System Sensor M501M User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
(+) (–)
TO NEXT DEVICE
BLACK
RED
(+)
(–)
(+)
(–)
VIOLET
YELLOW
0
1
2
3
4
5
6
7
8
9
SIGNAL LINE CIRCUIT (SLC)
47k EOL INCLUDED (ELR-47k)
UL LISTED
COMPATIBLE
CONTROL
PANEL
ALL WIRING
SHOWN IS
SUPERVISED AND
POWER LIMITED
0
7
8
6
5 4 3
2
1
9
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
M501M Monitor Module
SpECIfICATIONS
Nominal Operating Voltage: 15-32 VDC Average Operating Current: 350 µA, 1 communication every 5 seconds, 47k EOL; 600 µA Max. (Communicating, IDC Shorted) EOL Resistance: 47K Ohms Maximum IDC Wiring Resistance: 40 Ohms Maximum IDC Voltage: 11 Volts Maximum IDC Current: 400µA Temperature Range: 32°F to 120°F (0°C to 49°C) Humidity: 10% to 93% Non-condensing Dimensions: 1.3˝ H × 2.75˝ W × 0.65˝ D Wire Length: 6˝ minimum
www.systemsensor.com
I56-3857-001
BEfORE INSTALLINg
NOTICE: This manual should be left with the owner/user of this equipment.
gENERAL DESCRIpTION
The M501M monitor module can be installed in a single gang junction box directly behind the monitored unit. Its small size and light weight allow it to be installed without rigid mounting (see Figure 1). The M501M is intended for use in intelligent, two-wire systems where the individual address of each mod­ule is selected using rotary decade switches. It provides a two-wire initiating circuit for normally open contact fire alarm and security devices.
COMpATIBILITy REqUIREMENTS
To ensure proper operation, this module should only be connected to a com­patible control panel.
fIgURE 1:
MOUNTINg AND WIRINg
NOTE: This module is intended to be wired and mounted without rigid con­nections inside a standard electrical box. All wiring must conform to appli­cable local codes, ordinances, and regulations.
1. Connect the red (+) and black ( – ) wires to the positive and negative
loop power leads of the signaling line circuit.
2. Connect the violet (+) and yellow ( – ) wires to a two-wire, normally
open initiating loop.
3. Install the specified EOL resistor value to terminate the initiating loop.
4. Set the address on the module per job drawings.
5. Install the module in the desired mounting location.
fIgURE 2. TypICAL 2-WIRE STyLE B INITIATINg CIRCUIT CONfIgURATION:
SS-460-005 1 I56-3857-001 ©2007 System Sensor
C0614-03
C0613-04