System Sensor KBS, KMS User Manual

D770-06-00 1 I56-373-03
System Sensor, 3825 Ohio Avenue, St. Charles, Illinois 60174, 1-800-SENSOR2, FAX: 708-377-6495
KMS & KBS BELL SERIES
INSTALLATION INSTRUCTIONS
IMPORTANT Please Read Carefully and Save
This instruction manual contains important information about the installation and operation of bells. Purchasers who install bells for use by others must leave this manual or a copy of it with the user.
only those instructions that apply to the model you are installing.
CAUTION
DO NOT USE IN POTENTIALLY EXPLOSIVE ATMOSPHERES.
DO NOT LEAVE ANY UNUSED WIRES EXPOSED.
GENERAL DESCRIPTION
The National Fire Protection Association has published codes, standards, and recommended practices for the installa­tion and use of the above appliances. It is recommended that the installer be familiar with these requirements, with local codes, and any special requirements of the authority having jurisdiction.
These bells are intended to be connected to alarm indicating circuits of UL listed fire alarm control panels. Terminal con­nections are polarized to enable supervision of the installation wiring. The KMS bells require 24 VDC and the KBS bells require 120 VAC.
Before installing any alarm device, be thoroughly familiar with: NFPA 72: Installation, Maintenance, and Use of Protective Signaling Systems
NFPA 13: Installation of Sprinkler Systems NFPA 13A: Inspection, Testing, and Maintenance of Sprinkler Systems, specifically Chapters 4 and 5
Other applicable NFPA standards, local codes, and the requirements of the authority having jurisdiction. Failure to follow these directions may result in failure of the device to report an alarm condition. System Sensor is not
responsible for devices that have been improperly installed, tested, or maintained.
INSTALLATION
WARNING
High voltage. Electrocution Hazard. Do not handle live AC wiring or work on a device to which AC power is applied. Doing so may result in severe injury or death.
CAUTION: Do not loop wire under terminals. Break wire runs to provide supervision of connections.
1. Remove the gong.
2. Wire the bell in the circuit. See Figure 1. (Note polarity markings on bells.) NOTE: Terminals on bells are designed to accept 14 GA wire. When using a 10 or 12 GA wire use Panduit terminal
PV106LF or equivalent for connection of power leads.
3. Mount bell mechanism on 4square electrical box with the striker facing down. See Figures 2 – 5.
4. Replace the gong.
5. The top of the bell must be mounted a minimum of 90above the floor, or within 6of the ceiling.
A78-2390-00
Wire KBS 120 VAC powered bells per control panel manufacturer ’s instructions.
Figure 1. Typical KMS Bell Wiring Diagram (shown in alarm condition)
BASIC MECHANISM AND GONGS SURFACE INSTALLATION
A78-1562-01 A78-2387-00
Figure 2. Figure 3.
WEATHERPROOF INSTALLATION CONCEALED CONDUIT INSTALLATION
(SEMI-FLUSH)
A78-2388-00 A78-2389-00
Figure 4. Figure 5.
10" BELL
ELECTRICAL BOX (NOT INCLUDED)
ADAPTOR PLATE (NOT INCLUDED) PART NO. P40-86-03
4" SQUARE WEATHERPROOF BACK BOX (NOT INCLUDED) MODEL NO. WBBF
8" BELL
8" BELL
4" SQUARE ELECTRICAL BOX (NOT INCLUDED)
3-1/8"
3-3/8" SQUARE
MOUNTING HOLE PATTERN
(HOLES ARE LOCATED TO MOUNT TO A
STANDARD 4" SQUARE OUTLET BOX)
10"
8"
6"
STRIKER LOCATED ON BOTTOM OF BELL (VISIBLE FROM REAR)
3-3/8"
KMS BELL KMS BELL
24 VDC INDICATING CIRCUIT FROM FIRE ALARM CONTROL PANEL
EOL RESISTOR (SPECIFIED BY PANEL MANUFACTURER)
DO NOT LOOP WIRE UNDER TERMINALS; BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
POLARITIES ARE SHOWN IN ALARM.