System Sensor DH100ACDCLWP User Manual

D200-24-00 1 I56-0056-07R
DH100ACDCLWP Watertight Air Duct Smoke Detector with Extended Air Speed Range
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
800/736-7672, FAX: 630-377-6495
www.systemsensor.com
The Innovair DH100ACDCLWP is a photoelectric extended air speed range duct smoke detector with a NEMA 4 Rated watertight housing. This detector is specially designed for use in either indoor or outdoor applications to provide a degree of protection against falling dirt, rain, sleet, wind­blown dust, splashing water and hose-directed water.
The DH100ACDCLWP is listed for an extended air speed range of 100 to 4000 feet per minute (0.5 m/s to 20.2 m/s).
IMPORTANT NOTES The following temperature limitations must be observed during the installation and handling of this product: Operating temperature: +32° to +131°F (0° to + 55°C) Storage temperature: –22° to +158°F (–30° to +70°C)
To maintain the watertight properties of this duct smoke detector, watertight conduit and fittings must be used. Mount the product with the conduit holes facing down­wards, if possible.
Before Installing
Please thoroughly read the System Sensor Guide for Proper Use of Smoke Detectors in Duct Applications, which provides
detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available online at www.systemsensor.com or via System Sensor’s toll free fax-back service, Documents on Demand at 800/736-7672. NFPA Standards 72 and 90A should also be ref­erenced for detailed information. NOTICE: This manual shall be left with the owner/user of this equipment.
IMPORTANT: This detector must be tested regularly follow­ing NFPA 90 requirements. The detector should be cleaned at least once a year.
Table of Contents Page
[1] General Description 1 [2] Limitations of Duct Smoke Detectors 1 [3] Exploded View of Duct Smoke Detector Components 2 [4] Contents of the Duct Smoke Detector Kit 2 [5] Installation Sequence 2 [6]
Duct Smoke Detector Maintenance and Test Procedures
5 [7] Detector Cleaning Procedures 7 [8] Board Replacement 8 [9] Specifications 8 Warranty 8
[1] General Description
An HVAC system supplies conditioned air to virtually every area of a building. Smoke introduced into this air duct sys­tem will be distributed to the entire building. Smoke detec­tors designed for use in air duct systems are used to sense the presence of smoke in the duct.
Model DH100ACDCLWP Air Duct Smoke Detector is sup­plied as a photoelectronic model. This smoke detection method is combined with an efficient housing design that samples air passing through a duct and allows detection of a developing hazardous condition. When sufficient smoke is sensed, an alarm signal is initiated and appropriate action can be taken to shut off fans, blowers, change over air handling systems, etc. These actions can facilitate the management of toxic smoke and fire gases throughout the areas served by the duct system.
The DH100ACDCLWP detector is designed to operate on 24 VDC/VAC, 120 VAC, or 240 VAC. Alarm and supervisory relay contacts are available for control panel interface (alarm initiation), HVAC control, and other auxiliary functions. Auxiliary relays are also provided for fan shut down or sig­naling of up to 9 other detectors in the loop for multiple fan shut down. These detectors are not designed for 2-wire applications.
For testing, the alarm can be enabled by a magnet activated test switch or by the optional remote test station. The duct smoke detector latches into alarm state when an alarm occurs. Prior to cover installation, the green LED should be flashing, indicating that the detector is powered and func­tioning. To accurately determine detector status following installation, System Sensor offers a variety of remote annunciation and test accessories.
The DH100ACDCLWP can be reset by a momentary power interruption, the reset button on the front cover, the control panel, or remote reset accessory. The DH100ACDCLWP
incorporates a cover tamper feature that provides a trou­ble signal after 7 minutes if the cover is removed or improperly installed. Proper reinstallation of the cover
removes the trouble condition.
[2] Limitations Of Duct Smoke Detectors
The National Fire Protection Association has established that DUCT DETECTORS MUST NOT BE USED AS A SUBSTITUTE FOR OPEN AREA DETECTOR PROTECTION as a means of pro­viding life safety. Nor are they a substitute for early warning in a building’s regular fire detection system.
System Sensor supports this position and strongly recommends that the user read NFPA Standards 90A, 72, and 101. The DH100ACDCLWP Air Duct Smoke Detectors are listed per UL 268A.
This device will not operate without electrical power.
Fire situations may cause an interruption of power. The system safeguards should be discussed with your local fire protection specialist.
WARNING
WARNING
This device will not sense smoke unless the ventilation sys­tem is operating and the cover is installed.
For this detector to function properly, it MUST be installed according to the instructions in this manual. Furthermore, the detector MUST be operated within ALL electrical and environmental specifications listed in this manual. Failure to comply with these requirements may prevent the detec­tor from activating when smoke is present in the air duct.
[4] Contents Of The Duct Smoke Detector Kit
1. Complete housing base and cover assembly
2. Two #10×11⁄4″ sheet metal screws for mounting
3. Two sampling tube filters
4. One test magnet
5. Drilling template
6. Two foam gaskets
7. Four #6-self tapping mounting screws for the metal sampling tube and optional exhaust tube extension
8. One sampling tube end cap
9. One plastic telescoping sampling tube
10. One #8 self-tapping screw for the plastic sampling tube
NOTE: For ducts over 11⁄2 feet, longer sampling tubes must
be ordered to complete the installation. They must be the correct length for the width of the duct where they will be installed. See Table 1 on page 3 to determine the sampling tube required for differ­ent duct widths.
[5] Installation Sequence [5.1] Verify Duct Air Flow Direction And Velocity
Model DH100ACDCLWP detectors are designed to be used in air handling systems having air velocities of 100 to 4000 feet per minute. Be sure to check engineering specifications to ensure that the air velocity in the duct falls within these parameters. If necessary, use a velocity meter to check the air velocity in the duct.
WARNING
WARNING
[5.2] Select Mounting Orientation
If possible, mount the DH100ACDCLWP with the wiring entry hole(s) facing downwards, so that all wiring enters the housing from below. This minimizes the possibility of water entering around the conduit fittings. Mounting the product with the wiring entry holes on the uppermost sur­face should be avoided.
[5.3] Drill The Mounting Holes
Remove the paper backing from the mounting template supplied. Affix the template to the duct at the desired mounting location. Make sure the template lies flat and smooth on the duct. Center punch holes A and B. Drill the holes as indicated on the template.
[5.4] Secure The Detector Housing To The Duct
Slide the foam gaskets over the tube bushings as shown in Figure 2. Use the two 11⁄4″ long sheet metal screws to screw the detector housing to the duct.
CAUTION: Do not overtighten the screws.
Figure 2. Installation of foam gaskets over sampling tube bushings:
[5.5] Sampling Tube Installation
The sampling tube is identified by a series of air inlet holes on the tube. A plastic tube is included for ducts up to 18 in width. All other tubes must be ordered separately and resized for the duct width, as specified in Table 1. It is rec­ommended that the sampling tube length extend at least 2⁄3 across the duct width for optimal performance. The
D200-24-00 2 I56-0056-07R
[3] Figure 1: Exploded View Of Duct Smoke Detector Components
FOAM
GASKETS
METAL
SAMPLING TUBE
SAMPLING TUBE
FILTERS
DETECTOR
COVER
DETECTOR BOARD
CONDUIT HOLES
DETECTOR
HOUSING
TERMINAL STRIP
POWER BOARD
COVER MOUNTING
SCREWS
SCREW HOLES FOR ATTACHING HOUSING TO DUCT WORK.
exhaust tube is molded onto the base of the duct housing, and the A2440-00 Exhaust Tube Extension is available as an accessory in those cases where the molded exhaust port does not extend at least 2 inches into the duct. The sampling tube is always installed with the air inlet holes facing into the air flow. To assist proper installation, the tube’s mounting flange is marked with an arrow. Make sure the sampling tube is mounted so that the arrow points into the air flow (see Figure 3). Figure 4 shows the various combinations of tube mounting configurations with respect to air flow. Mounting the detector housing in a vertical ori­entation is acceptable, provided that the air flows directly into the sampling tube holes as indicated in Figure 3.
Table 1. Sampling tubes recommended for different duct widths:
Outside Duct Width Sampling Tube Recommended*
1 to 2 ft. ST-1.5 2 to 4 ft. ST-3 4 to 8 ft. ST-5
8 to 12 ft. ST-10
*Must extend a minimum of 2/3the duct width.
[5.5.1] Installation For Ducts Greater Than 11/2Feet But Less Than 8 Feet Wide
1. If the tube is longer than the width of the air duct, drill a
3
/4″ hole in the duct opposite the hole already cut for the sampling tube. Make sure the hole is 1″ to 2below the inlet hole on the opposite side of the duct to allow mois­ture drainage away from the detector. If the tube is short- er than the width of the air duct, install the end cap into the sampling tube as shown in Figure 4. Sampling tubes over 3 ft. long must be supported at the end opposite the duct smoke detector.
2. Slide the tube into the housing bushing that meets the air flow first. Position the tube so that the arrow points into the air flow.
3. Secure the tube flange to the housing bushing with two #6 self-tapping screws.
4. For tubes longer than the width of the air duct, the tube should extend out of the opposite side of the duct. If there are more than 2 holes in the section of the tube extending out of the duct, select a different length using Table 1. Otherwise, trim the end of the tube protruding through the duct so that 1to 2of the tube extend out­side the duct. Plug this end with the end cap and tape closed any holes in the protruding section of the tube. Be sure to seal the duct where the tube protrudes.
NOTE: The sampling tube end cap is critical to the proper
operation of the duct smoke detector. The end cap is needed to create the proper air flow to the sensor of the duct smoke detector.
Figure 3. Air duct detector sampling tube:
H0108-02
Figure 5. Tube mounting configurations with varying air flow direction:
H0109-01
NOTE: Only metal sampling tubes may be used on ori­entations C and D.
[5.5.2] Installation For Ducts More Than 8 Feet Wide
NOTE:
To install sampling tubes in ducts more than 8 feet wide, work must be performed inside the air duct. Sampling of air in ducts wider than 8 feet is accom­plished by using the ST-10 sampling tube. If the tube is shorter than the width of the air duct, install the end cap into the sampling tube as shown in Figure 4 and support the end opposite the duct smoke detector.
Install the inlet tube as follows:
1. Drill a 3/4-inch hole in the duct directly opposite the hole already drilled for the inlet tube. Make sure the hole is 1 to 2below the inlet hole on the opposite side of the duct to allow for moisture drainage.
2. Slide the sampling tube with the flange into the housing bushing that meets the air flow first. Position the tube so that the arrow points into the air flow. Secure the tube flange to the housing bushing with two #6 self-tapping screws.
3. From inside the duct, couple the other sections of the sampling tube to the section already installed using the
1
/2-inch conduit fittings supplied. Make sure that the holes on both of the air inlet tubes are lined up and fac­ing into the air flow.
4. Trim the end of the tube protruding through the duct so that 1 to 2of the tube extend outside the duct. Plug this end with the end cap and tape closed any holes in the protruding section of the tube. Be sure to seal the duct when the tube protrudes.
SAMPLING TUBE END CAP
AIR HOLES
ARROW
MUST FACE
INTO AIR FLOW
AIR FLOW DIRECTION
FLANGE
D200-24-00 3 I56-0056-07R
DOTS INDICATE POSITION OF
SAMPLING TUBE HOLES
AIR FLOW
DIRECTION
DETECTOR
HOUSING
AIR FLOW
DIRECTION
DETECTOR
HOUSING
AIR FLOW
DIRECTION
DETECTOR
HOUSING
A.
SAMPLING
EXHAUST
TUBE
TUBE
HORIZONTAL MOUNTING OF HOUSING
C.
VERTICAL MOUNTING OF HOUSING
EXHAUST
TUBE
SAMPLING
TUBE
EXHAUST
TUBE
SAMPLING
TUBE
B.
DETECTOR
HOUSING
AIR FLOW
DIRECTION
D.
NOTE: An alternate method to using the ST-10 is to use
two ST-5 sampling tubes. Remove the flange from one of the tubes and install as described above. After the installation, use electrical tape to close off some of the sampling holes so that there are a total of 10 to 12 holes spaced as evenly as possible across the width of the duct.
NOTE: Air currents inside the duct may cause excessive
vibration, especially when the longer sampling tubes are used. In these cases a 3 inch floor flange (available at most plumbing supply stores) may be used to fasten the sampling tube to the other side of the duct. When using the flange/connector mounting technique, drill a 1-inch to 11/4-inch hole where the flange will be used.
[5.5.3] Modifications of Sampling Tubes
There may be applications where duct widths are not what is specified for the installation. In such cases, it is permis­sible to modify a sampling tube that is longer than neces­sary to span the duct width.
Use a 0.193-inch diameter (#11) drill and add the appropriate number of holes so that the total number of holes exposed to the air flow in the duct is 10 to 12. Space the additional holes as evenly as possible over the length of the tube.
NOTE: This procedure should only be used as a temporary
fix. It is not intended as a permanent substitute for ordering the correct length tubes.
[5.6] Install The Filters
To install the sampling tube filters, simply push the filters into the sampling and exhaust tube holes, as shown in Figure 5.
Figure 5. Sampling tube filter installation:
Filters require periodic cleaning or replacement, depending on the amount of dust and dirt accumulated. Visually inspect the filters at least quarterly; inspect them more often if the dust accumulation warrants it. See Section [6] for more information. For replacement filters, contact your Innovair distributor. (Exhaust tube/intake tube filter P/N F36-09-11)
CAUTION
[5.7] Field Wiring Installation Guidelines
All wiring must be installed in compliance with the National Electrical Code and the local codes having juris­diction. Proper wire gauges should be used. The conduc­tors used to connect smoke detectors to control panels and accessory devices should be color-coded to prevent wiring mistakes. Improper connections can prevent a system from responding properly in the event of a fire. For signal wiring, (the wiring between interconnected detectors or from detectors to auxiliary devices), it is usu­ally recommended that single conductor wire be no small­er than 18 gauge. The duct smoke detector terminals accommodate wire sizes up to 12 gauge. In order to achieve NEMA 4 environmental protection, watertight conduit and fittings must be used when installing the DH100ACDCLWP.
Smoke detectors and alarm system control panels have specifications for allowable loop resistance. Consult the control panel manufacturer’s specifications for the total loop resistance allowed for the particular model control panel being used before wiring the detector loop.
Wiring Instructions
The DH100ACDCLWP detectors are designed for easy wiring. The housing provides a terminal strip with clamp­ing plates. Wiring connections are made by stripping about
3
/8-inch of insulation from the end of the wire, sliding the bare end under the plate, and tightening the clamping plate screw.
[5.8] Perform Detector Check
1. Perform STANDBY AND TROUBLE TEST per Section
[6.2.1].
2. Perform MAGNET TEST per Section [6.2.2.1]. The
RTS451 test of Section [6.2.2.2] may substitute for this requirement.
3. Perform AIR FLOW TEST per Section [6.1.1].
4. Perform SMOKE RESPONSE TEST per Section [6.1.2].
5. Perform SENSITIVITY TEST per Section [6.2.3].
[5.9] Install The Cover
Install the cover using the six screws that are captured in the housing cover. Be certain filters are installed as speci­fied in Section [5.6]. Make sure that the cover fits into the base groove and that all gaskets are in their proper posi­tions. Tighten the six screws.
[6] Duct Smoke Detector Maintenance And Test Procedures
As recommended in NFPA 90, all smoke detection devices designated for automatic shutdown shall be tested annually. The tests in this manual are designed to assist installation and maintenance personnel in verification of proper detector operation.
D200-24-00 4 I56-0056-07R
Before conducting these tests, notify the proper authorities that the smoke detection system will be temporarily out of service. Disable the zone or system under test to prevent unwanted alarms.
[6.1] Smoke Entry Tests [6.1.1] Air Flow
The DH100ACDCLWP is designed to operate over an extended air speed range of 100 to 4000 FPM. To verify suf­ficient sampling of ducted air, turn the air handler on and use a manometer to measure the differential pressure between the two sampling tubes. The differential pressure should measure at least 0.0015 inches of water and no more than 1.4 inches of water. Because most commercially available manometers cannot accurately measure very low pressure differentials, applications with less than 500 FPM of duct air speed may require one of the following: 1) the use of a current-sourcing pressure transmitter (Dwyer Series 607) per Section 6.1.4 or; 2) the use of aerosol smoke per Section 6.1.2.
[6.1.2] Air Flow Test using Aerosol Smoke
This test is intended for low-flow systems (100-500FPM). If the air speed is greater than 500FPM, use a conventional manometer to measure differential pressure between the sampling tubes as described in 6.1.1. Drill a 1⁄4″ hole 3 feet upstream from the duct smoke detector. With the air han­dler on, measure the air velocity with an anemometer. Air speed must be at least 100 FPM. Spray aerosol smoke* into the duct through the 1⁄4″ hole for five seconds. Wait two min- utes for the duct smoke detector to alarm. If the duct smoke detector alarms, air is flowing through the detector. Remove the duct smoke detector cover and blow out the residual aerosol smoke from the chamber and reset the duct smoke detector. Use duct tape to seal the aerosol smoke entry hole.
*Aerosol smoke can be purchased from several maufacturers, including Home Safeguard Industries, Malibu, CA. Phone: 310/457-5813.
[6.1.3] Smoke Entry Test
To determine if smoke is capable of entering the sensing chamber, visually identify any obstructions. With the cover removed, plug the exhaust and inlet tube holes to prevent ducted air from carrying smoke away from the detector head, then blow smoke such as cigarette, cotton wick, or punk directly at the head to cause an alarm. REMEMBER TO REMOVE THE PLUGS AFTER THIS TEST, OR THE DETECTOR WILL NOT FUNCTION PROPERLY.
[6.1.4] Air Flow Test using Dwyer Series 607 Differential Pressure Transmitter
To verify the air speed of the duct using an anemometer, air velocity must be at least 100 FPM. Disconnect power and remove cover. Remove both foam air filters from the inlet and exhaust tubes. Wire the Dwyer transmitter as shown in Figure 6. Connect the leads of the meter to either side of the 1000 Ω resistor. Allow unit to warm up for 15 seconds. With both HIGH and LOW pressure ports open to ambient air,
measure and record the voltage drop across the 1000 resistor (measurement 1), 4.00 volts is typical. Using flexi­ble tubing and rubber stoppers, connect the HIGH side of the transmitter to the sampling tube of the duct smoke detector housing, and the LOW side of the transmitter to the exhaust tube of the duct smoke detector housing. Measure and record the voltage drop across the 1000 Ω resistor (measurement 2). Subtract the voltage recorded in meas­urement 1 from the voltage recorded in measurement 2. If the difference is greater than 0.15 volts, there is enough air flow through the duct smoke detector for proper operation. Once readings are complete, reinsert both filters and rein­stall cover. Reconnect power.
Figure 6. Procedure for verifying air flow:
[
6.1.5] Filter Replacement
The filters do not substantially affect smoke performance even when up to 90% of the filter is clogged. Quarterly visual inspection usually suffices to determine whether the filters should be replaced because only a high percentage of contamination affects performance. If further testing is required, compare differential pressure readings with and without the filters installed. If the difference exceeds 10% replace the filters. In no case should the pressure differen­tial fall below 0.0015 inches of water.
[6.2] Standby, Alarm and Sensitivity Tests
The cover must be removed to perform these tests. The use of a remote accessory for visible indication of power and alarm is recommended.
[6.2.1] Standby And Trouble
Standby—Look for the presence of the flashing green LED. The
LED should flash approximately every 10 seconds.
Trouble— If the detector LED does not flash, then the detector
lacks power (check wiring, panel, or power supply), the detector board is missing (replace), the cover has been missing or not secured properly for more than 7 minutes (secure cover properly), or the unit is defective (return for repair).
Test— The trouble condition can be caused intentionally to
verify correct operation of the system. Remove the
D200-24-00 5 I56-0056-07R
HIGH
LOW
DIFFERENTIAL
PRESSURE TRANSMITTER MODEL #607-01
TO SAMPLING TUBE
TO EXHAUST TUBE
15 TO 36VDC
SUPPLY
9 VOLT
BATTERY
9 VOLT
1000 OHM 5% 1 WATT RESISTOR
VOLT METER
FLUKE MODEL 87
OR EQUIVALENT
BATTERY
9 VOLT
BATTERY
15
19
14
3
20
1
3
2
Alarm Signal
Aux. Power +
Sup. N. O.
Sup. COM
Aux. Power –
NOTE: Wiring diagram shown is for DH100ACDCLWP 4-wire duct
smoke detector system equipped without a control panel.
Alarm (Red LED)
Power (Green LED)
Common
APA451DH100ACDCLWP
D200-24-00 6 I56-0056-07R
Do not loop wire under terminals when wiring detectors. Break wire runs to provide system supervision of connections.
CAUTION
Figure 8. Wiring diagram for DH100ACDCLWP to APA451:
H0178-00
Figure 7. System wiring diagram for 4-wire duct smoke detectors:
Figure 9. Wiring diagram for DH100ACDCLWP to RTS451KEY and interconnect feature:
Important Interconnect Notes
• When using the interconnect feature, all interconnected units must be powered with the same, independent supply.
• Polarity must be maintained throughout the interconnect wiring. Connect terminal 12 on unit 1 to terminal 12 on unit 2 and so on. Similarly, connect terminal 1 on unit 1 to ter­minal 1 on unit 2 and so on.
• Up to 10 units may be interconnected.
Figure 10. Multiple fan shutdown (interconnect):
15
19
14
3
20
2
11
2
6
1
Alarm Signal
Aux. Power +
Sup. N. O.
Sup. COM
Aux. Power —
Reset
Test
(Red LED) Alarm
(Green LED) Power
DH100ACDCLWP
RTS451/RTS451KEY
5
4
3
*
For RTS451KEY only without a control panel.
*
H0155-01
INP
R
E
W
O
P
, 24 VAC
24 VDC
50-60 H
C
120 VA 220/240 VAC
ECT P
N
N
O
C
PPRO
A
TO
H D
C
F EA
O
NTAC
O
. C
AUX
30 V
10A @
250 V
10A @
A M
100m
P @
1/4 H
@
1/8 HP
TEN
T IN
NO
C
E
NN
O
C
ELS.
AN
P
BLE
U
O
TR
@
2.0 A @
2.0 A
TS
U
50-60 H
W
O
IATE
PR
ETECT
T R R
C
D
C
A
UM
IM
IN 240 VAC 120 VAC
DED
TO
N
TIO
O
C 30 VD 125 VD
EP
CC
A
50-60 H
R
Z, O
Z.
SO
ER
TERM
.
R
O
ATING
TIVE
ESIS
5 VD
@
R
FO
NTR
O
C
T R
TAC
N
C resistive
resistive
C
T
Z,
E
C
R
U
ALS
IN
S
C
L
O
G
ATIN
A
9
24V
ALARM
FAN
R
FO
16 6 17
C.N
.C.
UX
A
M
ALAR
DBY. C
STAN
S IN
A
M
ALAR
VISO
PER
SU
10 A
XILIAR
AU
SHU
.
N.O
Y C
ILIAR
TAC
N
O
DICA
Y TR
R
120
VAC
Y C
O
TD
TACT
N
O
TS TRAN
BY TH
TED
BLE C
U
O
BC
220/240
AC
V
TAC
N
O
, ETC
N
W
18 8
7
.
.O
S SH
R D
SFE
AR
E
TAC
N
O
TS
.
.
.C
N
C.N
IN
N
W
O
G
RIN
U
S.
W
O
R
TS
TS
U
P
IN
ER
W
O
P
LE
B
ILA
VA
14 3
.
Y
B
D
N
A
S
T
M
D
A
R
N
A
L
IN
D
O
A
C
L
E
S
S
T
C
A
C
O
T
E
L
N
O
B
R
U
T
A
O
T
C
N
M
E
O
E
R
V
O
T
C
N
IL
D
E
H
W
N
E
P
O
S
T
C D A
M
T
A
P
N
E
H
W
R
O C
O
T
L
R
A
S
N
IG
S
T
B
O
P
P
T
R
C
E
T
E
T
E
R
U
T
A
F
E
R
E
IT
C
O
D
E
L
N
B
U
IS
C
O
R
O
R
W
E
N
. O
E
T
I
P
U
O
M
S
E
.
O
L
T
E
O
N
N
P
A
I
A
910AB
24V
XILIARY
AU
16 6
.
.C
LAR
A
TAN
S
ALA
SU
ALARM
FO
A
M
BY. CO
D
M
R
R
PE
C
AS IN
FAN
R
.N
UXILIAR
ISO
V
SH
17
.
.O
N
Y C
TAC
N
DICATED
Y TR
R
U
O
TS TR
O
14
O
C
L
S
T
C
A
C
O
T
E
L
N
O
B
R
U
T
A
O
T
C
N
M
E
O
E
R
V
O
T
C
N
IL
D
E
H
W
N
E
P
O
S
T
C
M
T
A
P
N
E
H
W
R
O
D
C
A
O
T
L
R
A
S
N
IG
S
T
C
120
VAC
220/240
AC
V
TS
TAC
N
CO
.
, ETC
N
W
O
TD
7188
C.
.
.O
N
W
O
H
ACTS S
NT
DU
NSFER
A
RO
E AR
TH
Y
B
TAC
N
O
UBLE C
3
M
D
A
R
N
A
L
IN
D
A
E
S
B
O
P
P
T
C
R
R
O
C
E
T
E
T
IM
E
R
S
U
E
T
A
F
E
R
E
O
T
O
N
IT
C
I
O
D
E
L
N
B
U
C
AP
TO
F EA
O
EC
SP
D
AD
FO
IN
R
FO
.
.C
N
EVIC
D
N
A
M
STALLATIO
IN
C
R
O
IN
N
G
IN
R
S.
W
TS
D
N
A
S
T
O
R
W
E
. O
T
U
O
E
N
P
A
TE
O
N
O
PR
STO
CU
R
FO
E
TH
.
Y
B
IS
N
E
P
.
L
PR
H
C
IFIC
N
ITIO
ATIO
RM
IR
W
ES, REFE
FACTU
U
NTA
O
:
TH
ES A
VID
M AND
ST "NO
O D
ATIO
AL PO
IN
E S
IZED
" C
P
E
G
C
O
R
TEC
N
O
R N IN
T M
UPER
"FO
AR
N
IA
N .
ER'S
A
TAC
TE
S FO W
F AU
R TO
AN
P
D
INA
M
TER
E
. SE
R
TO
R
PPLY
SU
ER
XILIARY
TIO
UC
TR
S
TU
FAC
U
RY R
O
VIS
O
" C
C
RM
TIO
A
PLIC
APPLICATIO
T IS USE
LS
N
E
R
ELAY N
TA
N
S
N
D
S
.
R
W
O
R
T FO
C
.
LY
N
S, O
N
E
C
UR
SO
R
E
W
O
T P
C
E
N
N
O
TS
U
P
IN
ER
W
O
P
BLE
ILA
VA
+
LAR
A
ITIATIO
IN LO
5
M
M
LAR
M
N
P
O
A IN
O
C
ITIATIO
TAC
N
N
TS
C
IN
EN
P
O
TAC
N
O
C
ALAR
IN
4
STAN
TS C
.
M
.
BY
D
SE
LO
N
W
O
TS SH
TAC
N
O
ALAR IN
O
C
ITIATIO
TAC
N
5
N
W
O
SH
TS
C
TA
N
O
C
PEN
N
TS
O
N
O
C
ALAR
IN
4
BY.
D
STAN
IN
E
S
LO
TS C
C
TA
.
M
U C
L LIS
O
E
IR
4-W
TED
EL
L PAN
O
TR
N
FIR D
H
100A
P
LW
C
D
C
TO
ETEC
ST D
1
12
FAN
CONTROL
6
16
SYSTEM
CONTROL
POWER OR
THERMOSTAT
A
B
DETECTOR 1
C
1
12
FAN
CONTROL
6
16
CONTROL
POWER OR
THERMOSTAT
IN
R
SYSTEM
TH
E LO
A
B
DETECTOR 2
P
O
LAS D
H
100A
P
LW
C
D
C
P
O
E LO
TH
IN
R
TO
ETEC
T D
EO
BY
IFIED
EC
SP
AN
EL M
N
PA
ER
R
TU
FAC
U
R
ESISTO
L R
C
OUT TO
10 DETECTORS
MAXIMUM
1
12
FAN
CONTROL
SYSTEM CONTROL POWER OR
THERMOSTAT
A
DETECTOR 10
6
16
B
C
detector board to cause a trouble condition locally
and at the system control panel. Cover Tamper — If the cover is removed or not properly secured for
a period longer than 7 minutes, a trouble signal is generated to indicate the cover is missing.
Figure 13. Testing detector alarm:
H0160-00
[6.2.2] Alarm Tests [6.2.2.1] M02-04-00 Magnet Test
1. Place the painted surface of the magnet onto the TEST
locator on the bottom of the housing (Figure 13).
2. The red alarm LED on the detector should latch on, as
should any accessories (i.e. RA400Z, RTS451). Verify system control panel alarm status and control panel exe­cution of all intended auxiliary functions (i.e. fan shut­down, damper control, etc.).
3. The detector must be reset by system control panel, front
cover reset button, or remote accessory.
[6.2.2.2] RTS451/RTS451KEY Remote Test Station
The RTS451/RTS451KEY Remote Test Station facilitates test of the alarm capability of the duct smoke detector as indi­cated in the RTS451/RTS451KEY manual. The DH100ACD­CLWP duct smoke detector can be reset by the RTS451/RTS451KEY. If a system control panel is used, the panel itself may also require testing. To install the RTS451/RTS451KEY, connect the device as shown in Figure 9; wire runs must be limited to 25 ohms or less per interconnecting wire.
Please note that the magnetic coil supplied with the RTS451 and RTS451KEY is not required when these acces-
ALARM SIGNAL (+)
AUX POWER (—)
15
20
(+)
(—)
DUCT DETECTOR DH100ACDCLWP
PA400 (OPTIONAL) AUDIBLE ALERT
ALARM SIGNAL (+)
AUX POWER (—)
15
20
(+)
(—)
DUCT DETECTOR DH100ACDCLWP
RA400Z (OPTIONAL) REMOTE (LED) ANNUNCIATOR
RED
ACCESSORY CURRENT LOADS AT 24 VDC DEVICE APA451 PA400 RA400Z RTS451/RTS451KEY SSK451
STANDBY
12.5mA Max. 0mA 0mA 12mA* 5mA Max.
ALARM 30mA Max. 15mA Max. 10mA Max.
7.5mA Max. 30mA Max.
*NOTE: When a unit is powered at the 120VAC or 220/240VAC input, any combination of accessories may be used such that the given accessory loads are:
60 mA or less in the standby state; 110 mA or less in the alarm state.
TROUBLE n/a n/a n/a n/a 9mA Max.
D200-24-00 7 I56-0056-07R
sories are used with the DH100ACDCLWP detectors. The functionality of the magnetic coil has been designed into the circuitry of the new Innovair™ duct smoke detectors.
[6.2.2.3] SSK451 Multi-Signaling Accessory
The System Sensor SSK451 Multi-Signaling accessory com­bines a sounder feature with a key activated test and reset function. Green, amber and red LEDs provide a visual indica­tion of power, trouble, and alarm respectively. An optional strobe (PS24LO) with a smoke lens can be added to conform to the codes of certain jurisdictions. To install the SSK451, connect the device as shown in figure 12.
[6.2.3] Sensitivity Tests [6.2.3.1] MOD400 or MOD400R Test
After verification of alarm capability, use the MOD400R test module with a voltmeter to check detector sensitivity as indicated in the test module’s manual. The housing cover must be removed to perform this test.
If test module readings indicate that the detector head is outside of the acceptable range that is printed on the label of the detector, the detector chamber requires cleaning per Section [7] of this manual.
[7] Detector Cleaning Procedures
Notify the proper authorities that the smoke detector sys­tem is undergoing maintenance, and that the system will temporarily be out of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms and possible dispatch of the fire department.
[7.1] Air Filters
1. Turn off power to the system.
2. Remove and inspect sampling tube filters.
3. If filters are heavily coated with dirt, replace them with new filters. If they are not heavily coated, use a vacuum cleaner or compressed air nozzle to remove dust, then reinstall the filters.
[7.2] Photo Detector Board
1. Remove the screen by gently grasping on each side and pulling straight off.
2. Lift the photo chamber in the same fashion. Vacuum the screen and cover. Use clean, compressed air to loosen
Figure 11. Wiring diagrams for optional accessories:
A78-2354-08
15 ALARM SIGNAL 3 14 2 RESET 11 TEST 20 AUX. POWER (-) 19 AUX. POWER (+)
SSK451
FIELD INSTALLED JUMPER FOR TEMPORAL PATTERN
SUPERVISORY CONTACT
NO
FIELD INSTALLED JUMPER
DH100ACDC
COMMON 3
TEMPORAL SELECT 2
ALARM SIGNAL 1
SUPERVISORY SIGNAL 4
RESET 7
TEST 8
POWER (-) 6
POWER (+) 5
Figure 12. Wiring diagram for
DH100ACDCLWP to SSK451
D200-24-00 8 I56-0056-07R
Three-Year Limited Warranty
System Sensor warrants its enclosed air duct smoke detector to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this air duct smoke detector. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the air duct smoke detector which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization num­ber, send defective units postage prepaid to: System Sensor, Returns Department,
RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or inci­dental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or conse­quential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
[9] Model DH100ACDCLWP Air Duct Smoke Detector Specifications
Operating temperature: +32° to +131°F 0° to +55°C Storage temperature: –22° to +158°F –30° to +70°C Environmental Rating: NEMA 4 Humidity: 10% to 93% R.H. noncondensing Air Velocity: 100 to 4000 ft./min. 0.5 to 20.3 m/sec. Dimensions: 14.38L x 5.5W x 2.75″ D 37cm L x 14cm W x 7cm D Weight: 3.75 pounds 1.7 kg
Electrical Specifications
Power supply voltage: 20-29 VDC 24 VAC 50-60-Hz 120 VAC 50-60 Hz 220/240 VAC 50-60 Hz Input capacitance: 270 µF max. 270 µF max. N/A N/A Reset voltage: 3.0 VDC min. 2.0 VAC min. 10 VAC min. 20 VAC min. Reset time (with RTS451): .03 to 0.3 sec. .03 to 0.3 sec. .03 to 0.3 sec. .03 to 0.3 sec. Reset time (by power down): 0.6 sec. max. 0.6 sec. max. 0.6 sec. max. 0.6 sec. max. Power up time: 34 sec. max. 34 sec. max. 34 sec. max. 34 sec. max. Alarm response time: 2 to 17 sec. 2 to 17 sec. 2 to 17 sec. 2 to 17 sec. Sensitivity Test: See detector label See detector label See detector label See detector label
and blow out any remaining debris. Replacement screens (S08-39-01) are available.
3. Vacuum photo chamber, then use clean compressed air to blow area clean.
4. Replace the chamber by pressing it onto the base. Press the screen into place. It should fit tightly on the chamber.
[8.0] Board Replacement [8.1] Detector Board Replacement (part no. A5069)
1. Remove the two detector board mounting screws.
2. Pull gently on the board to remove it.
3. To replace the board, align the board mounting fea-
tures, holes, and the interconnect terminals. Push the board into place.
4. Secure board with the two mounting screws.
[8.2] Power Board replacement (par t no. A5064)
1. Disconnect wiring from the terminal block.
2. Remove the two power board mounting screws.
3. Pull gently on the board to remove it.
4. To replace the board, align the board mounting fea­tures, holes, and the interconnect terminals. Push the board into place.
5. Secure board with the two mounting screws.
6. Re-connect wiring to terminal block.
Please refer to insert for the Limitations of Fire Alarm Systems
Power Supply Voltage 20 - 29 VDC 24 VAC 50 - 60 Hz 120 VAC 50 - 60 Hz 220/240 VAC 50 - 60 Hz
CURRENT REQUIREMENTS (USING NO ACCESSORIES)
Max. standby current 15 mA 35 mA RMS 25 mA RMS* 15 mA RMS* Max. alarm current
CONTACT RATINGS
Alarm initiation contacts (SPST) 2.0A @ 30 VDC (resistive)
Alarm auxiliary contacts (DPDT) 10A @ 30 VDC
Note: Alarm auxiliary contacts must switch 100 mA minimum at 5VDC. Alarm auxiliary contacts shall not be
connected to inititaing circuits of control panels. Use the alarm initiation contact for this purpose.
Trouble contacts (SPDT) 2.0A @ 30 VDC (resistive)
10A @ 250 VAC 1/4 HP @ 240 VAC 1/8 HP @ 120 VAC
2.0A @ 125 VAC (resistive)
70 mA
125 mA RMS 35 mA RMS* 25 mA RMS*
ACCESSORY CURRENT LOADS AT 24 VDC DEVICE APA451 PA400 RA400Z RTS451 RTS451KEY SSK451
* NOTE: When a unit is powered at the 120VAC or 220/240VAC input, any combination of accessories may be used such that the given accessory loads are: 60 mA or less in the standby state, 110 mA or less in the alarm state.
STANDBY
12.5mA Max. 0mA 0mA 0mA 12mA* 5mA Max.
TROUBLE n/a n/a n/a n/a n/a 9mA Max.
ALARM 30mA Max. 15mA Max. 10mA Max.
7.5mA Max.
7.5mA Max. 30mA Max.
Loading...