System Sensor M500DM User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
M500DM Dual Monitor Module
SPECIFICATIONS
Normal Operating Voltage: 15 to 32 VDC Maximum Current Draw: 6.4 mA (LED on) Average Operating Current: 750 µA (LED flashing) EOL Resistance: 47K Ohms Maximium SLC wiring resistance: 40 Ohms Maximum IDC wiring resistance: 1,500 Ohms Maximum IDC Voltage: 11 Volts Maximum IDC Current: 240µA Temperature Range: 32°F to 120°F (0°C to 49°C) Humidity: 10% to 93% Non-condensing Dimensions: 41/2 in H x 4.275 in W x 1.4 in D (Mounts to a 4-inch square by 21/8-inch deep box.) Accessories: SMB500 Electrical Box
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to the control panel installation manual for detailed system information. If the modules will be installed in an existing operational system, inform the opera­tor and local authority that the system will be temporarily out of service. Dis­connect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The Dual Monitor Module is intended for use in intelligent, two wire systems. It provides two independent 2-wire initiating device circuits (IDC), at two sep­arate, consecutive addresses. It is capable of monitoring normally open con­tact fire alarm and supervisory devices, or either normally open or normally closed security devices.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, these modules shall be connected to listed com­patible system control panels only.
FIGURE 1. CONTROLS AND INDICATORS:
MOUNTING
Mounts directly to 4-inch square electrical boxes (see Figure 2A). The box must have a minimum depth of 21/8 inches. Surface mounted electrical boxes (SMB500) are available from System Sensor.
FIGURE 2. MODULE MOUNTING: FIGURE 2B:
I56-3869-001
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
C1075-00
C0917-01
WIRING
H
L
TWO INITIATING DEVICE CIRCUITS (L&H), EACH POWER LIMITED TO 240 µA @ 11 VDC MAX.
UL LISTED CONTACT CLOSURE DEVICES MAY BE USED. DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY, OR SECURITY DEVICES ON THE SAME INITIATING DEVICE CIRCUIT.
INSTALL CONTACT CLOSURE DEVICES PER MANUFACTURER’S INSTALLATION INSTRUCTIONS.
47k EOL RESISTOR
47k EOL RESISTOR
TO NEXT DEVICE
(+)
(−)
(+)
(−)
(+)
(−)
FROM PANEL OR PREVIOUS DEVICE
CONNECT MODULES TO LISTED COMPATIBLE CONTROL PANELS ONLY
MONITOR L (TERMINALS 6 & 7) RESPONDS AT ADDRESS SET ON CODE SWITCHES. MONITOR H (TERMINALS 8 &
9) RESPONDS AT NEXT HIGHER ADDRESS.
SIGNAL LINE CIRCUIT (SLC) 32 VDC MAX. TWISTED PAIR IS RECOMMENDED
MONITOR
MODULE
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
NOTE: All wiring must conform to applicable local codes, ordinances, and regulations. This module is intended for power limited wiring only.
1. Install module wiring in accordance with the job drawings and appropri­ate wiring diagrams.
2. Set the address on the module per job drawings.
NOTE: Monitor module L (using terminals 6 and 7) responds at the ad-
dress set on the code switches. Monitor module H (using terminals 8 and
9) will automatically respond at the next higher address. For example, if the code switches are set to 76, module L will respond at address 76 and module H will respond at address 77. Use caution to avoid duplicate ad­dressing of modules on the system.
3. Secure module to electrical box (supplied by installer), as shown in Fig­ure 2.
FIGURE 3. TYPICAL 2-WIRE INITIATING CIRCUIT CONFIGURATION, NFPA STYLE B:
System Sensor warrants its enclosed product to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for the enclosed product. No agent, representative, dealer, or employee of the Company has the authority to in­crease or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the replacement of any part of the product which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Returns Department, RA
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation is subject to the following two conditions: (1) This device may not cause harmful radiation, and (2) this device must accept any interference received, including interference that may cause undesired operation.
SS-460-009 2 I56-3869-001 ©2008 System Sensor
THREE-YEAR LIMITED WARRANTY
FCC STATEMENT
#__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
C1074-07
Loading...