System Sensor M500M User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
ISOLATED
QUADRANT
M500M Monitor Module
SpECIfICATIONS
Normal Operating Voltage: 15 to 32 VDC Maximum Current Draw: 5.0mA (LED on) Average Operating Current: 350 μA, 1 communication every 5 seconds, 47k EOL EOL Resistance: 47K Ohms Maximum IDC wiring resistance: 40 Ohms Maximum IDC Voltage: 11 Volts Maximum IDC Current: 400μA Temperature Range: 32˚F to 120˚F (0˚C to 49˚C) Humidity: 10% to 93% Non-condensing Dimensions: 41/2˝ H x 4˝ W x 11/4˝ D (Mounts to a 4˝ square by 21/8˝ deep box.) Accessories: SMB500 Electrical Box
I56-3855-001
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
BEfORE INSTALLINg
This information is included as a quick reference installation guide. Refer to the control panel installation manual for detailed system information. If the modules will be installed in an existing operational system, inform the opera­tor and local authority that the system will be temporarily out of service. Dis­connect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
gENERAL DESCRIpTION
The M500M Monitor Module is intended for use in intelligent, two-wire sys­tems, where the individual address of each module is selected using the built­in rotary decade switches. It provides either a 2-wire or 4-wire fault tolerant initiating circuit for normally open contact fire alarm, supervisory, or security devices. The module has a panel controlled LED indicator.
COMpATIBILITy REqUIREMENTS
To ensure proper operation, these modules shall be connected to listed com­patible system control panels only.
fIgURE 1. CONTROLS AND INDICATORS:
MOUNTINg
The M500M mounts directly to 4-inch square electrical boxes (see Figure 2). The box must have a minimum depth of 21/8 inches. Surface mounted electri­cal boxes (SMB500) are available from System Sensor.
fIgURE 2. MODULE MOUNTINg:
C1044-00
WIRINg
NOTE: All wiring must conform to applicable local codes, ordinances, and regulations. This module is intended for power limited wiring only.
C0917-01
SS-460-004 1 I56-3855-001
1. Install module wiring in accordance with the job drawings and appropri­ate wiring diagrams.
2. Set the address on the module per job drawings.
3. Secure module to electrical box (supplied by installer), as shown in Figure 2.
fIgURE 3. TypICAL 2-WIRE INITIATINg CIRCUIT CONfIgURATION, NfpA STyLE B:
(+)
(–)
(+)
(–)
(+)
(–)
MONITOR
MODULE
ANY NUMBER OF UL LISTED
CONTACT CLOSURE DEVICES
MAY BE USED. DO NOT MIX FIRE
ALARM INITIATING,
SUPERVISORY, OR SECURITY
DEVICES ON THE SAME MODULE.
TO NEXT
DEVICE
FROM PANEL OR
PREVIOUS DEVICE
47K EOL
RESISTOR
ELR-47K
CONNECT MODULES TO LISTED
COMPATIBLE CONTROL PANELS ONLY
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
SHIELDED-TWISTED PAIR
IS RECOMMENDED
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
INITIATING DEVICE CIRCUIT (IDC) - NFPA STYLE B
POWER LIMITED: 400µA MAX. @ 11 VDC MAX
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER’S INSTALLATION INSTRUCTIONS.
(+)
(-)
(+)
(–)
(+)
(–)
MONITOR
MODULE
TO NEXT
DEVICE
FROM PANEL OR
PREVIOUS DEVICE
CONNECT MODULES TO LISTED
COMPATIBLE CONTROL PANELS ONLY
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
SHIELDED-TWISTED PAIR
IS RECOMMENDED
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
ANY NUMBER OF UL LISTED
CONTACT CLOSURE DEVICES
MAY BE USED. DO NOT MIX FIRE
ALARM INITIATING,
SUPERVISORY, OR SECURITY
DEVICES ON THE SAME MODULE.
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER’S INSTALLATION INSTRUCTIONS.
EOL RESISTOR
IS INTERNAL AT
TERMINALS
8 AND 9
fIgURE 4. TypICAL 4-WIRE fAULT TOLERANT INITIATINg CIRCUIT CONfIgURATION, NfpA STyLE D:
C1051-00
System Sensor warrants its enclosed product to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for the enclosed product. No agent, representative, dealer, or employee of the Company has the authority to in­crease or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the replacement of any part of the product which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Returns Department, RA
SS-460-004 2 I56-3855-001 ©2007 System Sensor
ThREE-yEAR LIMITED WARRANTy
#__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
C0919-03