slide switch on the rear of the product to position the desired can­dela setting in the small window on the front of the unit. All products meet the light output profiles specified in the appropriate UL Standards. For K series products used outdoors at low temperatures, listed candela ratings must be re­duced in accordance with Table 2. Use Table 1 to determine the current draw for each candela setting. WIRING DIAGRAMS
NOTE: SpectrAlert products set at 15 and 15/75 candela automatically work on either 12V or 24V power supplies. The products are not listed for 12V op­erating voltages when set to any other candela settings. For 4-Wire products, total current draw may be determined by adding current draw for the specific candela selection in Table 1 with the current draw for the specific horn selec­tion in Table 3.
TABLE 2. CANDELA DERATING:
Listed Candela
Candela rating at –40°F
(K Series Outdoor Applications Only)
15
Do not use below 32°F15/75 30 75 44 95 70
110 110
115 115 135 135 150 150 177 177 185 185
HORN SELECTION
Turn the rotary switch on the back of the product to the desired setting. For horn and 4-wire horn/strobe products, the current draw for each setting is listed in Table 3. For 2-wire horn/strobe products (P2 series), current draws are listed in Tables 4 and 5. The sound output measurement for each horn setting is shown in Table 6.
TABLE 3. HORN CURRENT DRAW ( ) FOR H, P4 & PC4 SERIES:
Pos Sound Pattern dA Out
mA
8–17.5 Volts 16–33 Volts
DC FWR DC FWR 1 Temporal High 57 55 69 75 2 Temporal Medium 44 49 58 69 3 Temporal Low 38 44 44 48 4 Non-temporal High 57 56 69 75 5 Non-temporal Medium 42 50 60 69 6 Non-temporal Low 41 44 50 50 7 Coded High 57 55 69 75 8 Coded Medium 44 51 56 69 9 Coded Low 40 46 52 50
NOTE: In positions 7, 8, and 9, temporal coding must be provided by the NAC. If the NAC voltage is held constant, the horn output will remain constantly on. Positions 7, 8, and 9 are not available on 2-wire horn/strobe products.
D690-03-00 2 I56-2769-015R
TABLE 4. 2-WIRE HORN/STROBE CURRENT DRAW ( ) FOR P2 AND PC2 STANDARD CANDELA SERIES:
DC Input
Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non-temporal High 141 152 91 100 116 176 201 221 229 Non-temporal Medium 133 145 75 85 102 163 187 207 216 Non-temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non-temporal High 142 161 103 112 126 181 203 221 229 Non-temporal Medium 134 155 85 95 110 166 189 208 216 Non-temporal Low 132 154 80 90 105 161 184 202 211
8–17.5 Volts 16–33 Volts
15 cd 15/75 cd 15 cd 15/75 cd 30 cd 75 cd 95 cd 110 cd 115 cd
mA
TABLE 5. 2-WIRE HORN/STROBE CURRENT DRAW ( ) FOR P2 AND PC2 HIGH CANDELA RANGE SERIES:
Sound Pattern
Temporal High 245 259 290 297 215 231 258 265
Temporal Medium 235 253 288 297 209 224 250 258
Temporal Low 232 251 282 292 207 221 248 256
Non-temporal High 255 270 303 309 233 248 275 281
Non-temporal Medium 242 259 293 299 219 232 262 267
Non-temporal Low 238 254 291 295 214 229 256 262
TABLE 6. HORN OUTPUT ( BA) IN UL REVERBERANT ROOM:
Switch Position
7* Coded High 82 82 88 88 93 92 101 101 8* Coded Medium 78 78 85 85 90 89 97 98 9* Coded Low 74 75 81 81 85 83 96 92
*Horn & 4-wire Horn/Strobe only. ** Minimum dB rating for Operational Voltage Range as per UL 464.
MOUNTING INDOOR WALL OR CEILING PRODUCTS
1. Attach mounting plate to junction box as shown in Figures 4 and 5. The mounting plate is compatible with 4-inch square, double gang, and 4-inch octagon junction boxes (2-wire products may be used with a single gang box). If using a back box skirt, attach the mounting plate to the skirt and then attach the entire assembly to the junction box (see Figures 6 and 7).
2. Connect field wiring to terminals, as shown in Figures 1 and 2.
3. If the product is not to be installed at this point, use the paint cover to prevent contamination of the mounting plate. (For indoor models only)
4. To attach product to mounting plate, remove the paint cover, then hook tabs on the product housing into the grooves on mounting plate.
5. Then, swing product into position to engage the pins on the product with the terminals on the mounting plate. Make sure that the tabs on the back of the product housing fully engage with the mounting plate.
6. Secure product by tightening the single mounting screw in the front of the product housing. For tamper resistance, the standard captivated mounting screw may be replaced with the enclosed Torx screw.
D690-03-00 3 I56-2769-015R
Sound Pattern dA
1 Temporal High 78 78 84 84 88 88 99 98 2 Temporal Medium 75 75 80 80 86 85 96 96 3 Temporal Low 71 71 76 76 81 79 94 89 4 Non-temporal High 82 82 88 88 93 92 100 100 5 Non-temporal Medium 78 78 85 85 90 89 98 98 6 Non-temporal Low 75 75 81 81 86 84 96 92
d
135 cd 150 cd 177 cd 185 cd 135 cd 150 cd 177 cd 185 cd
mA
16–33 Volts Volts DC 16–33 Volts Volts FWR
8–17.5 Volts** 16–33 Volts**
DC FWR DC FWR DC FWR DC FWR
K SERIES MOUNTING
1. K Series products may be used indoors or outdoors. They must be in­stalled using the proper SpectrAlert Advance weatherproof back box (SA­WBB, SA-WBBW, SA-WBBC or SA-WBBCW). Do not attempt to use boxes other than the ones supplied with the product.
2. The wall mount box (SA-WBB or SA-WBBW) must be mounted with its internal post in the lower left corner, as shown in Figure 8.
3. Threaded holes are provided in the sides of the box for ¾-inch conduit adapters. Knockout plugs in the back of the box can be used for ¾-inch rear entry. Unused holes must be sealed. Plugs and O-Rings are provided with the box for this purpose.
4. It is the responsibility of the installer to make sure that all openings and connections are sealed properly. Outdoor installations that are protected from direct exposure to rain are still subject to condensation or leakage through hidden areas, such as a soffit.
5. Water may pool on the back box due to condensation or direct exposure to rain or snow. Use watertight fittings for all wiring connections, includ­ing the knockout plugs on the back of the box. When using plastic plugs to fill unused threaded holes, apply teflon tape and/or silicone sealant to reduce the chance of leakage.
6. Attach the mounting plate to the weatherproof back box using the four unpainted screws.
7. Follow steps 2 – 6 of the indoor mounting instructions to wire and attach the product.
24 V Nominal Measurements
Reverberant Anechoic
FIGURE 4. WALL MOUNT PRODUCT:
4-wire mounting plate
FIGURE 7: CEILING MOUNT PRODUCT WITH BACK BOX SKIRT:
A0348-00
FIGURE 5. CEILING MOUNT PRODUCT:
FIGURE 8. WALL MOUNT HORN/STROBE WITH WEATHERPROOF BACKBOX:
2-wire mounting plate
A0369-00
FIGURE 6. WALL MOUNT PRODUCT WITH BACK BOX SKIRT:
A0349-00
NOTE: Use all four mounting plate screws when installing outdoor units.
FIGURE 9. WALL AND CEILING MOUNT WEATHERPROOF BACKBOXES:
NOTE: Wall and Ceiling models may be used interchangeably (wall products may be used on the ceiling and ceiling products may be used on the wall).
A0370-00
A0418-00
A0417-00
Please refer to insert for the Limitations of Fire Alarm Systems
WARNING
The Limitations of Horn/Strobes
The horn and/or strobe will not work without power. The horn/strobe gets its power from the fire/security panel monitoring the alarm system. If power is cut off for any reason, the horn/strobe will not provide the desired audio or visual warning.
The horn may not be heard. The loudness of the horn meets (or exceeds) current Underwriters Laboratories’ standards. However, the horn may not alert a sound sleeper or one who has recently used drugs or has been drinking alcoholic bever­ages. The horn may not be heard if it is placed on a different floor from the person in hazard or if placed too far away to be heard over the ambient noise such as traffic, air conditioners, machinery or music appliances that may prevent alert persons from hearing the alarm. The horn may not be heard by persons who are hearing impaired.
NOTE: Strobes must be powered continuously for horn operation.
Three-Year Limited Warranty
Syst em Sens or wa rra nts its enclos ed product t o be free from defec ts in ma­terials a nd wor kmans hip unde r normal use and s ervic e for a pe riod of t hree years from dat e of ma nufac ture. System S ensor makes no oth er express war­ranty for this product. No age nt, repres entat ive, dealer, or employee o f the Company has t he aut hority to increas e or al ter th e obligations or lim itations of this Warranty. The Company’s o bligati on o f this Warran ty sha ll b e li mited to the repl acement of a ny p art of the pro duct w hich i s foun d to be def ective in m ateri als or wo rkman ship und er norma l use and se rvice du ring the three year per iod com mencing with the d ate of ma nufacture. Af ter pho ning Syste m Sensor’s toll f ree nu mber 800 -SENSOR2 (736 -7672) f or a Return Auth oriza tion number, sen d defect ive un its post age prepaid to: System S ensor, Retu rns
FCC Statement
SpectrAlert Strobes and Horn/Strobes have been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses,
D690-03-00 4 I56-2769-015R ©2010 System Sensor
The signal strobe may not be seen. The electronic visual warning signal uses an extremely reliable xenon flash tube. It flashes at least once every second. The strobe must not be in­stalled in direct sunlight or areas of high light intensity (over 60 foot candles) where the visual flash might be disregarded or not seen. The strobe may not be seen by the visually impaired.
The signal strobe may cause seizures. Individuals who have positive photoic response to visual stimuli with seizures, such as persons with epilepsy, should avoid prolonged exposure to environments in which strobe signals, including this strobe, are activated.
The signal strobe cannot operate from coded power supplies. Coded power supplies produce interrupted power. The strobe must have an uninterrupted source of power in order to operate correctly. System Sensor recommends that the horn and signal strobe always be used in combination so that the risks from any of the above limitations are minimized.
Departme nt, RA #____ ______, 3825 O hio Avenue, St. Charl es, IL 60174. Please include a note descr ibing the malfuncti on and suspe cted cause of failu re. The Comp any shal l not be obliga ted t o replac e units wh ich a re found to be defective be cause of d amage, unreasonab le use, modif icati ons, or al terations occurrin g after the date of manufa cture. In no case shall the Company be liable for any co nsequen tial or incid ental dama ges for bre ach o f t his o r a ny other Warran ty, ex pre ssed o r impl ied whatsoever, eve n if the lo ss o r dama ge is cause d by the Com pany’s negligen ce or f ault. S ome sta tes do not all ow th e excl usion or limit ation of incidental or con sequent ial da mages, so th e above limitati on or excl usion may no t apply t o yo u. This Warran ty gives you spe cific legal rights, an d yo u may al so have other rig hts wh ich vary from sta te to state.
and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Loading...