System Sensor DH200RPL User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
FOAM
GASKETS
SAMPLING TUBE
SAMPLING TUBE
FILTERS
DETECTOR
COVER
DETECTOR BOARD
CONDUIT HOLES
DETECTOR
HOUSING
TERMINAL STRIP
POWER BOARD
COVER MOUNTING
SCREWS
DH200RPL Intelligent Air Duct Smoke Detector with Extended Air Speed Range
Before installing detectors, please thoroughly read the NEMA Guide for
Proper Use of Smoke Detectors in Duct Applications, which provides
detailed information on detector spacing, placement, zoning, wiring,
and special applications. Copies of this manual are available from
NEMA (National Electrical Manufacturers Association, 2101 L Street NW,
erenced for detailed information.
NOTICE: This manual shall be left with the owner/user of this
equipment.
lowing NFPA 72 requirements. The detector should be cleaned at least
once a year.
General Description
An HVAC system supplies conditioned air to virtually every area of
uted to the entire building. Smoke detectors designed for use in air
duct systems are used to sense the presence of smoke in the duct.
The DH200RPL air duct smoke detector is photoelectric detector. This
smoke detection method combines with an efficient housing design that
samples air passing through a duct and allows detection of a developing
hazardous condition. When sufficient smoke is sensed, an alarm signal is
initiated at the fire control panel monitoring the detector, and appropriate
action can be taken to shut off fans, blowers and change over air handling
systems, etc. This can prevent the distribution or it can isolate toxic smoke
and fire gases throughout the areas served by the duct system.
Two LEDs on each detector may illuminate, if programmed by the system
control panel, to provide a local alarm indication. There is also a remote
alarm output for use with auxiliary devices. The DH200RPL has remote
test capability with the RTS451/RTS451KEY Remote Test Station.
The DH200RPL incorporates a cover tamper feature. When the cover is
removed for more than 20 minutes, the unit loses communication at the
panel, a trouble is indicated at the panel and the alarm relay switches
states thereby shutting down fans, dampers and blowers. In the case
when the sensor is removed or when there is no power to the unit, only a
trouble is indicated at the panel (alarm relay does not work any longer).
3825 Ohio Avenue, St. Charles, Illinois 60174
800/736-7672, FAX: 630-377-6495
www.systemsensor.com
Contents of the Duct Smoke Detector Housing Kit
The DH200RPL Duct Smoke Detector consists of the following items
(See Figure 1.):
Figure 1. Exploded View Of Duct Smoke Detector Components:
NOTE: For ducts over 11⁄2 feet (0.46m), longer sampling tubes must be ordered to complete the installation. They must be the correct length for the
width of the duct where they will be installed. See Table 1 on page 3 to determine the sampling tube required for different duct widths.
D200-39-00 1 I56-1977-004R
Contents Of The Duct Smoke Detector
1. Complete duct smoke detector assembly with
sensor
2. Two #10 x 11⁄4 sheet metal mounting screws
3. Two sampling tube filters
4. One test magnet
5. Drilling template
6. Two foam gaskets
7. Four #6-self tapping mounting screws for the
sampling tube and optional exhaust tube
extension
8. One sampling tube end cap
9. One plastic sampling tube
10. One #8 self-tapping screw for plastic sampling
tube
NOTE: A detector sensor board DOES NOT need to
be ordered separately.
Limitations of Duct Detectors
WARNING
WARNING
WARNING
WARNING
The National Fire Protection Association has established that DUCT
DETECTORS MUST NOT BE USED AS A SUBSTITUTE FOR OPEN AREA
DETECTOR PROTECTION as a means of providing life safety. Nor are they
a substitute for early warning in a building’s regular fire detection system.
It is strongly recommended that the user read NFPA Standards 90A, 72,
and 101.
This device will not operate without electrical power. Fire situations
may cause an interruption of power. The system safeguards should be
discussed with your local fire protection specialist.
ing.
In order to function properly, this detector must be installed according to
the instructions. Do not exceed the electrical or ambient specifications or
the detector will not function properly. This detector must be protected
from the elements.
Installation Sequence
Step 1. Verify duct air flow direction and velocity ...........................2
Step 2. Drill the mounting holes .....................................................2
Step 2.1 Install the sampling tube for ducts
less than 11⁄2 feet (0.46m) wide ...........................................2
Step 3. Secure the detector housing to the duct...............................2
Step 4. Install the sampling tube for ducts
greater than 11⁄2 feet (0.46m) wide ......................................2
Step 4.1 Installation for ducts greater than 11⁄2 feet
(0.46m) but less than 8 feet (2.4m) wide ............................3
Step 4.2 Installation for ducts more than 8 feet
(2.4m) wide.......................................................................4
Step 5. Install the filters .................................................................4
Step 6. Field wiring .......................................................................4
Step 7. Perform detector check.......................................................5
Step 8. Install the cover .................................................................5
Step 9. Detector Maintenance and Test Procedures..........................5
[1] Verify Duct Air Flow Direction And Velocity
dling systems having air velocities of 100 to 4000 feet per minute (0.5 to
20.32m/s). Be sure to check engineering specifications to ensure that the
air velocity in the duct falls within these parameters. If necessary, use a
velocity meter to check the air velocity in the duct. See Air Flow Test,
section 9.1.
[2] Drill The Mounting Holes
Remove the paper backing from the mounting template
supplied. Affix the template to the duct at the desired mounting location.
Make sure the template lies flat and smooth on the duct. Center punch holes A and B. Drill the holes as indicated on the template.
[2.1] Sampling Tube Installation for Ducts Less Than 11⁄2 Feet
(0.46m) Wide (see Figure 2)
1. Remove the front cover.
2. Slide the plastic sampling tube into the housing bushing.
3. Align the holes in the bushing with the holes in the sampling tube. Make
sure there are 6 exposed holes on the plastic sampling tube. Secure with the
#8 self-tapping screw into the bottom of the permanent tube (shown in Fig.
2).
NOTE: For ducts greater than 11⁄2 feet (0.46m) in width, refer to sec-
tions [4], [4.1] and [4.2].
[3] Secure The Detector Housing To The Duct
Slide the foam gaskets over the tube bushings as shown in Figure 3. Use
the two 1
1
⁄4″ long sheet metal screws to screw the detector housing to
the duct.
CAUTION: Do not overtighten the screws.
[4] Sampling Tube Installation for Ducts Greater Than 11⁄2 Feet
(0.46m) Wide
The sampling tube is identified by a series of air inlet holes on the tube.
A plastic tube is included for ducts up to 11⁄2 feet (0.46m) wide. All other
fied in Table 1, for width of the duct where it will be installed. It is recom-
mended that the sampling tube length extend at least 2⁄3 across the duct
width for optimal performance. The exhaust tube is molded onto the base
of the duct housing, and the A2440-00 Exhaust Tube Extension is available
as an accessory in those cases where the molded exhaust port does not
extend at least 2 inches (50mm) into the duct.
The sampling tube is always installed with the air inlet holes facing into
the air flow. To assist proper installation, the tube’s mounting flange is
marked with an arrow. Make sure the sampling tube is mounted so that
the arrow points into the air flow (see Figure 4). Figure 5 shows the
various combinations of tube mounting configurations with respect to air
flow. Mounting the detector housing in a vertical orientation is acceptable,
provided that a metal sampling tube is installed and the air flows directly
into the sampling tube holes as indicated in Figure 4.
Figure 2. Plastic sampling tube connected to duct smoke detector:
[4.1] Installation For Ducts Greater Than 11⁄2 Feet (0.46m) But
Less Than 8 Feet (2.4m) Wide
1. If the tube is longer than the width of the air duct, drill a 3⁄4 (19mm)
hole in the duct opposite the hole already cut for the sampling tube.
Make sure the hole is 1 to 2 (25 to 50mm) below the inlet hole on
the opposite side of the duct to allow moisture drainage away from the
detector. If the tube is shorter than the width of the air duct, install the
end cap into the sampling tube as shown in Figure 4. Sampling tubes
over 3 ft. (0.91m) long must be supported at the end opposite the duct
smoke detector.
D200-39-00 2 I56-1977-004R
SCREW HOLES FOR ATTA
CHING HOUSING
TO
DUCT WORK.
SAMPLING TUBE END CAP
AIR HOLES
ARROW
MUST
FACE
INTO AIR FLOW
AIR FLOW DIRECTION
FLANGE
AIR FLOW
DIRECTION
DETECTOR
HOUSING
DOTS INDICATE POSITION OF
SAMPLING TUBE HOLES
AIR FLOW
DIRECTION
DETECTOR
HOUSING
SAMPLING
TUBE
EXHAUST
TUBE
AIR FLOW
DIRECTION
EXHAUST
TUBE
SAMPLING
TUBE
SAMPLING
TUBE
EXHAUST
TUBE
DETECTOR
HOUSING
AIR FLOW
DIRECTION
DETECTOR
HOUSING
A.
B.
C.
D.
HORIZONTAL MOUNTING OF HOUSING
VERTICAL MOUNTING OF HOUSING
2. Slide the tube into the housing bushing that meets the air flow first.
Position the tube so that the arrow points into the air flow, as shown
in Figure 4.
3. Secure the tube flange to the housing bushing with two #6 self-tapping
screws.
4. For tubes longer than the width of the air duct, the tube should extend
out of the opposite side of the duct. If there are more than 2 holes in
the section of the tube extending out of the duct, select a different
length using Table 1. Otherwise, trim the end of the tube protruding
through the duct so that 1 to 2 (25 to 50mm) of the tube extend
outside the duct. Plug this end with the end cap and tape closed any
holes in the protruding section of the tube. Be sure to seal the duct
where the tube protrudes.
NOTE: The sampling tube end cap is critical to the proper operation of the
duct smoke detectors. The end cap is needed to create the proper air flow
to the sensor of the duct smoke detector.
Figure 5. Tube mounting configurations with varying air flow direction:
Figure 3. Installation of foam gaskets over sampling tube bushings:
NOTE: Only metal sampling tubes can be installed in
orientations C and D.
[4.2] Installation For Ducts More Than 8 Feet (2.4m) Wide
NOTE: To install sampling tubes in ducts more than 8 feet (2.4m) wide,
work must be performed inside the air duct. Sampling of air in
ducts wider than 8 feet (2.4m) is accomplished by using the
ST-10 sampling tube. If the tube is shorter than the width of the
air duct, install the end cap into the sampling tube as shown
in Figure 4 and support the end opposite the duct smoke detec-
tor.
Install the sampling tube as follows:
Table 1. Sampling tubes recommended for different duct widths:
Outside Duct Width Sampling Tube Recommended*
1 to 2 ft. (0.3 to 0.6 m) ST-1.5
2 to 4 ft. (0.6 to 1.2 m) ST-3
4 to 8 ft. (1.2 to 2.4 m) ST-5
8 to 12 ft. (2.4 to 3.7 m) ST-10
*Must extend a minimum of 2⁄3 the duct width
1. Drill a 3⁄4-inch (19mm) hole in the duct directly opposite the hole
already drilled for the sampling tube. Make sure the hole is 1 to 2
(25 to 50mm) below the inlet hole on the opposite side of the duct to
allow for moisture drainage.
2. Slide the sampling tube with the flange into the housing bushing that
meets the air flow first. Position the tube so that the arrow points into
the air flow. Secure the tube flange to the housing bushing with two
#6 self-tapping screws.
3. From inside the duct, couple the other sections of the sampling tube
Figure 4. Air duct detector sampling tube:
to the section already installed using the 1⁄2-inch conduit fittings sup-
plied. Make sure that the holes on both of the sampling tubes are lined
up and facing into the air flow.
4. Trim the end of the tube protruding through the duct so that 1 to 2
(25 to 50mm) of the tube extend outside the duct. Plug this end with
the end cap and tape closed any holes in the protruding section of the
tube. Be sure to seal the duct where the tube protrudes.
H0108-02
D200-39-00 3 I56-1977-004R
NOTE: An alternate method to using the ST-10 is to use two ST-5 sam-
pling tubes. Remove the flange from one of the tubes and install
as described above. After the installation, use electrical tape to
close off some of the sampling holes so that there are a total of
10 to 12 holes spaced as evenly as possible across the width of
the duct.
Loading...
+ 5 hidden pages