Please thoroughly read the System Sensor Guide for Proper
Use of Smoke Detectors in Duct Applications (I56-473),
which provides detailed information on detector spacing,
placement, zoning, wiring, and special applications. Copies of this manual are available from System Sensor. NFPA
Standards 72 and 90A should also be referenced for detailed information.
NOTICE: This manual should be left with the owner/user
of this equipment.
IMPORTANT: This detector must be tested and maintained
regularly following NFPA 72 requirements. The detector
should be cleaned at least once a year.
Table of ContentsPage
[1] General Description 1
[2] Limitations of Duct Smoke Detectors1
[3] Exploded View of Duct Smoke Detector Components 2
[4] Contents of the Duct Smoke Detector Kit2
[5] Installation Sequence2
[6] Duct Smoke Detector Maintenance and Test Procedures 5
[7] Detector Cleaning Procedures7
[8] Board Replacement7
[9] Specifications8
Warranty8
[1] General Description
An HVAC system supplies conditioned air to virtually every
area of a building. Smoke introduced into this air duct system will be distributed to the entire building. Smoke detectors designed for use in air duct systems are used to sense
the presence of smoke in the duct.
Model DH100 Air Duct Smoke Detectors are supplied as a
photoelectronic model. This smoke detection method is
combined with an efficient housing design that samples air
passing through a duct and allows detection of a developing hazardous condition. When sufficient smoke is sensed,
an alarm signal is initiated at the fire control panel monitoring the detector, and appropriate action can be taken to
shut off fans, blowers, change over air handling systems,
etc. These actions can facilitate the management of toxic
smoke and fire gases throughout the areas served by the
duct system.
DH100 detectors are designed to operate with 12 or 24
VDC UL listed compatible 2-wire control panels. Alarm
current must be limited to 100mA or less by the control
panel. Auxiliary relay contacts for control purposes are
not available for use with the DH100. Control must initiate from the control panel.
For testing, the alarm can be enabled by a magnet activated test switch or by the optional remote test station.
The duct smoke detector latches into alarm state when
an alarm occurs. A green LED flashes to indicate power,
a red LED signals local alarm indication, and optional
accessories offer a variety of annunciation capabilities.
The DH100 can be reset by a momentary power interruption, the reset button on the front cover, the control panel,
or remote reset accessory.
[2] Limitations Of Duct Smoke Detectors
WARNING
The National Fire Protection Association has established
that DUCT DETECTORS MUST NOT BE USED AS A SUBSTITUTE FOR OPEN AREA DETECTOR PROTECTION as a
means of providing life safety. Nor are they a substitute for
early warning in a building’s regular fire detection system.
System Sensor supports this position and strongly recommends that the user read NFPA Standards 90A, 72, and 101.
The DH100 Air Duct Smoke Detectors are listed per UL 268A.
WARNING
This device will not operate without electrical power.
Fire situations may cause an interruption of power. The
system safeguards should be discussed with your local fire
protection specialist.
WARNING
This device will not sense smoke unless the ventilation system is operating and the cover is installed.
WARNING
For this detector to function properly, it MUST be installed
according to the instructions in this manual. Furthermore,
the detector MUST be protected from the elements and operated within ALL electrical and environmental specifications listed in this manual. Failure to comply with these
requirements may prevent the detector from activating
when smoke is present in the air duct.
D100-67-001I56-1148-04
[3] Figure 1: Exploded View Of Duct Detector Components
FOAM
GASKETS
TELESCOPING TUBE
TELESCOPING TUBE
#8 SELF-TAPPING SCREW
DETECTOR BOARD
SAMPLING TUBE
FILTERS
DETECTOR
COVER
CONDUIT HOLES
COVER MOUNTING
DETECTOR
SCREWS
[4] Contents Of The Duct Smoke Detector Kit
1. Complete housing base and cover assembly
2. Two #10 machine screws for mounting
3. Two sampling tube filters
4. One test magnet
5. Drilling template
6. Two foam gaskets
7. Four #6-self tapping mounting screws for the metal
sampling tube and optional exhaust tube extension
8. Two jack nuts
9. One inlet tube end plug
10. Metal sampling tube end plug
11. One telescoping sampling tube
12. One #8 self-tapping screw for the telescoping sampling tube
NOTE: For ducts over 11/2 feet, longer inlet sampling tubes
must be ordered to complete the installation. They
must be the correct length for the width of the duct
where they will be installed. See Table 1 on page 3
to determine the inlet tube required for different
duct widths.
[5] Installation Sequence
[5.1] Verify Duct Air Flow Direction And Velocity
Model DH100 detectors are designed to be used in air handling systems having air velocities of 500 to 4000 feet per
minute. Be sure to check engineering specifications to ensure that the air velocity in the duct falls within these parameters. If necessary, use a velocity meter to check the air
velocity in the duct.
HOUSING
TERMINAL STRIP
POWER BOARD
Tube Installation Chart:
SupplementalDuct
Tube HolesWidth
512″-14″
614″-16″
716″-18″
holes as indicated on the template. Insert the two jack nut
receptacles. Drive a #10 machine screw into the jacknut to
flare the retainer and then back the screw out to use for detector mounting.
[5.2.1] Sampling Tube Installation for Ducts Less
Than 11/2 Feet Wide (see Figure 2)
1. Remove the front cover.
2. Use the tube installation chart above to determine the
set screw setting.
3. Slide the sampling tube into the housing bushing.
4. Align the holes in the bushing with the holes in the sampling tube. Make sure the number of holes exposed on
the supplemental tube matches the number as determined in step 2. Secure with the #8 self-tapping screw
into the bottom hole of the permanent tube.
NOTE: For ducts greater than 11/2 feet in width, refer to
sections [5.4.1] and [5.4.2].
Figure 2. Sampling tubes connected to duct smoke
detector:
[5.2] Drill The Mounting Holes
Remove the paper backing from the mounting template
supplied. Affix the template to the duct at the desired
mounting location. Make sure the template lies flat and
smooth on the duct. Center punch holes A and B. Drill the
D100-67-002I56-1148-04
[5.3] Secure The Detector Housing To The Duct
Slide the foam gaskets over the tube bushings as shown in
Figure 3. Use the two machine screws to screw the detector
housing to the duct.
CAUTION: Do not overtighten the screws.
Figure 3. Installation of foam gaskets over sampling
tube bushings:
A78-2045-00
[5.4] Sampling Tube Installation of Ducts Greater
Than 11/2 Feet Wide
The sampling tube is identified by a series of air inlet holes
on the tube. One telescoping tube is included for ducts up
to 18″ in width. All other lengths must be purchased separately. Order the correct length, as specified in Table 1, for
width of the duct where it will be installed. The exhaust
tube is molded onto the base of the duct housing, and the
A2440-00 Exhaust Tube Extension is available as an accessory in those cases where the molded exhaust port does not
extend at least 2 inches into the duct.
the inlet tube. Make sure the hole is 1″ to 2″ below the inlet hole on the opposite side of the duct to allow for moisture drainage. If the tube is shorter than the width of the airduct, install the end plug into the inlet tube as shown in
Figure 4. Sampling tubes over 3 ft. long must be supported
at the end opposite the duct detector.
2. Slide the tube into the housing bushing that meets the
air flow first. Position the tube so that the arrows point
into the air flow.
3. Secure the tube flange to the housing bushing with two
#6 self-tapping screws.
4. For tubes longer than the width of the air duct, the tube
should extend out of the opposite side of the duct. If
there are more than 2 holes in the section of the tube extending out of the duct, select a different length using
Table 1. Otherwise, trim the end of the tube protruding
through the duct so that 1″ to 2″ of the tube extend outside the duct. Plug this end with the end plug and tape
closed any holes in the protruding section of the tube. Be
sure to seal the duct when the tube protrudes.
Figure 4. Air duct detector inlet sampling tube:
FLANGE
AIR HOLES
ARROWS
MUST FACE
INTO AIR FLOW
AIR FLOW DIRECTION
INLET
TUBE
END
PLUG
The inlet tube is always installed with the air inlet holes
facing into the air flow. To assist proper installation, the
tube’s mounting flange is marked with arrows. Make sure
the inlet tube is mounted so that the arrows point into the
air flow (see Figure 4). Figure 5 shows the various combinations of tube mounting configurations with respect to air
flow. Mounting the detector housing in a vertical orientation is acceptable, provided that the air flows directly into
the sampling tube holes as indicated in Figure 4.
Table 1. Inlet tubes required for different duct
widths:
Outside Duct WidthInlet Tube Required
1 to 2 ft.ST-1.5
2 to 4 ft.ST-3
4 to 8 ft.ST-5
8 to 12 ft.ST-10
[5.4.1] Installation For Ducts Greater Than 1 1/2 Feet
But Less Than 8 Feet Wide
1. If the tube is longer than the width of the air duct, drill a
3
/4-inch hole in the duct opposite the hole already cut for
A78-2047-00
Figure 5. Tube mounting configurations with varying
air flow direction:
DOTS INDICATE POSITION OF
SAMPLING TUBE HOLES
INLET
TUBE
INLET
TUBE
AIR FLOW
DIRECTION
DUCT
DETECTOR
HOUSING
B.
DUCT
DETECTOR
HOUSING
D.
A78-1812-08
AIR FLOW
DIRECTION
DUCT
DETECTOR
HOUSING
DUCT
DETECTOR
HOUSING
TUBE
INLET
TUBE
A.
C.
INLET
TUBE
EXHAUST
TUBE
EXHAUST
AIR FLOW
DIRECTION
NOTE: Orientations C and D apply only to metal sampling tubes.
EXHAUST
TUBE
EXHAUST
TUBE
AIR FLOW
DIRECTION
D100-67-003I56-1148-04
Loading...
+ 5 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.