System Sensor DH100ACDCLWP User Manual

D200-24-00 1 I56-0056-07R
DH100ACDCLWP Watertight Air Duct Smoke Detector with Extended Air Speed Range
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
800/736-7672, FAX: 630-377-6495
www.systemsensor.com
The Innovair DH100ACDCLWP is a photoelectric extended air speed range duct smoke detector with a NEMA 4 Rated watertight housing. This detector is specially designed for use in either indoor or outdoor applications to provide a degree of protection against falling dirt, rain, sleet, wind­blown dust, splashing water and hose-directed water.
The DH100ACDCLWP is listed for an extended air speed range of 100 to 4000 feet per minute (0.5 m/s to 20.2 m/s).
IMPORTANT NOTES The following temperature limitations must be observed during the installation and handling of this product: Operating temperature: +32° to +131°F (0° to + 55°C) Storage temperature: –22° to +158°F (–30° to +70°C)
To maintain the watertight properties of this duct smoke detector, watertight conduit and fittings must be used. Mount the product with the conduit holes facing down­wards, if possible.
Before Installing
Please thoroughly read the System Sensor Guide for Proper Use of Smoke Detectors in Duct Applications, which provides
detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available online at www.systemsensor.com or via System Sensor’s toll free fax-back service, Documents on Demand at 800/736-7672. NFPA Standards 72 and 90A should also be ref­erenced for detailed information. NOTICE: This manual shall be left with the owner/user of this equipment.
IMPORTANT: This detector must be tested regularly follow­ing NFPA 90 requirements. The detector should be cleaned at least once a year.
Table of Contents Page
[1] General Description 1 [2] Limitations of Duct Smoke Detectors 1 [3] Exploded View of Duct Smoke Detector Components 2 [4] Contents of the Duct Smoke Detector Kit 2 [5] Installation Sequence 2 [6]
Duct Smoke Detector Maintenance and Test Procedures
5 [7] Detector Cleaning Procedures 7 [8] Board Replacement 8 [9] Specifications 8 Warranty 8
[1] General Description
An HVAC system supplies conditioned air to virtually every area of a building. Smoke introduced into this air duct sys­tem will be distributed to the entire building. Smoke detec­tors designed for use in air duct systems are used to sense the presence of smoke in the duct.
Model DH100ACDCLWP Air Duct Smoke Detector is sup­plied as a photoelectronic model. This smoke detection method is combined with an efficient housing design that samples air passing through a duct and allows detection of a developing hazardous condition. When sufficient smoke is sensed, an alarm signal is initiated and appropriate action can be taken to shut off fans, blowers, change over air handling systems, etc. These actions can facilitate the management of toxic smoke and fire gases throughout the areas served by the duct system.
The DH100ACDCLWP detector is designed to operate on 24 VDC/VAC, 120 VAC, or 240 VAC. Alarm and supervisory relay contacts are available for control panel interface (alarm initiation), HVAC control, and other auxiliary functions. Auxiliary relays are also provided for fan shut down or sig­naling of up to 9 other detectors in the loop for multiple fan shut down. These detectors are not designed for 2-wire applications.
For testing, the alarm can be enabled by a magnet activated test switch or by the optional remote test station. The duct smoke detector latches into alarm state when an alarm occurs. Prior to cover installation, the green LED should be flashing, indicating that the detector is powered and func­tioning. To accurately determine detector status following installation, System Sensor offers a variety of remote annunciation and test accessories.
The DH100ACDCLWP can be reset by a momentary power interruption, the reset button on the front cover, the control panel, or remote reset accessory. The DH100ACDCLWP
incorporates a cover tamper feature that provides a trou­ble signal after 7 minutes if the cover is removed or improperly installed. Proper reinstallation of the cover
removes the trouble condition.
[2] Limitations Of Duct Smoke Detectors
The National Fire Protection Association has established that DUCT DETECTORS MUST NOT BE USED AS A SUBSTITUTE FOR OPEN AREA DETECTOR PROTECTION as a means of pro­viding life safety. Nor are they a substitute for early warning in a building’s regular fire detection system.
System Sensor supports this position and strongly recommends that the user read NFPA Standards 90A, 72, and 101. The DH100ACDCLWP Air Duct Smoke Detectors are listed per UL 268A.
This device will not operate without electrical power.
Fire situations may cause an interruption of power. The system safeguards should be discussed with your local fire protection specialist.
WARNING
WARNING
This device will not sense smoke unless the ventilation sys­tem is operating and the cover is installed.
For this detector to function properly, it MUST be installed according to the instructions in this manual. Furthermore, the detector MUST be operated within ALL electrical and environmental specifications listed in this manual. Failure to comply with these requirements may prevent the detec­tor from activating when smoke is present in the air duct.
[4] Contents Of The Duct Smoke Detector Kit
1. Complete housing base and cover assembly
2. Two #10×11⁄4″ sheet metal screws for mounting
3. Two sampling tube filters
4. One test magnet
5. Drilling template
6. Two foam gaskets
7. Four #6-self tapping mounting screws for the metal sampling tube and optional exhaust tube extension
8. One sampling tube end cap
9. One plastic telescoping sampling tube
10. One #8 self-tapping screw for the plastic sampling tube
NOTE: For ducts over 11⁄2 feet, longer sampling tubes must
be ordered to complete the installation. They must be the correct length for the width of the duct where they will be installed. See Table 1 on page 3 to determine the sampling tube required for differ­ent duct widths.
[5] Installation Sequence [5.1] Verify Duct Air Flow Direction And Velocity
Model DH100ACDCLWP detectors are designed to be used in air handling systems having air velocities of 100 to 4000 feet per minute. Be sure to check engineering specifications to ensure that the air velocity in the duct falls within these parameters. If necessary, use a velocity meter to check the air velocity in the duct.
WARNING
WARNING
[5.2] Select Mounting Orientation
If possible, mount the DH100ACDCLWP with the wiring entry hole(s) facing downwards, so that all wiring enters the housing from below. This minimizes the possibility of water entering around the conduit fittings. Mounting the product with the wiring entry holes on the uppermost sur­face should be avoided.
[5.3] Drill The Mounting Holes
Remove the paper backing from the mounting template supplied. Affix the template to the duct at the desired mounting location. Make sure the template lies flat and smooth on the duct. Center punch holes A and B. Drill the holes as indicated on the template.
[5.4] Secure The Detector Housing To The Duct
Slide the foam gaskets over the tube bushings as shown in Figure 2. Use the two 11⁄4″ long sheet metal screws to screw the detector housing to the duct.
CAUTION: Do not overtighten the screws.
Figure 2. Installation of foam gaskets over sampling tube bushings:
[5.5] Sampling Tube Installation
The sampling tube is identified by a series of air inlet holes on the tube. A plastic tube is included for ducts up to 18 in width. All other tubes must be ordered separately and resized for the duct width, as specified in Table 1. It is rec­ommended that the sampling tube length extend at least 2⁄3 across the duct width for optimal performance. The
D200-24-00 2 I56-0056-07R
[3] Figure 1: Exploded View Of Duct Smoke Detector Components
FOAM
GASKETS
METAL
SAMPLING TUBE
SAMPLING TUBE
FILTERS
DETECTOR
COVER
DETECTOR BOARD
CONDUIT HOLES
DETECTOR
HOUSING
TERMINAL STRIP
POWER BOARD
COVER MOUNTING
SCREWS
SCREW HOLES FOR ATTACHING HOUSING TO DUCT WORK.
exhaust tube is molded onto the base of the duct housing, and the A2440-00 Exhaust Tube Extension is available as an accessory in those cases where the molded exhaust port does not extend at least 2 inches into the duct. The sampling tube is always installed with the air inlet holes facing into the air flow. To assist proper installation, the tube’s mounting flange is marked with an arrow. Make sure the sampling tube is mounted so that the arrow points into the air flow (see Figure 3). Figure 4 shows the various combinations of tube mounting configurations with respect to air flow. Mounting the detector housing in a vertical ori­entation is acceptable, provided that the air flows directly into the sampling tube holes as indicated in Figure 3.
Table 1. Sampling tubes recommended for different duct widths:
Outside Duct Width Sampling Tube Recommended*
1 to 2 ft. ST-1.5 2 to 4 ft. ST-3 4 to 8 ft. ST-5
8 to 12 ft. ST-10
*Must extend a minimum of 2/3the duct width.
[5.5.1] Installation For Ducts Greater Than 11/2Feet But Less Than 8 Feet Wide
1. If the tube is longer than the width of the air duct, drill a
3
/4″ hole in the duct opposite the hole already cut for the sampling tube. Make sure the hole is 1″ to 2below the inlet hole on the opposite side of the duct to allow mois­ture drainage away from the detector. If the tube is short- er than the width of the air duct, install the end cap into the sampling tube as shown in Figure 4. Sampling tubes over 3 ft. long must be supported at the end opposite the duct smoke detector.
2. Slide the tube into the housing bushing that meets the air flow first. Position the tube so that the arrow points into the air flow.
3. Secure the tube flange to the housing bushing with two #6 self-tapping screws.
4. For tubes longer than the width of the air duct, the tube should extend out of the opposite side of the duct. If there are more than 2 holes in the section of the tube extending out of the duct, select a different length using Table 1. Otherwise, trim the end of the tube protruding through the duct so that 1to 2of the tube extend out­side the duct. Plug this end with the end cap and tape closed any holes in the protruding section of the tube. Be sure to seal the duct where the tube protrudes.
NOTE: The sampling tube end cap is critical to the proper
operation of the duct smoke detector. The end cap is needed to create the proper air flow to the sensor of the duct smoke detector.
Figure 3. Air duct detector sampling tube:
H0108-02
Figure 5. Tube mounting configurations with varying air flow direction:
H0109-01
NOTE: Only metal sampling tubes may be used on ori­entations C and D.
[5.5.2] Installation For Ducts More Than 8 Feet Wide
NOTE:
To install sampling tubes in ducts more than 8 feet wide, work must be performed inside the air duct. Sampling of air in ducts wider than 8 feet is accom­plished by using the ST-10 sampling tube. If the tube is shorter than the width of the air duct, install the end cap into the sampling tube as shown in Figure 4 and support the end opposite the duct smoke detector.
Install the inlet tube as follows:
1. Drill a 3/4-inch hole in the duct directly opposite the hole already drilled for the inlet tube. Make sure the hole is 1 to 2below the inlet hole on the opposite side of the duct to allow for moisture drainage.
2. Slide the sampling tube with the flange into the housing bushing that meets the air flow first. Position the tube so that the arrow points into the air flow. Secure the tube flange to the housing bushing with two #6 self-tapping screws.
3. From inside the duct, couple the other sections of the sampling tube to the section already installed using the
1
/2-inch conduit fittings supplied. Make sure that the holes on both of the air inlet tubes are lined up and fac­ing into the air flow.
4. Trim the end of the tube protruding through the duct so that 1 to 2of the tube extend outside the duct. Plug this end with the end cap and tape closed any holes in the protruding section of the tube. Be sure to seal the duct when the tube protrudes.
SAMPLING TUBE END CAP
AIR HOLES
ARROW
MUST FACE
INTO AIR FLOW
AIR FLOW DIRECTION
FLANGE
D200-24-00 3 I56-0056-07R
DOTS INDICATE POSITION OF
SAMPLING TUBE HOLES
AIR FLOW
DIRECTION
DETECTOR
HOUSING
AIR FLOW
DIRECTION
DETECTOR
HOUSING
AIR FLOW
DIRECTION
DETECTOR
HOUSING
A.
SAMPLING
EXHAUST
TUBE
TUBE
HORIZONTAL MOUNTING OF HOUSING
C.
VERTICAL MOUNTING OF HOUSING
EXHAUST
TUBE
SAMPLING
TUBE
EXHAUST
TUBE
SAMPLING
TUBE
B.
DETECTOR
HOUSING
AIR FLOW
DIRECTION
D.
Loading...
+ 5 hidden pages