System Sensor i4 User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-3871-001
i4 Series Interface Module COSMOD2W and COSMOD4W
*For use with COSMO-2W and COSMO-4W detectors
SPECIFICATIONS
Electrical Specifications
Power Supply Voltage: Resettable power; 2-Wire: Min. 8.5 Volts DC (Power limited); Max. 35 Volts DC (Power limited); 4-Wire: Min. 10 Volts DC (Power limited); Max. 35Volts DC (Power limited) Device Power-up Time: 200 milliseconds Max. Standby Current: 2-Wire: 62mA; 4-Wire: 52mA (Does not include current draw from attached detectors or EOL relay) Max. Alarm Current: 2-Wire: 174mA; 4-Wire: 75mA (Does not include reverse polarity current draw from attached detectors) Nom. Standby Current: 2-Wire: 45mA@12V, 27mA@24V; 4-Wire: 36mA@12V, 21mA@24V (Does not include current draw from attached detectors or EOL relay) Alarm Contact Rating: 100 mA @ 36 Volts DC, resistive, 25 ohms Maintenance Contact Rating: 100 mA @ 36 Volts DC, resistive, 25 ohms Max. IDC Loop Wiring Resistance: 2-Wire: 50 Ohms; 4-Wire: 300 Ohms Trigger Inputs: Min. On Voltage: 1.5V; Max. On Voltage=Vin Aux Power Out: Same Voltage as Input Power (Unregulated, limited to 250mA) Min. Reset Time: 300 milliseconds Initial Communication Cycle: 6 minutes EZ Walk Test Availability: 6 minutes after power up or panel reset
Physical Specifications
Operating Temperature Range: 0 - 50° C (32 - 122° F) Operating Humidity Range: 5 - 95% RH Storage Temperature Range: -20 - 70° C (-4 - 158° F) Height: 6.04 inches Width: 6.04 inches Depth: 1.16 inches Shipping Weight: 0.6 lbs Wire Gauge Acceptance: Min: 22 AWG; Max: 14 AWG
2-wire Compatibility Requirements
Min. Loop Voltage: 12.9 Volts DC Max. Loop Voltage: 14.5 Volts DC Max. Loop Resistance: 50 Ohms Max. Loop Ripple: 240 mVpp Max. Loading Capacitance: 0.01 mF Max. Alarm Current: 46 mA Max. Reset Voltage: 0.30 Volts DC Alarm Delay: n/a Min. Alarm Reset Time: 0.3 seconds Max. Normal Load Current: 2.4 mA Zone Type: Standard EOL Device: 3.9k Ohms (+-5%) Loop Style: B and D Compatibility Zone Identifier: A Detector Zone Identifier: A Max. Detectors Per Zone: (12) 2-wire i4 series model #COSMO-2W and/or i3 series model #2WTA-B detectors
BEFORE INSTALLATION
This information is included as a quick reference installation guide. Refer to the control panel installation manual for detailed system information. If the module will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Discon­nect power to the control panel before installing the module.
Notice: This manual should be left with the owner/user of this equipment. This product is intended for use in ordinary indoor locations.
GENERAL DESCRIPTION
The i4 series module is designed to interface between compatible i4 series combination CO/smoke detectors (Model COSMO-2W and COSMO-4W) and compatible security/fire panels. It can also be used to retrofit compatible i4 series detectors into an existing loop of i3 smoke detector models 2WTA-B or 4WTA-B, without adding wires. The module interprets signals and translates them into a separate smoke zone and a separate CO zone, each with alarm and trouble signals. When signaled by the panel, a module will synchronize connected detector sounders in either Temporal 3 or Temporal 4 pattern. Local status indication is provided by 4 LED’s and a 3 position DIP switch enables user configuration.
SS-500-004 1 I56-3871-001
4
The i
COSMOD2W, 2-wire interface module, offers additional functionality
including:
• Ability to query for a “need for maintenance” condition from 2-wire i4 series model COSMO-2W and i3 series model 2WTA-B smoke detectors
• One relay is available to indicate a multitude of maintenance conditions at the control panel
• All conditions are displayed at the module and at the detector
• EZ Walk test mode allows the installer to easily verify that all detectors on a loop are operational
• Allows 2-wire smoke detectors to be used on any compatible 4-wire control panel and provides Style D wiring on the detector loop
FEATURES
• Compatible with System Sensor i4 series combination CO/smoke detectors and System Sensor i3 Series smoke detectors models 2WTA-B or 4WTA-B.
• Allows up to 12 compatible devices including the i4 series combination CO/smoke detector to be integrated with a panel
3825 Ohio Avenue, St. Charles, Illinois 60174
www.systemsensor.com
• Allows sounder activation of all detectors on loop in either Temporal 3
HOLE FOR MOUNTING
or Temporal 4 pattern
VISIBLE ANNUNCIATON
The i4 series interface module has four visible LED’s: The green LED is a su­pervisory LED; it blinks during power on, reset, and during normal operation. The yellow LED is used to indicate a loop wiring fault and will blink when it is in EZ Walk test mode. The red LED signals smoke events; it blinks during smoke maintenance events and lights constantly during smoke alarm events. The blue LED signals CO events; it blinks during CO trouble or CO end-of-life, and lights constantly during CO alarm.
FIGURE 1: MODULE FRONT VIEW
Green LED
Yellow LED
Red LED
Blue LED
EZ Walk Test Switch (2-wire only)
S0331-00
TABLE 1: OPERATION MODES
OPERATION
MODE
Normal (standby) Blink 5 Sec. OFF OFF OFF
No power/ Non-operational
Loop wiring fault Blink 5 Sec. ON OFF OFF
EZ Walk Test Mode (2-wire only)
Alarm Smoke Blink 5 Sec. OFF ON OFF
Alarm CO Blink 5 Sec. OFF OFF ON
Alarm Smoke & CO Blink 5 Sec. OFF ON ON
Maintenance (2-wire only)
Freeze Trouble (2­wire only)
CO Trouble Blink 5 Sec. OFF OFF Blink 5 Sec.
GREEN
LED
OFF OFF OFF OFF
Blink 5 Sec. Blink 5 Sec. OFF OFF
Blink 5 Sec. OFF Blink 5 Sec. OFF
Blink 5 Sec. OFF Blink 10 Sec. OFF
YELLOW
LED
RED LED BLUE LED
NORMAL (STANDBY)
The module is powered and detectors on the loop are operating normally.
NO POWER/NON-OPERATIONAL
Power is not applied to the module or communication between the module and the detectors on the loop is unsuccessful.
LOOP WIRING FAULT
If an open circuit occurs on the loop, the module will indicate the condition by illuminating the yellow LED. 2-wire units will then power the style-D ter­minals. When the wiring issue on the loop has been resolved, the module will turn the yellow LED off.
EZ WALK TEST MODE
This indicates the module and detectors are in EZ Walk Test Mode. See “EZ Walk Test” section for instructions on how to initiate and perform the EZ Walk test.
ALARM SMOKE/ALARM CO/ALARM SMOKE & CO
A smoke alarm will be indicated by the red LED. A CO alarm will be indicated by the blue LED.
A smoke alarm is not self-restoring. Once a smoke alarm has been signaled, the red LED will illuminate until the module is reset by removal of power.
Note: On some panels, resetting a smoke alarm may require additional steps
at the keypad to clear the trouble conditions on CO and smoke mainte­nance zones due to power loss to the module.
A CO alarm is self-clearing. Once a CO alarm has been signaled, the blue LED will illuminate. Once the initiating device ceases to signal the CO event, the blue LED will turn off. If a CO alarm is signaled, and not cleared, prior to a smoke alarm condition, the module will keep both the blue and red LED’s illuminated. If a smoke alarm is signaled first, the module will not be able to receive notification of a CO alarm condition and will not be able to report it to the panel.
MAINTENANCE
This condition means one or more detectors on the loop have a smoke main­tenance issue. See “Smoke Maintenance Inquiry” section for further details.
FREEZE TROUBLE
This condition means one or more detectors on the loop are measuring the ambient temperature is near the freezing point. See “Freeze Trouble Inquiry” section for further details.
CO TROUBLE
The module can be notified of a detector with a CO trouble condition. All CO trouble conditions will be reported on the CO zone and displayed with a blink­ing blue LED. The module is not able to determine the number of detectors that have a CO trouble condition or which trouble condition exists.
INSTALLATION MOUNTING
The module can be mounted to a 4-11/16 inch back box or inside a listed, dedi- cated enclosure. When mounting inside an enclosure with pre-stamped holes, it may be easier to align the bottom screw hole first. It is not necessary to use the module cover when mounting inside an enclosure.
FIGURE 2: MOUNTING
TO VISTA ENCLOSURE
(No. 6x3/4 Type AB)
SLOT FOR MOUNTING TO VISTA ENCLOSURE
(No. 6x5/16Type AB or Type F)
SLOTS FOR MOUNTING
TO 4-11/16 JUNCTION BOX
0331-00
WIRING GUIDELINES
All wiring must be installed in compliance with the NFPA 70 standards, Na­tional Electrical Code, applicable state and local codes, and any special re­quirements at the local Authority Having Jurisdiction (AHJ).
The screw terminals in the mounting base will accept 14-22 gauge wire. Wire connections are made by stripping approximately ¼” of insulation from the end of the feed wire, inserting it into the proper base terminal, and tightening the screw to secure the wire in place. Do not put wires more than 2 gauge apart under the same clamping plate.
Note: The module must be installed in the same room and within 20 feet of the panel and enclosed within conduit or equivalently protected against me­chanical injury.
WARNING
Remove power from alarm control unit or initiating device circuits before in­stalling detectors.
SS-500-004 2 I56-3871-001
Loading...
+ 2 hidden pages