Sounder Tone Select DIP Switch configuration
Table 2
DIMENSIONS
ADDRESS SETTING
To set one of the 159 available addresses for the device
use the two rotary selectors located alongside the dip
switch unit.
The 'tens' digits go from 0 to 15 (0 to F) and the 'units'
from 0 to 9.
A= 10
B = 11
C = 12
D = 13
E = 14
F = 15
System Sensor Europe, Units 15-19 Trescott Road, Redditch, Worcestershire, England. B98 7AH.
115mm
109mm
68mm
Sounder Output data, in accordance with EN54-3, is available on Document Ref: D 535.
DIP setting
O=Off/1=On
SW 1,2,3,4,5
No Pattern
Nominal
Frequency
Switching
Frequency
Description Standard
2nd
Stage
Tone
0,0,0,0,0 1 Alternating 554/440
2Hz
(100mS/400mS)
French Fire Sound
AFNOR
NFS 32-001 7
1,0,0,0,0 2 Alternating 800/970 1Hz BS5839 Pt1 8
0,1,0,0,0 3 Alternating 800/970 2Hz
Alternating tone
telecoms
BS5839 Pt1
FP1063.1 Telecoms
8
1,1,0,0,0 4 Alternating 2400/2900 3Hz 10
0,0,1,0,0 5 Alternating 2500/3100 2Hz 10
1,0,1,0,0 6 Alternating 988/645 2Hz 8
0,1,1,0,0 7 Continuous 660 All Clear 1
1,1,1,0,0 8 Continuous 970 BS5839 Pt1 2
0,0,0,1,0 9 Continuous 1200 2
1,0,0,1,0 10 Continuous 2850
Banshee/Bedlam HF
Continuous
4
0,1,0,1,0 11 Continuous 4000 5
1,1,0,1,0 12 Intermittent 660
0.05Hz 6.5s on,
13s off
7
0,0,1,1,0 13 Intermittent 660
0.277Hz 1.8s on,
1.8s off
7
1,0,1,1,0 14 Intermittent 660
3.33Hz 150mS on,
150mS off
Swedish Alarm Tone 7
0,1,1,1,0 15 Intermittent 970
0.8Hz 0.25s on, 1s
off
intermittent Tone BS5839 Pt1 8
1,1,1,1,0 16 Intermittent 970 1Hz 1s on, 1s off
Backup alarm HF &
BS5839 Pt1
BS5839 Pt1 8
DIP setting
O=Off/1=On
SW 1,2,3,4,5
No Pattern
Nominal
Frequency
Switching
Frequency
Description Standard
2nd
Stage
Tone
0,0,0,0,1 17 Intermittent 2850 1Hz
Backup alarm HF &
BS5839 Pt1 2nd Tone
BS5839 Pt1 10
1,0,0,0,1 18 Intermittent 970
1Hz 500mS on,
500mS off
ISO 8201 LF &
BS5839 Pt1
BS5839 Pt1, ISO
8201
8
0,1,0,0,1 19 Intermittent 950
0.22Hz (0.5s on,
0.5s off)*3, 1.5s off
8
1,1,0,0,1 20 Intermittent 2850
4Hz 150mS on,
100mS off
Pelican Crossing 10
0,0,1,0,1 21 Sweep 400-1200
(0.5s on, 0.5s
off)*3, 1.5s off
9
1,0,1,0,1 22 Sweep 1200 - 500
0.99Hz 1s on,
0.01s off
Evacuate, DIN tone &
PFEER
DIN, PFEER 8
0,1,1,0,1 23 Sweep 2400 - 2850 7Hz Fast Sweep Vds Vds 10
1,1,1,0,1 24 Sweep 500 - 1200
0.5sec off
3.5sec on
Slow whoop evacuate
Netherlands NEN 2575
8
0,0,0,1,1 25 Sweep 800 - 970 50Hz LF buzz BS5839 Pt1 BS5839 Pt1 8
1,0,0,1,1 26 Sweep 800 - 970 7Hz
Fast sweep LF BS5839
Pt1
BS5839 Pt1 8
0,1,0,1,1 27 Sweep 800 - 970 1Hz
Medium sweep LF
buzz BS5839 Pt1 Vds
BS5839 Pt1 8
1,1,0,1,1 28 Sweep 2400 - 2850 50Hz 10
0,0,1,1,1 29 Sweep 500 - 1000 7Hz 8
1,0,1,1,1 30 Sweep
500 - 1200 -
500
0.166Hz rise 1s,
stable 4s, fall 1s
8
0,1,1,1,1 31 Sweep 800 - 1000 2Hz 8