System Sensor i3 Series, i3 2WTR-B, i3 2WTA-B, i3 4WTR-B, i3 4WTA-B Installation And Maintenance Instructions Manual

...
INSTALLATION AND MAINTENANCE INSTRUCTIONS
WARNING
Photoelectric Smoke Detector
2-Wire: 2WTR-B (Form C Relay), 2WTA-B (Sounder) 4-Wire: 4WTR-B (Form C Relay), 4WTA-B (Sounder) 4WTAR-B (Form C Relay, Sounder), 4WITAR-B (Isolated Thermal, Form C Relay, Sounder)
Before Installing
Please read thoroughly System Sensor Application Guide: System Smoke Detectors, which provides detailed information
on detector spacing, placement, zoning, wiring, and special applications. Copies are available on System Sensor’s web site: www.systemsensor.com.
NOTICE: This manual shall be left with the owner/user of this equipment.
IMPORTANT: This detector must be tested and maintained regu­larly following National Fire Protection Association (NFPA) 72 National Fire Alarm Code requirements. At a minimum, cleaning should be performed annually.
General Description
Models 2WTR-B and 2WTA-B are 2-wire photoelectric smoke detectors; models 4WTR-B, 4WTA-B, 4WTAR-B, and 4WITAR-B are 4-wire photoelectric smoke detectors. All models incorpo­rate a state-of-the-art optical sensing chamber and an advanced microprocessor. The microprocessor allows the detector to auto­matically adjust its sensitivity back to the factory setting when it becomes more sensitive due to contaminants settling in its chamber. In order for this feature to work properly, the chamber must never be opened while power is applied to the smoke detec­tor. This includes cleaning, maintenance or screen replacement. All models also feature a restorable, built-in, fixed temperature (135°F) thermal detector and are also capable of sensing a freeze condition if the temperature is below 41°F.
Models 2WTA-B, 4WTA-B, 4WTAR-B, and 4WITAR-B contain a piezoelectric horn which generates the ANSI S3.41 temporal pat­tern in an alarm condition. All detectors on a zone will sound when the power supply to them is reversed. The RRS-MOD can be used for the power supply reversal function. The RRS-MOD also enables all the detectors’ sounders on a zone to be synchronized and allows the zone to be silenced from the panel by entering the alarm silence key at the keypad.
The detector that initiated the alarm condition will have its red LED and Form C relays (if applicable) latched until reset by panel.
The model 4WITAR-B photoelectronic smoke sensor is isolated from the fixed-temperature heat sensor, providing a self-resetting, local audible smoke alarm that does not alarm at the panel. Only the fixed-temperature heat sensor will cause the 4WITAR-B to ini­tiate an alarm at the panel and the relay to change its state.
NOTE: In order for all i3 sounder detectors on a loop to sound when the panel alarms, the supply voltage polarity must be reversed. A reversing relay, System Sensor model number RRS-MOD, must be used. The RRS-MOD is designed to allow all i3 Series detectors in the same loop to sound when one of the detectors goes into alarm. In addition, the RRS-MOD will
D100-99-00 1 I56-2170-04R
synchronize all of the i3 Series sounder smoke detectors on the loop. Some panels may require the use of programmable outputs. Refer to System Sensor literature for further informa­tion on the RRS-MOD.
All i3 Series detectors are designed to provide open area protec­tion. Two-wire models must be used with compatible UL Listed panels only.
When used with an “i3 Ready” control panel or the i3 Series 2W­MOD2 module (refer to installation manual), the 2WTR-B and 2WTA-B are capable of generating a “maintenance needed” sig­nal. The 2W-MOD2 can indicate a need for cleaning, replacement, or a freeze trouble at the control panel or module.
The 2W-MOD2 has replaced the previous model number 2W­MOD. To ensure proper remote maintenance signaling capabili­ties, do not use the 2W-MOD with i3 model numbers 2WTR-B and 2WTA-B.
Installation of the 2WTR-B, 2WTA-B, 4WTR-B, 4WTA-B, 4WTAR­B, and 4WITAR-B detectors is simplified by the use of a mounting base that may be pre-wired to the system, allowing the detector to be easily installed or removed. The mounting base installation is further simplified by the incorporation of features compatible with drywall fasteners.
Two LEDs on the detector provide a local visual indication of the detector’s status:
Table 1: Detector LED Modes
| Green LED | Red LED Power-up | Blink 10 sec | Blink 10 sec Normal (standby) | Blink 5 sec | — Out of sensitivity | — | Blink 5 sec Freeze Trouble | — | Blink 10 sec Alarm | — | Solid
During an initial power-up delay, the red and green LEDs will blink synchronously once every ten seconds. It will take approximately 80 seconds for the detector to finish the power-up cycle (see Table 2).
Table 2: Power-up Sequence for LED Status Indication*
Condition | Duration Initial LED Status Indication | 80 seconds Initial LED Status Indication (if excessive electrical noise is present) | 4 minutes
*Refer to Electrical Specifications for start-up time in conjuction with panel alarm verification.
NOTE: If, during power-up, the detector determines there is exces­sive electrical noise in the system such as those caused by improp­er grounding of the system or the conduit, both LEDs will blink for up to 4 minutes before displaying detector status (see Table 2).
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
|
After power-up has completed and the detector is functioning
SNAP OFF TAB FOR TAMPER LOCK
TAMPER RELEASE TAB
DIRECT MOUNT HOLES
2-WIRE ZONE
2-WIRE CONTROL PANEL
+
(5)
RA –
(4)
RA +
(3)
– IN/OUT
(2)
+ OUT
(1)
+ IN
RA400Z
EOL RESISTOR
OPTIONAL RELEASING DEVICE
(6) NC
(7) C
(8) NO
NOT INCLUDED ON 2WTA-B MODEL
normally within its listed sensitivity range, the green LED blinks once every five seconds. If the detector is in need of maintenance because its sensitivity has shifted outside the listed limits, the red LED blinks once every five seconds. When the detector is in the alarm mode, the red LED latches on. The LED indication must not be used in lieu of the tests specified under Testing. In a freeze trouble condition, the red LED will blink once every 10 seconds (refer to Table 1).
To measure the detector’s sensitivity, the i3 Series Model SENS­RDR Infrared Sensitivity Reader tool (see Figure 4) should be used. Refer to instructions manual D100-98-00 for the proper use of the SENS-RDR.
Models 2WTR-B and 2WTA-B also include an output that allows an optional Model RA400Z Remote Annunciator to be connected.
Mounting
General spacing guidelines are 30′× 30, with each detector cover­ing 900 ft2 under maximum conditions.
Consult NFPA 72, the local Authority Having Jurisdiction (AHJ), and/or applicable codes for specific information regarding the spacing and placement of smoke detectors.
Each i3 Series detector is supplied with a mounting base that can be ceiling- or wall-mounted:
1. To a single gang box, or
2. To a 31⁄2-inch or 4-inch octagonal box, or
3. To a 4-inch square box with a plaster ring, or
4. Direct mount or to ceiling using drywall fasteners.
Figure 1: Mounting of Detector
Figure 2: Tamper-Resistant Feature
S0109-00
Wiring Installation Guidelines
All wiring must be installed in compliance with the NFPA 70, National Electrical Code, applicable state and local codes, and any special requirements of the local Authority Having Jurisdiction.
Proper wire gauges should be used. The conductors used to con­nect smoke detectors to the alarm control panel and accessory devices should be color-coded to reduce the likelihood of wiring errors. Improper connections can prevent a system from respond­ing properly in the event of a fire.
The screw terminals in the mounting base will accept 14–22 gauge wire. For best system performance, all wiring should be installed in separate grounded conduit; do not mix fire alarm system wiring in the same conduit as any other electrical wiring. Twisted pair may be used to provide additional protection against extraneous electrical interference.
Wire connections are made by stripping approximately 1⁄4-inch of insu- lation from the end of the feed wire, inserting it into the proper base terminal, and tightening the screw to secure the wire in place. Do not put wires more than 2 gauge apart under the same clamping plate.
Two-Wire Compatibility
System Sensor two-wire smoke detectors are marked with a com­patibility identifier located on the label on the back of the product. For two-wire models 2WTR-B and 2WTA-B, connect detectors only
S0121-00
The i3 Series heads and bases are keyed so that all heads will only fit into their respective bases. One model 4-wire relay base will accept the 4WTR-B, 4WTAR-B and 4WITAR-B detector heads and no others. The 2WTR-B, 2WTA-B and 4WTA-B will only fit into their respective mounting bases and no others. The heads and bases are clearly iden­tified as either 2-wire or 4-wire. When mounting the i3 Series, ensure that the head is mounted to the correct base, and the test switch is aligned with the tamper release tab.
to compatible alarm control panels as identified by System Sensor’s two-wire compatibility chart, available at www.systemsensor.com.
NOTE: Models 2WTR-B and 2WTA-B are not to be installed
on initiating circuits containing other makes/models of smoke detectors.
NOTE: Style D initiating circuits require the use of a 2W-
MOD2 for models 2WTR-B and 2WTA-B
Wiring Diagrams Figure 3a: Wiring Diagram, 2WTR-B and 2WTA-B
Tamper-Resistant Feature
The i3 Series detectors include a tamper-resistant feature that pre­vents removal from the mounting base without the use of a tool. To engage the tamper-resistant feature, cut the small plastic tab located on the mounting base (Figure 2), and then install the detec­tor. To remove the detector from the base once it has been made tamper resistant, use a small screwdriver to depress the square tamper release tab, located on the skirt of the mounting base, and turn the detector counterclockwise.
Installation Guidelines
The i3 Series detectors represent an advancement over the previous sounder and Form C relay models and are designed to be used with the 2W-MOD2 and RRS-MOD only. Do not mix detector models on a zone.
D100-99-00 2 I56-2170-04R
NOTE: FOR ALL COMPATIBLE ADEMCO PANELS,
DO NOT EXCEED 30 OHMS LINE IMPEDANCE.
NOTE: ONLY ONE 2WTR-B DETECTOR PER ZONE CAN BE USED.
S0122-00
NOTE: Only one 2WTA-B detector shall be installed on a zone,
AUX OR SMOKE POWER
IDC
4-WIRE CONTROL PANEL
+
+
(
5 )
A
(
4 )
A
(
3 )
– IN/OUT
(
2 )
+ OUT
(
1 )
+ IN
EOL RELAY (
A77-716B
)
EOL RESISTOR
(
5 )
A
(
4 )
A
(
3 )
– IN/OUT
(
2 )
+ OUT
(
1 )
+ IN
NOT INCLUDED ON 4WTA-B MODEL
NOT INCLUDED ON 4WTA-B MODEL
OPTIONAL RELEASING DEVICE
(6) NC
(7) C
(8) NO
OPTIONAL RELEASING DEVICE
(6) NC
(7) C
(8) NO
WARNING
CAUTION
LED
RECESSED TEST SWITC
H
POSITION SENS-RDR AT
AN ANGLE ON THE OVAL AREA OR AT THE CHAMBER OPENIN
G
BY
THE WORD “PAINT”
PUSH RECESSED SWITCH WITH A
0.18 MAX.
DIAMETER
TOOL
WARNING
unless the panel switches the zone to a reverse polarity, non-cur­rent limited power supply. For panels that do not provide this fea­ture, a reversing relay, System Sensor model RRS-MOD, may be used. When utilized with the 2WTA-B, it allows for more than one detector to be utilized on a loop. Some panels may require the use of programmable outputs. Refer to System Sensor literature for further information on the RRS-MOD. The 2WTA-B detector shall not be mixed with other 2-wire detectors on the same zone.
Figure 3b: Wiring Diagram, 4WTR-B, 4WTA-B, 4WTAR-B, and 4WITAR-B
prevent any unwanted alarms.
Ensure proper wiring and power is applied. After power up, allow
80 seconds for the detector to stabilize before testing.
Test i3 Series detectors as follows: A. Test Switch
1. An opening for the recessed test switch is located on the detector housing (See Figure 4).
2. Insert a small screwdriver or allen wrench (0.18 max.) into the test switch opening; push and hold.
3. If the detector is within the listed sensitivity limits, the detector’s red LED should light within one second.
Figure 4: Recessed Test Switch Opening and SENS-RDR Position
B. Smoke Entry Test
S0110-00
Hold a smoldering punk stick or cotton wick at the side of the
S0123-00
Installation
detector and gently blow the smoke through the detector until
it alarms. C. Direct Heat Method Using a 1000-1500 watt hair dryer, direct the heat toward either
Remove power from alarm control unit or initiating device circuits before installing detectors.
NOTE: To install units so that corresponding LEDs are lined up, refer to the “Green LED” indicator on the base.
1. Wire the mounting base screw terminals per Figure 3a or Figure 3b, as applicable.
2. Place detector on the base and rotate clockwise. The detector will drop into the base and lock into place with a “click”.
3. After all detectors have been installed, apply power to the alarm control unit.
4. Test each detector as described in Testing.
5. Reset all the detectors at the alarm control unit.
6. Notify the proper authorities that the system is in operation.
of the thermistors. Hold the heat source about 12 inches from the detector to avoid damage to the plastic.
NOTE: For the above tests, the detector will reset only after the power source has been momentarily interrupted. It is not necessary to reset the model 4WITAR-B, when smoke is used to initiate the alarm.
When testing the 4WITAR-B model, pressing the test switch will result in a non-latching local alarm that does not alarm at the con­trol panel. Once the test button is released, the unit will return to its standby condition. Only the fixed-temperature heat sensor will cause the 4WITAR-B to initiate an alarm at the panel.
If a detector fails any of the above test methods, its wiring should be checked and it should be cleaned as outlined in the Maintenance section. If the detector still fails, it should be replaced.
Notify the proper authorities when the system is back in service.
Dust covers are an effective way to limit the entry of dust into the smoke detector sensing chamber during construction. However, they may not completely prevent airborne dust particles from entering the detector. Therefore, System Sensor recommends the removal of detectors before beginning construction or other dust producing activity. When returning the system to service, be sure to remove the dust covers from any detectors that were left in place during construction.
Testing
Detectors must be tested after installation and following maintenance.
NOTE: Before testing, notify the proper authorities that mainte­nance is being performed and the system will be temporarily out of service. Disable the zone or system undergoing maintenance to
D100-99-00 3 I56-2170-04R
Loop Verification (models 2WTR-B and 2WTA-B only)
Loop verification is provided by the EZ Walk loop test feature. This feature is for use with i3 Series compatible control panels or the i3 Series 2W-MOD2 module only. The EZ Walk loop test veri­fies the initiating loop wiring and provides visual status indica­tion at each detector. Refer to System Sensor literature for further information on the 2W-MOD2.
The 2W-MOD2 has replaced the previous model number 2W­MOD. To ensure proper EZ Walk Test capabilities, do not use the 2W-MOD with i3 model numbers 2WTR-B and 2WTA-B.
Table 3: EZ Walk Test Detector Modes
REMOVABLE DETECTOR COVER
SCREEN/SENSING CHAMBER (TOP HALF)
DETECTOR HOUSING
|Green LED |Red LED Proper Operation |Double blink 5 sec |— Out of Sensitivity |— |Double Blink 5 sec Freeze Condition |— |Double Blink 10 sec
NOTE: The EZ Walk loop test must not be used instead of alarm
testing.
Maintenance
NOTE: Before performing maintenance on the detector, notify the proper authorities that maintenance is being performed and the system will be temporarily out of service. Disable the zone or system undergoing maintenance to prevent any unwanted alarms.
Power must be removed from the detector before performing maintenance of any kind.
1. Remove the detector cover by turning counterclockwise. (See Figure 5.)
2. Vacuum the cover or use canned air to remove any dust or debris.
3. Remove the top half of the screen/sensing chamber by lifting straight up (Figure 5).
4. Vacuum or use canned air to remove any dust or particles that are present on both chamber halves.
5. Replace the top half of the screen/sensing chamber by aligning the arrow on the screen/sensing chamber with the arrow on the housing. Press down firmly until the screen/sensing chamber is fully seated.
6. Replace the detector cover by placing it over the screen/sensing chamber and turning it clockwise until it snaps into place.
7. Reinstall the detector and test. (See the Testing section.)
8. Notify the proper authorities when the system is back in service.
Figure 5: Removing Screen/Sensing Chamber
S0111-00
Electrical Specifications 2-wire 4-wire
System Voltage –Nominal: 12/24 12/24 V (Non-polarized for 2WTR-B and 4WTR-B) Min.: 8.5 10 V Max.: 35 35 V Max. Ripple Voltage: 30 30 % peak to peak of applied voltage Avg. Standby Current: 50 50 µA average Peak Standby Current: 100 — µA Max. Alarm Current 4WTA-B, 4WTR-B: — 35 mA 4WTAR-B, 4WITAR-B: — 50 mA 2WTR-B: 130 — mA panel must limit current 2WTA-B: 130* Alarm Contact Ratings: — 0.5 A @ 30 V AC/DC Form C Contact Ratings: 2 2 A @ 30 V AC/DC Audible Signal (temp-3 tone): 85 85 dBA min. in alarm or supply polarity reversed (Sounder units only) Remote Annunciator Output: 7 — mA maximum EOL Relay: — 12/24 A77-716B Reset Time (min): 0.3 0.3 seconds Max. Start-up Capacitance: 0.1 — µF Max. Initial Start-up Time: 45 15 seconds Alarm Verification** Start-up Time: 15 15 seconds
* Direct Power (Non-reverse Polarity): 130 mA limited by panel.
Reverse Polarity Power: 30 mA for the 2WTA-B in alarm; 12 mA for all other 2WTA-B units on the loop. Add 25 mA for the RRS-MOD reversing relay alarm current.
** Assumes the panel’s alarm verification reset time is 10 seconds or less. Should the
alarm verification reset exceed 10 seconds, use the maximum initial start-up time.
Physical Specifications
Heat Sensor: 135°F (57.2°C) Freeze Trouble: 41°F (5°C) Operating Temperature Range: 32 to 100°F (0 to 37.8°C) Operating Humidity Range: 0 to 95% RH non-condensing Storage Temperature Range: –4 to 158°F (–20 to 70°C) Diameter (including base): 5.3 inches Height (including base): 2.0 inches Weight: 7.1 oz.
Please refer to insert for the Limitations of Fire Alarm Systems
Three-Year Limited Warranty
System Sensor warrants its enclosed smoke detector to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express war­ranty for this smoke detector. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the replacement of any part of the smoke detector which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Returns Department, RA
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the
equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: – Reorient or relocate the receiving antenna. – Increase the separation between the equipment and receiver. – Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. – Consult the dealer or an experienced radio/TV technician for help.
FCC Statement
D100-99-00 4 I56-2170-04R ©System Sensor 2003
#__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or con­sequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
Loading...