System Sensor i4 Series COSMO-2W, i4 Series COSMO-4W Installation And Maintenance Instructions Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
i4 Series Combination Carbon
I56-3747-001R
Monoxide(CO)/Photoelectric Smoke Detector COSMO-2W (2-wire) and COSMO-4W (4-wire)
SPECIFICATIONS COSMO-2W COSMO-4W
Electrical Specifications Physical Spcecificaitons
System Voltage: 12/24 volts DC 12/24 volts DC Operating Temperature Range: 0 - 50° C (32 - 122° F) Min: 8.5 volts 8.5 volts Operating Humidity Range: 20-95% RH Max: 35 volts 35 volts Storage Temperature Range: -10 - 70° C (14 - 158° F) Max Startup Current: 200uA 200uA Diameter: 5.5 inches Max Standby Current: 50uA 50uA Height: 2.5 inches Max Alarm Current: 50mA 40mA Weight: 9.2 oz; 261 g Max Reverse Polarity Current: 20mA 20mA Wire Gauge Acceptance: Min: 22 AWG Max: 14 AWG Audible Signal (Supplemental*): 85dBA 85dBA 2-Wire Compatibility Zone Identifier: A Max Start-up Capacitance: .10uF .10uF *NFPA requires a UL listed sounder on the NAC circuit
Notice: This manual shall be left with the owner/user of this equipment.
BEFORE INSTALLATION
Please read this manual thoroughly along with manual I56-3871 for the i4 series interface module and the Application Guides for System Sensor Smoke (A05-1003) and CO Detectors (A05-1099), which provide detailed information on detector spacing, placement, zoning, wiring, and special applications. Cop­ies of these manuals are available at systemsensor.com.
IMPORTANT: This detector must be tested and maintained regularly following
NFPA 72/NFPA 720 requirements. At a minimum, cleaning and testing should be performed annually.
GENERAL DESCRIPTION
The i4 series is a plug-in, system-connected, combination carbon monoxide/ smoke detector. It is available in either a 2-wire or 4-wire configuration. The i4 series detectors must be used with the corresponding i4 series Interface Mod­ule to connect to the panel. The i4 interface module is also compatible with i3 series smoke detector model 2WTA-B or 4WTA-B.
FEATURES
Smoke Features
• Photoelectric smoke sensor
• Drift compensation and noise rejection algorithms
• Red smoke LED indicator
• Smoke test switch
CO Features
• Field replaceable, electrochemical CO sensor
• RealTest® functional test capable
• Blue CO LED indicator
• Sensor end-of-life notification
Audible Annunciation
• Local integral sounder
• Polarity reversal
Installation and Maintenance
• Stop-Drop-N-Lock plug-in base
• SEMS wiring terminals
• COSMO-2W designed for 2-wire i4 Zone type
• COSMO-4W designed for 4-wire i4 Zone type
• SENS-RDR sensitivity reader compatible with extended range
• Removable cover for cleaning
• Replaceable screen
Other Features
• Green supervisory LED
• Listed to UL standards 268 and 2075
VISIBLE ANNUNCIATON
The i4 series detector has three visible LED’s; Green, Red and Blue. The green LED is a supervisory LED; it blinks during power on, reset, and during normal operation. It is extinguished during smoke maintenance, CO trouble, smoke
SS-500-003 1 I56-3747-001R
alarm and CO alarm events. The red LED signals smoke events; it blinks dur­ing smoke maintenance events and lights constantly during smoke alarm events. The blue LED signals CO events; it blinks blue during CO trouble or CO end-of-life; it blinks rapidly during RealTest®; and lights constant during CO alarm.
TABLE 1: OPERATION MODES
OPERATION
MODE
Normal (standby) Blink 5 Sec. OFF OFF OFF
Alarm Smoke OFF ON OFF Temp 3
Alarm CO OFF OFF ON Temp 4
Alarm Smoke & CO OFF ON ON Temp 3
RealTest® Mode OFF OFF Blink 1 Sec. OFF
(After CO is Sprayed) OFF OFF ON Temp 4
Trouble feature: When the sensor (supervision) is in a trouble condition
(such as a detector that is dirty), the detector will send a trouble signal to the module then to the FACP. Depending on the issue, the detector must then be serviced or replaced.
CO sensor end-of-life timer feature: When the CO sensor has passed end-of­life, a trouble signal will be sent to the module then to the FACP. This indicates that the CO sensor inside the detector must be replaced. If unresolved for 30 days, the detector will chirp intermittently. The typical life of the CO sensor is six years from the date of manufacture; it is recommended to periodically check the “Replace by” sticker located on the replaceable CO cell.
INSTALLATION GUIDELINES
Ceiling: Detector should be at least 12 inches from any wall.
Wall: Detector should be no closer than 6 inches from ceiling.
• Do not install outdoors or in any environment that does not comply with the detector’s environmental specifications
• Install in accordance with NFPA 72 and 720 standards. NFPA 72 and 720 define standards for both commercial and residential installation of smoke and CO detectors. State and local laws involving CO detection should also be considered.
• If the installation can be interpreted as residential, consult the section of NFPA 720 that outlines residential applications. Chapter 9.4.1.1, for example, states that carbon monoxide alarms or detectors shall be in­stalled as follows:
• Outside each separate dwelling unit sleeping area in the immediate vicinity of the bedroom
• On every level of a dwelling unit, including basements
• Consult NFPA 72, the local Authority Having Jurisdiction (AHJ), and/ or applicable codes for specific information regarding the spacing and placement of smoke detectors.
• Do not install detectors in the following areas:
• In or near areas where particles of combustion are normally present such as
3825 Ohio Avenue, St. Charles, Illinois 60174
www.systemsensor.com
GREEN
LED
RED LED BLUE LED SOUNDER
kitchens, in garages, near furnaces, hot water heaters, or gas space heaters.
WARNING
• In very cold or very hot areas.
• In wet or excessively humid areas, or next to bathrooms with showers.
• In dusty, dirty, or insect-infested areas.
• Near fresh air inlets or returns or excessively drafty areas. Air con­ditioners, heaters, fans, and fresh air intakes and returns can drive smoke away from the detector.
Note: This unit is UL listed as containing a supplemental sounder and should not be used as a primary sounder for evacuation.
FIGURE 1: ALARM LOCATION DIAGRAM FOR RESIDENTIAL APPLICATION
BEDROOM
TO BR
BEDROOM BEDROOM
LIVING ROOM
KITCHEN
CLOSED DOOR
GARAGE
S0295-01
BASEMENT
CARBON MONOXIDE/SMOKE ALARM LOCATION FOR MULTI-LEVEL RESIDENCE
MOUNTING
The i4 detector can be ceiling mounted or wall mounted:
1. To a single gang box, 2 in. by 4 in. box, 3½ in. or 4 in. octagonal or 3½ in. or 4 in. round ceiling
2. Direct mount to ceiling or to wall using drywall fasteners
FIGURE 2: MOUNTING OF DETECTOR
S0326-00
WIRING INSTALLATION GUIDELINES
All wiring must be installed in compliance with the NFPA 70 standards, Na­tional Electrical Code, applicable state and local codes.
The screw terminals in the mounting base will accept 14-22 gauge wire. Wire connections are made by stripping approximately 3/8" to ½" of insulation from
FIGURE 3: COSMO-2W WIRING DIAGRAM
ALL CIRCUITS ARE SUPERVISED (EXCEPT TRIGGERS) AND MUST
SMOKE
BE POWER LIMITED
AUXPOWER
(resettable)
the end of the feed wire, inserting it into the proper base terminal, and tight­ening the screw to secure the wire in place. Do not put wires more than 2 gauge apart under the same clamping plate.
Remove power from alarm control unit or initiating device circuits before installing detectors.
1. Remove detector from packaging and separate the base from the detector head.
2. Wire the detector base screw terminals.
3. Screw the base of the detector onto an electrical box, or to the surface of the wall or ceiling using the hardware included in the packaging.
4. Attach the detector head to the base by applying light pressure and rotat­ing clockwise. The detector will lock in place when properly aligned.
5. After all detectors have been installed, apply power to the alarm control unit. Refer to Table 3 for time to LED stabilization. Once stabilized, the green LED will blink once every 5 seconds.
6. Test each detector as described in the Testing section.
7. Notify the proper authority that the system is in operation.
CAUTION
NFPA 72 recommends the installation of detectors only after completing construction or any other dust producing activity
TABLE 2: LED INDICATION DURING POWER UP SEQUENCE
Green LED Red LED Blue LED
No Power OFF OFF OFF
Power on Reset Blink 5 Sec. Blink 5 Sec. Blink 5 Sec.
TABLE 3: POWER UP TIME TO FIRST ALARM / LED STABILIZATION
Power Up Time 45 Seconds
Power up time after
10 second reset
LED Indication time
Status LED indication
stabilization time
15 Seconds
Typical: 45 seconds
Maximum: 55 seconds
Typical: 55 seconds
Maximum: 268 seconds
TESTING
The detector must be tested after installation. The detector has two discrete test switches, one for smoke testing and one for CO testing. The detector may also be functionally tested using canned smoke and canned CO.
NOTE: Before testing, notify the proper authorities to avoid any nuisance alarms. Ensure the proper wiring and power is applied to the detector. After power up, allow approximately 5 minutes for the detector to stabilize before testing.
SMOKE
ZONE
CO
ZONE
MAINT.
ZONE
BELL
OR
SMOKE
TRIGGER OUT
CO
TRIGGER
OUT
Panel
EOL
Resistor
SS-500-003 2 I56-3747-001R
COSMOD2W
Panel
EOL
Resistors
LOOP STYLE D WIRING
COSMO-2W
3.9k
RESISTOR
(supplied
with module)
S0329-00
Loading...
+ 2 hidden pages