INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-1684-007R
DH100ACDCI Ionization
Air Duct Smoke Detector
Before Installing
Please thoroughly read the System Sensor Guide for Proper Use
of Smoke Detectors in Duct Applications (A05-1004), which
provides detailed information on detector spacing, placement,
zoning, wiring, and special applications. Copies of this manual
are available online at www.systemsensor.com or via System
Sensor’s toll free fax-back service, Documents on Demand at
800/736-7672. NFPA Standards 72 and 90A should also be refer
enced for detailed information.
NOTICE: This manual shall be left with the owner/user of
this equipment.
IMPORTANT: This detector must be tested and maintained regularly following NFPA 72 requirements. The detector should be
cleaned at least once a year.
Table of Contents Page
[1] General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
[2] Limitations of Duct Smoke Detectors
[3] Contents of the Duct Smoke Detector Kit
[4] Exploded View of Duct Smoke Detector Components
[5] Installation Sequence
[6] Duct Smoke Detector Maintenance and Test Procedures
[7] Detector Cleaning Procedures
[8] Board Replacement
[9] Specifications
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
[1] General Description
An HVAC system supplies conditioned air to virtually every area
of a building. Smoke introduced into this air duct system will be
distributed to the entire building. Smoke detectors designed for
use in air duct systems are used to sense the presence of smoke
in the duct.
Model DH100ACDCI Air Duct Smoke Detectors utilizes ioniza
tion technology for the detection of smoke. This smoke detection
method, when combined with an efficient housing design, sam
ples air passing through the duct and allows detection of a de
veloping hazardous condition. When sufficient smoke is sensed,
an alarm signal is initiated and appropriate action can be taken
to shut off fans, blowers, change over air handling systems, etc.
These actions can facilitate the management of toxic smoke and
fire gases throughout the areas served by the duct system.
The DH100ACDCI detector is designed to operate on 24 VDC/VAC,
120 VAC, or 240 VAC. Alarm and supervisory relay contacts are
available for control panel interface (alarm initiation), HVAC con
trol, and other auxiliary functions. Auxiliary relays are also pro
vided for fan shut down or signaling of up to 9 other detectors
in the loop for multiple fan shut down. These detectors are not
designed for 2-wire applications.
For testing, the alarm can be enabled by a magnet activated test
switch or by the optional remote test station. The duct smoke
detector latches into alarm state when an alarm occurs. A green
LED flashes to indicate power, a red LED signals local alarm
indication, and optional accessories offer a variety of annuncia
tion capabilities.
. . . . . . . . . . . . . . . . . 1
. . . . . . . . . . . . . . 1
. . . . . 2
. . . 4
. . . . . . . . . . . . . . . . . . . . . . 5
3825 Ohio Avenue, St. Charles, Illinois 60174
800/736-7672, FAX: 630-377-6495
www.systemsensor.com
The DH100ACDCI can be reset by a momentary power interruption, the reset button on the front cover, the control panel, or
remote reset accessory.
tamper feature that provides a trouble signal after 7 minutes if
the cover is removed or improperly installed. Proper installation
of the cover removes the trouble condition.
The DH100ACDCI incorporates a cover
[2] Limitations Of Duct Smoke Detectors
-
The National Fire Protection Association has established that
DUCT DETECTORS MUST NOT BE USED AS A SUBSTITUTE FOR
OPEN AREA DETECTOR PROTECTION as a means of providing
life safety. Nor are they a substitute for early warning in a build
ing’s regular fire detection system.
System Sensor supports this position and strongly recom
mends that the user read NFPA Standards 90A, 72, and 101. The
DH100ACDCI Air Duct Smoke Detectors are listed per UL 268A.
This device will not operate without electrical power. Fire situa
tions may cause an interruption of power. The system safeguards
should be discussed with your local fire protection specialist.
This device will not sense smoke unless the ventilation system is
operating and the cover is installed.
For this detector to function properly, it MUST be installed accord
ing to the instructions in this manual. Furthermore, the detector
MUST be protected from the elements and operated within ALL
electrical and environmental specifications listed in this manual.
Failure to comply with these requirements may prevent the detec
tor from activating when smoke is present in the air duct.
[3] Contents Of The Duct Smoke Detector Kit
1. Complete housing base and cover assembly
2. Two #10 x 1
-
3. Two sampling tube filters
4. One test magnet
-
5. Drilling template
-
6. Two foam gaskets
7. Four #6-self tapping mounting screws for the metal sampling
tube and optional exhaust tube extension
8. One sampling tube end cap
9. One plastic sampling tube
10. One #8 self-tapping screw for the plastic sampling tube
NOTE: For ducts over 11⁄2 feet, longer sampling tubes must be
ordered to complete the installation. They must be the correct
length for the width of the duct where they will be installed. See
Table 1 on page 3 to determine the sampling tube required for dif
ferent duct widths.
-
1
/4˝ sheet metal screws for mounting
-
-
-
-
-
-
D100-68-00 1 I56-1684-007R
SCREW HOLES FOR
ATTACHING HOUSING
TO DUCT WORK.
[4] Figure 1: Exploded View Of Duct Smoke Detector Components
FOAM
GASKETS
PLASTIC
SAMPLING TUBE
CONDUIT HOLES
DETECTOR
HOUSING
TERMINAL STRIP
DETECTOR
COVER
SAMPLING TUBE
FILTERS
PLASTIC SAMPLING TUBE
SELF-TAPPING SCREW
POWER BOARD
DETECTOR BOARD
COVER MOUNTING
SCREWS
[5] Installation Sequence
[5.1] Verify Duct Air Flow Direction And Velocity
Model DH100ACDCI detectors are designed to be used in air handling systems having air velocities of 500 to 4000 feet per minute.
Be sure to check engineering specifications to ensure that the air
velocity in the duct falls within these parameters. If necessary, use
a velocity meter to check the air velocity in the duct.
[5.2] Drill The Mounting Holes
Remove the paper backing from the mounting template supplied.
Affix the template to the duct at the desired mounting location.
Make sure the template lies flat and smooth on the duct. Center
punch holes A and B. Drill the holes as indicated on the template.
[5.3] Secure The Detector Housing To The Duct
Slide the foam gaskets over the tube bushings as shown in Figure 3.
Use the two 1
ing to the duct.
CAUTION: Do not overtighten the screws.
1
/4˝ long sheet metal screws to screw the detector hous-
Figure 3. Installation of foam gaskets over sampling
tube bushings:
H0401-00
[5.2.1] Sampling Tube Installation for Ducts Less
Than 11⁄2 Feet Wide (see Figure 2)
1. Remove the front cover.
2. Slide the plastic sampling tube into the housing bushing.
3. Align the holes in the bushing with the holes in the sampling
tube. Make sure there are 6 exposed holes on the plastic sam
pling tube. Secure with the #8 self-tapping screw into the bot
tom of the permanent tube (shown in
Figure 1).
NOTE: The sampling tube end cap is critical to the proper opera-
tion of the duct smoke detector. The end cap is needed to create
the proper air flow to the sensor of the duct smoke detector.
NOTE: For ducts greater than 11⁄2 feet in width, refer to sections
[5.4.1] and [5.4.2].
Figure 2. Plastic sampling tube
connected to duct smoke detector:
D100-68-00 2 I56-1684-007R
H0110-00
-
-
[5.4] Sampling Tube Installation for Ducts Greater
Than 11⁄2 Feet Wide
The sampling tube is identified by a series of air inlet holes on
the tube. A plastic tube is included for ducts up to 18 in width.
All other lengths must be purchased separately. Order the cor
rect length, as specified in Table 1, for width of the duct where it
will be installed. It is recommended that the sampling tube length
extend at least two-thirds across the duct width for optimal per
formance. The exhaust tube is molded onto the base of the duct
housing, and the A2440-00 Exhaust Tube Extension is available as
an accessory in those cases where the molded exhaust port does
not extend at least 2 inches into the duct.
The sampling tube is always installed with the air inlet holes
facing into the air flow. To assist proper installation, the tube’s
mounting flange is marked with an arrow. Make sure the sam
pling tube is mounted so that the arrow points into the air flow
(see
Figure 4). Figure 5 shows the various combinations of tube
mounting configurations with respect to air flow. Mounting the
detector housing in a vertical orientation is acceptable, provided
that the air flows directly into the sampling tube holes as indi
cated in
Figure 4.
H0107-00
-
-
-
-
SAMPLING
TUBE
END CAP
AIR HOLES
ARROW
MUST FACE
INTO AIR FLOW
AIR FLOW DIRECTION
FLANGE
AIR FLOW
DIRECTION
DETECTOR
HOUSING
DOTS INDICATE POSITION OF
SAMPLING TUBE HOLES
AIR FLOW
DIRECTION
DETECTOR
HOUSING
SAMPLING
TUBE
EXHAUST
TUBE
AIR FLOW
DIRECTION
EXHAUST
TUBE
SAMPLING
TUBE
SAMPLING
TUBE
EXHAUST
TUBE
DETECTOR
HOUSING
AIR FLOW
DIRECTION
DETECTOR
HOUSING
A.
B.
C.
D.
HORIZONTAL MOUNTING OF HOUSING
VERTICAL MOUNTING OF HOUSING
Table 1. Sampling tubes recommended for different
duct widths:
Figure 5. Tube mounting configurations with varying
air flow direction:
Outside Duct Width Sampling Tube Recommended*
1 to 2 ft. ST-1.5
2 to 4 ft. ST-3
4 to 8 ft. ST-5
8 to 12 ft. ST-10
*Must extend a minimum of two-thirds the duct width.
[5.4.1] Installation For Ducts Greater Than 11⁄2 Feet
But Less Than 8 Feet Wide
1. If the tube is longer than the width of the air duct, drill a 3⁄4”
hole in the duct opposite the hole already cut for the sam
pling tube. Make sure the hole is 1” to 2” below the inlet hole
on the opposite side of the duct to allow moisture drainage
away from the detector.
If the tube is shorter than the width
of the air duct, install the end cap into the sampling tube as
shown in
Figure 4. Sampling tubes over 3 ft. long must be
supported at the end opposite the duct smoke detector.
2. Slide the tube into the housing bushing that meets the air flow
first. Position the tube so that the arrows point into the air flow.
3. Secure the tube flange to the housing bushing with two #6
self-tapping screws.
4. For tubes longer than the width of the air duct, the tube
should extend out of the opposite side of the duct. If there
are more than 2 holes in the section of the tube extending
out of the duct, select a different length using Table 1. Oth
erwise, trim the end of the tube protruding through the duct
so that 1” to 2” of the tube extend outside the duct. Plug
this end with the end cap and tape closed any holes in the
protruding section of the tube. Be sure to seal the duct where
the tube protrudes.
NOTE: The sampling tube end cap is critical to the proper operation of the duct smoke detector. The end cap is needed to create
the proper air flow to the sensor of the duct smoke detector.
Figure 4. Air duct detector sampling tube:
[5.4.2] Installation For Ducts More Than 8 Feet Wide
NOTE: To install sampling tubes in ducts more than 8 feet wide,
work must be performed inside the air duct. Sampling of air in
ducts wider than 8 feet is accomplished by using the ST-10 inlet
sampling tube. If the tube is shorter than the width of the air duct,
install the end cap into the sampling tube as shown in
and support the end opposite the duct smoke detector.
D100-68-00 3 I56-1684-007R
Figure 4
H0108-02
-
NOTE: Only metal sampling tubes may be used on orientations
C and D.
In no case should more than 2 air inlet holes be cut off the tube.
There must be a minimum of 10 holes in the tube exposed to the
air stream.
Install the inlet tube as follows:
1. Drill a
2. Slide the sampling tube with the flange into the housing bush
3. From inside the duct, couple the other sections of the sam
4. Trim the end of the tube protruding through the duct so that
NOTE: An alternate method to using the ST-10 is to use two ST-5
sampling tubes. Remove the flange from one of the tubes and in
stall as described above. After the installation, use electrical tape
to close off some of the sampling holes so that there are a total
of 10 to 12 holes spaced as evenly as possible across the width of
the duct.
NOTE: Air currents inside the duct may cause excessive vibration, especially when the longer sampling tubes are used. In these
cases a 3” floor flange (available at most plumbing supply stores)
may be used to fasten the sampling tube to the other side of the
duct. When using the flange/connector mounting technique, drill
a 1 inch to 1
3
⁄4˝ hole in the duct directly opposite the hole already
drilled for the sampling tube. Make sure the hole is 1 to 2”
below the inlet hole on the opposite side of the duct to allow
for moisture drainage.
ing that meets the air flow first. Position the tube so that the
arrow points into the air flow. Secure the tube flange to the
housing bushing with two #6 self-tapping screws.
pling tube to the section already installed using the 1⁄2 inch
conduit fittings supplied. Make sure that the holes on both of
the air inlet tubes are lined up and facing into the air flow.
1 to 2 inches of the tube extend outside the duct. Plug this
end with the end cap and tape closed any holes in the pro
truding section of the tube. Be sure to seal the duct when the
tube protrudes.
1
⁄4 inch hole where the flange will be used.
H0109-01
-
-
-
-