System Sensor DH100LP User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
WARNING
WARNING
WARNING
DH100LP Air Duct Smoke Detector with Extended Air Speed Range
The Innovair DH100LP model is a photoelectric detector approved for an extended air speed range of 100 to 4000 feet per minute (0.5 m/s to 20.3 m/s) and has an opera­tional temperature range of 32°F to 131°F (0°C to 55°C).
Before Installing
Please thoroughly read the System Sensor Guide for Proper Use of Smoke Detectors in Duct Applications (A05-1004),
which provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available online at www.systemsensor.com or via System Sensor’s toll free fax-back service, Documents on Demand at 800/736-7672. NFPA Standards 72 and 90A
should also be referenced for detailed information.
action can be taken to shut off fans, blowers, change over air handling systems, etc. These actions can facilitate the management of toxic smoke and fire gases throughout the areas served by the duct system.
DH100LP detectors are designed to operate with 12/24VDC UL listed compatible 2-wire control panels. Alarm current must be limited to 130mA or less by the control panel. Auxiliary relay contacts for control purposes are not avail­able for use with the DH100LP. Control must initiate from the control panel.
For testing, the alarm can be enabled by a magnet activated
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
test switch or by the optional remote test station. The duct
NOTICE: This manual shall be left with the owner/user of this equipment.
smoke detector latches into alarm state when an alarm occurs. A green LED flashes to indicate power, a red LED signals local alarm indication, and optional accessories
IMPORTANT: This detector must be tested and maintained
offer a variety of annunciation capabilities.
regularly following NFPA 72 requirements. The detector should be cleaned at least once a year.
The DH100LP can be reset by a momentary power interrup­tion, the reset button on the front cover, the control panel,
Table of Contents Page
or remote reset accessory.
[1] General Description ................................................... 1
[2] Limitations of Duct Smoke Detectors........................... 1
[2] Limitations Of Duct Smoke Detectors
[3] Exploded View of Duct Smoke Detector Components .. 2
[4] Contents of the Duct Smoke Detector Kit..................... 2
[5] Installation Sequence.................................................. 2
[6] Duct Smoke Detector Maintenance
and Test Procedures.................................................... 5
[7] Detector Cleaning Procedures...................................... 7
[8] Board Replacement..................................................... 7
[9] Specifications.............................................................. 8
The National Fire Protection Association has established that DUCT DETECTORS MUST NOT BE USED AS A SUBSTITUTE FOR OPEN AREA DETECTOR PROTECTION as a means of providing life safety. Nor are they a substi­tute for early warning in a building’s regular fire detection system.
Warranty........................................................................... 8
[1] General Description
An HVAC system supplies conditioned air to virtually every area of a building. Smoke introduced into this air duct
mends that the user read NFPA Standards 90A, 72, and 101. The DH100LP Air Duct Smoke Detectors are listed per UL 268A.
system will be distributed throughout the entire building. Smoke detectors designed for use in air duct systems are used to sense the presence of smoke in the duct.
This device will not operate without electrical power. Fire situations may cause an interruption of power. The
system safeguards should be discussed with your local fire protection specialist.
tion method when combined with an efficient housing design samples air passing through the duct and allows detection of a developing hazardous condition. When suf­ficient smoke is sensed, an alarm signal is initiated at the
This device will not sense smoke unless the ventilation system is operating and the cover is installed.
fire control panel monitoring the detector, and appropriate
D200-15-00 1 I56-0083-07R
WARNING
[3] Figure 1: Exploded View Of Duct Detector Components
FOAM
GASKETS
PLASTIC
SAMPLING TUBE
SAMPLING TUBE
FILTERS
PLASTIC SAMPLING TUBE
SELF-TAPPING SCREW
DETECTOR
COVER
DETECTOR BOARD
CONDUIT HOLES
DETECTOR
HOUSING
TERMINAL STRIP
POWER BOARD
COVER MOUNTING
SCREWS
For this detector to function properly, it MUST be installed according to the instructions in this manual. Furthermore, the detector MUST be protected from the elements and operated within ALL electrical and environmental specifi­cations listed in this manual. Failure to comply with these requirements may prevent the detector from activating when smoke is present in the air duct.
[4] Contents Of The Duct Smoke Detector Kit
1. Complete housing base and cover assembly
2.
Two #10 x 11⁄4
3. Two sampling tube filters
4. One test magnet
5. Drilling template
6. Two foam gaskets
7. Four #6-self tapping mounting screws for the metal sampling tube and optional exhaust tube extension
8. One sampling tube end cap
9. Metal sampling tube end plug
10. One plastic sampling tube
11. One #8 self-tapping screw for the plastic sampling tube
NOTE: For ducts over 11⁄2 feet, longer sampling tubes must
[5] Installation Sequence [5.1] Verify Duct Air Flow Direction And Velocity
Model DH100LP detectors are designed to be used in air handling systems having air velocities of 100 to 4000 feet per minute. Be sure to check engineering specifications to ensure that the air velocity in the duct falls within these parameters. If necessary, use a velocity meter (anemom­eter) to check the air velocity in the duct.
D200-15-00 2 I56-0083-07R
” sheet metal machine screws for mounting
be ordered to complete the installation. They must be the correct length for the width of the duct where they will be installed. See Table 1 on page 3 to determine the sampling tube required for differ­ent duct widths.
[5.2] Drill The Mounting Holes
Remove the paper backing from the mounting template supplied. Affix the template to the duct at the desired mounting location. Make sure the template lies flat and smooth on the duct. Center punch holes A and B. Drill the holes as indicated on the template.
[5.2.1] Sampling Tube Installation for Ducts Less Than 11⁄2 Feet Wide (see Figure 2)
1. Remove the front cover.
2. Slide the plastic sampling tube into the housing bushing.
3. Align the holes in the bushing with the holes in the sam­pling tube. Make sure there are six exposed holes on the plastic sampling tube. Secure with the #8 self-tapping screw into the bottom hole of the permanent tube.
NOTE: The sampling tube end cap is critical to the proper
operation of the duct smoke detector. The end cap is needed to create the proper air flow to the sensor of the duct smoke detector.
NOTE: For ducts greater than 11⁄2 feet in width, refer to
sections [5.4.1] and [5.4.2].
Figure 2. Sampling tubes connected to duct smoke
detector:
SAMPLING TUBE END CAP
AIR HOLES
ARROW
MUST
FACE
INTO AIR FLOW
AIR FLOW DIRECTION
FLANGE
AIR FLOW
DIRECTION
DETECTOR
HOUSING
DOTS INDICATE POSITION OF
SAMPLING TUBE HOLES
AIR FLOW
DIRECTION
DETECTOR
HOUSING
SAMPLING
TUBE
EXHAUST
TUBE
AIR FLOW
DIRECTION
EXHAUST
TUBE
SAMPLING
TUBE
SAMPLING
TUBE
EXHAUST
TUBE
DETECTOR
HOUSING
AIR FLOW
DIRECTION
DETECTOR
HOUSING
A.
B.
C.
D.
HORIZONTAL MOUNTING OF HOUSING
VERTICAL MOUNTING OF HOUSING
[5.3] Secure The Detector Housing To The Duct
SCREW HOLES FOR ATTA
CHING HOUSING
TO
DUCT WORK.
Slide the foam gaskets over the tube bushings as shown in Figure 3. Use the two 11⁄4″ long sheet metal screws to screw the detector housing to the duct.
CAUTION: Do not overtighten the screws.
Figure 3. Installation of foam gaskets over sampling tube bushings:
H0107-00
[5.4] Sampling Tube Installation of Ducts Greater Than 11⁄2 Feet Wide
The sampling tube is identified by a series of air inlet holes on the tube. One plastic tube is included for ducts up to 18 in width. All other lengths must be purchased separately. Order the correct length, as specified in Table 1, for width of the duct where it will be installed. It is recommended that the sampling tube length extend at least 2⁄3″ across the duct width for optimal performance. The exhaust tube is molded onto the base of the duct housing, and the A2440-00 Exhaust Tube Extension is available as an accessory in those cases where the molded exhaust port does not extend at least 2 inches into the duct.
the inlet hole on the opposite side of the duct to allow for moisture drainage. If the tube is shorter than the width of the air duct, install the end cap into the sampling tube as shown in Figure 4. Sampling tubes over 3 ft. long must be supported at the end opposite the duct detector.
2. Slide the tube into the housing bushing that meets the
air flow first. Position the tube so that the arrow points into the air flow.
3. Secure the tube flange to the housing bushing with two
#6 self-tapping screws.
4. For tubes longer than the width of the air duct, the tube
should extend out of the opposite side of the duct. If there are more than 2 holes in the section of the tube extending out of the duct, select a different length using Table 1. Otherwise, trim the end of the tube protruding through the duct so that 1 to 2 of the tube extend out­side the duct. Plug this end with the end cap and tape closed any holes in the protruding section of the tube. Be sure to seal the duct when the tube protrudes.
NOTE: The sampling tube end cap is critical to the proper
operation of the duct smoke detector. The end cap is needed to create the proper air flow to the sensor of the duct smoke detector.
Figure 4. Air duct detector inlet sampling tube:
The sampling tube is always installed with the air inlet holes facing into the air flow. To assist proper installation, the tube’s mounting flange is marked with an arrow. Make sure the sampling tube is mounted so that the arrow points
Figure 5. Tube mounting configurations with varying air flow direction:
into the air flow (see Figure 4). Figure 5 shows the various combinations of tube mounting configurations with respect to air flow. Mounting the detector housing in a vertical ori­entation is acceptable, provided that the air flows directly into the sampling tube holes as indicated in Figure 4.
Table 1. Sampling tubes recommended for different duct widths:
Outside Duct Width Sampling Tube Recommended*
1 to 2 ft. ST-1.5 2 to 4 ft. ST-3 4 to 8 ft. ST-5 8 to 12 ft. ST-10
2
the duct width
3
NOTE: Only metal sampling tubes may be used on ori­entations C and D.
*Must extend a minimum of
[5.4.1] Installation For Ducts Greater Than 11⁄2 Feet But Less Than 8 Feet Wide
1. If the tube is longer than the width of the air duct, drill a
3
4-inch hole in the duct opposite the hole already cut for
the sampling tube. Make sure the hole is 1 to 2 below
D200-15-00 3 I56-0083-07R
H0108-02
H0109-01
WARNING
WARNING
In no case should more than 2 air inlet holes be cut off the tube. There must be a minimum of 10 holes in the tube exposed to the air stream.
[5.4.3] Modifications of Sampling Tubes
There may be applications where duct widths are not what is specified for the installation. In such cases, it is permis­sible to modify a sampling tube that is longer than neces­sary to span the duct width.
[5.4.2] Installation For Ducts More Than 8 Feet Wide
NOTE: To install sampling tubes in ducts more than 8
feet wide, work must be performed inside the air duct. Sampling of air in ducts wider than 8 feet is accomplished by using the ST-10 sampling tube. If the tube is shorter than the width of the air duct, install the end cap into the sampling tube as shown in Figure 4 and support the end opposite the duct smoke detector.
Install the sampling tube as follows:
1. Drill a 3⁄4-inch hole in the duct opposite the hole already drilled for the sampling tube. Drill the hole 1 to 2 below the inlet hole on the opposite side of the duct to allow for moisture drainage away from the detector.
2. Slide the sampling tube with the flange into the housing bushing that meets the air flow first. Position the tube so that the arrow points into the air flow. Secure the tube flange to the housing bushing with two #6 self-tapping screws.
3. From inside the duct, couple the other sections of the sampling tube to the section already installed using the
1
⁄2-inch conduit fittings supplied. Make sure that the holes on both of the air inlet tubes are lined up and fac­ing into the air flow.
4. Trim the end of the tube protruding through the duct so that 1 to 2 of the tube extend outside the duct. Plug this end with the end cap and tape closed any holes in the protruding section of the tube. Be sure to seal the duct when the tube protrudes.
NOTE: An alternate method to using the ST-10 is to use
two ST-5 sampling tubes. Remove the flange from one of the tubes and install as described above. After the installation, use electrical tape to close off some of the sampling holes so that there are a total of 10 to 12 holes spaced as evenly as possible across the width of the duct.
NOTE: Air currents inside the duct may cause excessive vibration, especially when the longer sampling tubes are used. In these cases a 3 inch floor flange (available at most plumbing supply stores) may be used to fasten the sam­pling tube to the other side of the duct. When using the flange/connector mounting technique, drill a 1 to 11⁄4 inch hole where the flange will be used.
NOTE: This procedure should only be used as a temporary
fix. It is not intended as a permanent substitute for ordering the correct length tubes.
[5.5] Install The Filters
To install the sampling tube filters, simply push the filters into the sampling and exhaust tube holes as shown in Figure 6. If a metal sampling tube is used, install the filter over the sampling tube.
Figure 6. Sampling tube filter installation:
[5.6] Field Wiring Installation Guidelines
All wiring must be installed in compliance with the National Electrical Code and the local codes having juris­diction. Proper wire gauges should be used. The conduc­tors used to connect smoke detectors to control panels and accessory devices should be color-coded to prevent wiring mistakes. Improper connections can prevent a system from responding properly in the event of a fire.
D200-15-00 4 I56-0083-07R
For signal wiring, (the wiring between interconnected detectors or from detectors to auxiliary devices), it is usu­ally recommended that single conductor wire be no smaller than 18 gauge. The duct smoke detector terminals accom­modate wire sizes up to 12 gauge. The last foot of conduit should be flexible conduit (available in electrical supply houses), which facilitates easier installation and puts less strain on the conduit holes in the housing. Solid conduit connections may be used if desired.
Smoke detectors and alarm system control panels have specifications for allowable loop resistance. Consult the control panel manufacturer’s specifications for the total loop resistance allowed for the particular model control panel being used before wiring the detector loop.
Wiring Instructions
The DH100LP detectors are designed for easy wiring. The housing provides a terminal strip with clamping plates. Wiring connections are made by stripping about 3/8-inch of insulation from the end of the wire, sliding the bare end under the plate, and tightening the clamping plate screw. The DH100LP duct smoke detector is designed to operate with 12 or 24 VDC UL listed 2-wire compatible control pan­els. Alarm current must be limited by the control panel to 100mA or less. An example of a UL listed compatible con­trol panel is the Fire-Lite model Sensiscan 1000 using zone card ANC-2 and compatibility identification “A”. Install per installation instruction S1000/801. A maximum of 20 detec­tors may be installed per zone.
[5.7] Perform Detector Check
1. Perform STANDBY AND TROUBLE TEST per Section
[6.2.1].
2. Perform MAGNET TEST per Section [6.2.2.1]. The
RTS451 test of Section [6.2.2.2] may substitute for this requirement.
3. Perform AIR FLOW TEST per Section [6.1.1].
4. Perform SMOKE RESPONSE TEST per Section [6.1.2].
5. Perform SENSITIVITY TEST per Section [6.2.3].
[5.8] Install The Cover
Install the cover using the six screws that are captured in the housing cover. Be certain filters are installed as speci­fied in Section [5.5]. Make sure that the cover fits into the base groove and that all gaskets are in their proper posi­tions. Tighten the six screws.
[6] Duct Smoke Detector Maintenance And Test Procedures
Test and maintain duct smoke detectors as recommended in NFPA 72. The tests contained in this manual were devised to assist maintenance personnel in verification of proper detector operation.
Before conducting these tests, notify the proper authorities that the smoke detection system will be temporarily out of
service. Disable the zone or system under test to prevent unwanted alarms.
[6.1] Smoke Entry Tests [6.1.1] Air Flow
The DH100LP is designed to operate over an extended air speed range of 100 to 4000 FPM. To verify sufficient sampling of ducted air, turn the air handler on and use a manometer to measure the differential pressure between the two sam­pling tubes. The differential pressure should measure at least
0.0015 inches of water and no more than 1.2 inches of water. Because most commercially available manometers cannot accurately measure very low pressure differentials, applica­tions with less than 500 FPM of duct air speed may require one of the following: 1) the use of a current-sourcing pressure transmitter (Dwyer Series 607) per Section 6.1.4 or; 2) the use of aerosol smoke per section 6.1.2.
[6.1.2] Air Flow Test using Aerosol Smoke
This test is intended for low-flow systems (100-500FPM). If the air speed is greater than 500FPM, use a conventional manometer to measure differential pressure between the sampling tubes as described in 6.1.1. Drill a 1⁄4” hole 3 feet upstream from the duct smoke detector. With the air handler on, measure the air velocity with an anemometer. Air speed must be at least 100 FPM. Spray aerosol smoke* into the duct through the 1⁄4” hole for five seconds. Wait two minutes for the duct smoke detector to alarm. If the duct smoke detector alarms, air is flowing through the detector. Remove the duct smoke detector cover and blow out the residual aerosol smoke from the chamber and reset the duct smoke detector. Use duct tape to seal the aerosol smoke entry hole.
*Aerosol smoke can be purchased from Home Safeguard Industries, Malibu, CA. Phone: 310/457-5813.
[6.1.3] Smoke Entry Test
[6.1.4] Air Flow Test using Dwyer Series 607 Differential Pressure Transmitter
Verify the air speed of the duct using an anemometer. Air speed must be at least 100 FPM. Wire the Dwyer transmit­ter as shown in Figure 7. Connect the leads of the meter to either side of the 1000Ω resistor. Allow unit to warm up for 15 seconds. With both HIGH and LOW pressure ports open to ambient air, measure and record the voltage drop acrossthe 1000Ω resistor (measurement 1), 4.00 volts is typical. Using flexible tubing and rubber stoppers, connect the HIGH side of the transmitter to the sampling tube of
D200-15-00 5 I56-0083-07R
DETECTOR
BOARD
7 6
4
(+) IN (+) OUT
(+)
(+)
5
8
(–)
(–) IN (–) OUT
1ST DETECTOR IN LOOP DH100LP
(–)
RA400Z (OPTIONAL) REMOTE ALARM LED
2.8 VDC NOM. IN ALARM
DETECTOR
BOARD
7 6
4
(+) IN (+) OUT
(+)
(+)
5
8
(–
)
(–) IN (–) OUT
LAST DETECTOR IN LOOP DH100LP
(–
)
RA400Z (OPTIONAL) REMOTE ALARM LED
2.8 VDC NOM. IN ALARM
E O L R
STYLE D OPTIONAL WIRING
UL LISTED COMPATIBLE 2-WIRE CONTROL PANEL
ALARM INITIATION LOOP
(+)
(–)
EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER
CAUTION
1
2
3
4
5
3
4
5
Test +
Test / Reset
Reset
+
Test
Reset
RA +
RA –
DH100LP
RTS451/RTS451KEY
2
1
Alarm
LED
the duct smoke detector housing, and the LOW side of the
DIFFERENTIAL
PRESSURE
TRANSMITTER
HIGH
LOW
TO SAMPLING TUBE
TO EXHAUST TUBE
VOLT METER
FLUKE MODEL 87
OR EQUIVALENT
1000 OHM 5% 1 WATT RESISTOR
9 VOLT
BATTER
Y
9 VOL
T
BATTER
Y
9 VOL
T
BATTER
Y
15 TO 36VDC
SUPPL
Y
Figure 7. Procedure for verifying air flow:
[6.1.5] Filter Replacement
The filters do not substantially affect smoke performance even when up to 90% of the filter is clogged. Quarterly visual inspection usually suffices to determine whether the filters should be replaced because only a high percentage of contamination affects performance. If further testing is required, compare differential pressure readings with and without the filters installed. If the difference exceeds 10% replace the filters. In no case should the pressure differen­tial fall below 0.0015 inches of water.
[6.2] Standby, Alarm, And Sensitivity Tests [6.2.1] Standby And Trouble
Standby — Look for the presence of the flashing green
LED through the transparent housing cover. The LED should flash approximately every 10 seconds.
Trouble — If the Green LED does not flash, then the de-
tector lacks power (check wiring, panel, or power supply), the detector board is missing (replace), or the unit is defective (return for replacement).
Figure 8. System wiring diagram for 2-wire duct smoke detectors (detectors powered from initiating circuit):
Do not loop wire under terminals when wiring detectors. Break wire runs to provide system supervision of connections.
A78-2696-00
Figure 9. Wiring diagram for the DH100LP to RTS451/RTS451KEY:
D200-15-00 6 I56-0083-07R
A78-2697-00
Test — The trouble condition can be caused inten-
tionally to verify correct operation of the sys­ tem. Remove the detector board to cause a trouble condition locally and at the system control panel.
[6.2.2] Alarm Tests [6.2.2.1] M02-04-00 Magnet Test
1. Place the painted surface of the magnet onto the TEST
locator on the bottom of the housing (Figure 9).
2. The red alarm LEDs on the detector should latch on,
as should any accessories (i.e. RA400Z, RTS451). Verify system control panel alarm status, and control panel execution of all intended auxiliary functions (i.e. fan shutdown, damper control, etc.).
3. The detector must be reset by the system control panel,
the local reset button, or the remote accessory.
Figure 10. Testing detector alarm:
If test module readings indicate that the detector head is outside of the acceptable range that is printed on the label of the detector, the detector requires cleaning per Section [7] of this manual.
[7] Detector Cleaning Procedures
[7.1] Air Filters
1. Turn off power to the system.
2. Remove and inspect sampling tube filters.
3. If filters are heavily coated with dirt, replace them with new filters. If they are not heavily coated, use a vacuum cleaner or compressed air nozzle to remove dust, then reinstall the filters.
[7.2] Photo Detector Boards
1. Remove the screen by gently grasping on each side and pulling straight off
2. Lift the photo chamber in the same fashion. Vacuum the screen and cover. Use clean, compressed air to loosen and blow out any remaining debris. Replacement screens (S08-39-01) are available.
3. Vacuum photo chamber, then use clean compressed air to blow area clean.
4. Replace the chamber by pressing it onto the base. Press the screen into place. It should fit tightly on the chamber.
[6.2.2.2] RTS451/RTS451KEY Remote Test Station
The RTS451/RTS451KEY Remote Test Station facilitates test of the alarm capability of the duct smoke detector as indicated in the RTS451/RTS451KEY manual. The DH100LP duct smoke detector can be reset by the RTS451/RTS451KEY. If a system control panel is used, the panel itself may also require testing.
To install the RTS451/RTS451KEY, connect the device as shown in Figure 9; wire runs must be limited to 25 ohms or less per interconnecting wire.
[6.2.3] Sensitivity Tests [6.2.3.1] MOD400 or MOD400R Test
After verification of alarm capability, use the MOD400R test module with a voltmeter to check detector sensitivity as indicated in the test module’s manual. The housing cover must be removed to perform this test.
[8.0] Board Replacement [8.1] Detector Board Replacement (part no. A5180)
1. Remove the two detector board mounting screws.
2. Pull gently on the board to remove it.
3. To replace the board, align the board mounting features, holes, and the interconnect terminals. Push the board into place.
4. Secure board with the two mounting screws.
[8.2] Power Board replacement (par t no. A5061)
1. Disconnect wiring from the terminal block.
2. Remove the two power board mounting screws.
3. Pull gently on the board to remove it.
4. To replace the board, align the board mounting features, holes, and the interconnect terminals. Push the board into place.
5. Secure board with the two mounting screws.
6. Re-connect wiring to terminal block.
D200-15-00 7 I56-0083-07R
[9] Model DH100LP Air Duct Smoke Detector Specifications
Operating Temperature: +32° to +131° F 0° to +55° C Storage Temperature: –22° to +158° F –30° to +70° C Humidity: 10% to 93% R.H. noncondensing Air Velocity: 100 to 4000 ft./min. 0.5 to 20.3 m/sec. Dimensions: 14.38” L x 5.5” W x 2.75” D 36.5cm L x 14cm W x 7cm D Weight: 3.25 pounds 1.5 kg
Electrical Ratings — includes base and detector
System Voltage: 12/24 VDC Maximum Ripple Voltage: 4 Volts peak to peak Start-up Capacitance: 0.02 µF maximum Standby Ratings: 8.5 VDC minimum 35 VDC maximum 120 µA maximum Alarm Ratings: 4.2 VDC minimum at 10mA
6.6 VDC maximum at 130mA Alarm current must be limited to 130mA or less by the control panel. If used, the RA400Z remote lamp operates within the specified alarm currents. Reset Voltage: 2.50 VDC minimum Reset Time: 0.3 Sec. maximum Start-up Time: 34.0 Sec. maximum
Please refer to insert for the Limitations of Fire Alarm Systems
Three-Year Limited Warranty
System Sensor warrants its enclosed air duct smoke detector to be free from defects in materials and workmanship under normal use and ser­vice for a period of three years from date of manufacture. System Sensor makes no other express warranty for this air duct smoke detector. No agent, representative, dealer, or employee of the Company has the author­ity to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the air duct smoke detector which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Returns Department, RA #__________, 3825 Ohio
D200-15-00 8 I56-0083-07R
©2003 System Sensor
Avenue, St. Charles, IL 60174. Please include a note describing the mal­function and suspected cause of failure. The Company shall not be obli­gated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
Loading...