System Sensor I56-1148-04, D100-67-00 User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
DH100 Air Duct Smoke Detector
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Before Installing
Please thoroughly read the System Sensor Guide for Proper Use of Smoke Detectors in Duct Applications (I56-473),
which provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Cop­ies of this manual are available from System Sensor. NFPA Standards 72 and 90A should also be referenced for de­tailed information.
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: This detector must be tested and maintained regularly following NFPA 72 requirements. The detector should be cleaned at least once a year.
Table of Contents Page
[1] General Description 1 [2] Limitations of Duct Smoke Detectors 1 [3] Exploded View of Duct Smoke Detector Components 2 [4] Contents of the Duct Smoke Detector Kit 2 [5] Installation Sequence 2 [6] Duct Smoke Detector Maintenance and Test Procedures 5 [7] Detector Cleaning Procedures 7 [8] Board Replacement 7 [9] Specifications 8 Warranty 8
[1] General Description
An HVAC system supplies conditioned air to virtually every area of a building. Smoke introduced into this air duct sys­tem will be distributed to the entire building. Smoke detec­tors designed for use in air duct systems are used to sense the presence of smoke in the duct.
Model DH100 Air Duct Smoke Detectors are supplied as a photoelectronic model. This smoke detection method is combined with an efficient housing design that samples air passing through a duct and allows detection of a develop­ing hazardous condition. When sufficient smoke is sensed, an alarm signal is initiated at the fire control panel monitor­ing the detector, and appropriate action can be taken to shut off fans, blowers, change over air handling systems, etc. These actions can facilitate the management of toxic smoke and fire gases throughout the areas served by the duct system.
DH100 detectors are designed to operate with 12 or 24 VDC UL listed compatible 2-wire control panels. Alarm current must be limited to 100mA or less by the control panel. Auxiliary relay contacts for control purposes are not available for use with the DH100. Control must ini­tiate from the control panel.
For testing, the alarm can be enabled by a magnet acti­vated test switch or by the optional remote test station. The duct smoke detector latches into alarm state when an alarm occurs. A green LED flashes to indicate power, a red LED signals local alarm indication, and optional accessories offer a variety of annunciation capabilities.
The DH100 can be reset by a momentary power interrup­tion, the reset button on the front cover, the control panel, or remote reset accessory.
[2] Limitations Of Duct Smoke Detectors
WARNING
The National Fire Protection Association has established that DUCT DETECTORS MUST NOT BE USED AS A SUB­STITUTE FOR OPEN AREA DETECTOR PROTECTION as a means of providing life safety. Nor are they a substitute for early warning in a building’s regular fire detection system.
System Sensor supports this position and strongly recom­mends that the user read NFPA Standards 90A, 72, and 101. The DH100 Air Duct Smoke Detectors are listed per UL 268A.
WARNING
This device will not operate without electrical power.
WARNING
This device will not sense smoke unless the ventilation sys­tem is operating and the cover is installed.
WARNING
For this detector to function properly, it MUST be installed according to the instructions in this manual. Furthermore, the detector MUST be protected from the elements and op­erated within ALL electrical and environmental specifica­tions listed in this manual. Failure to comply with these requirements may prevent the detector from activating when smoke is present in the air duct.
D100-67-00 1 I56-1148-04
[3] Figure 1: Exploded View Of Duct Detector Components
FOAM
GASKETS
TELESCOPING TUBE
TELESCOPING TUBE
#8 SELF-TAPPING SCREW
DETECTOR BOARD
SAMPLING TUBE
FILTERS
DETECTOR
COVER
CONDUIT HOLES
COVER MOUNTING
DETECTOR
SCREWS
[4] Contents Of The Duct Smoke Detector Kit
1. Complete housing base and cover assembly
2. Two #10 machine screws for mounting
3. Two sampling tube filters
4. One test magnet
5. Drilling template
6. Two foam gaskets
7. Four #6-self tapping mounting screws for the metal sampling tube and optional exhaust tube extension
8. Two jack nuts
9. One inlet tube end plug
10. Metal sampling tube end plug
11. One telescoping sampling tube
12. One #8 self-tapping screw for the telescoping sampling tube
NOTE: For ducts over 11/2 feet, longer inlet sampling tubes
must be ordered to complete the installation. They must be the correct length for the width of the duct where they will be installed. See Table 1 on page 3 to determine the inlet tube required for different duct widths.
[5] Installation Sequence [5.1] Verify Duct Air Flow Direction And Velocity
Model DH100 detectors are designed to be used in air han­dling systems having air velocities of 500 to 4000 feet per minute. Be sure to check engineering specifications to en­sure that the air velocity in the duct falls within these pa­rameters. If necessary, use a velocity meter to check the air velocity in the duct.
HOUSING
TERMINAL STRIP
POWER BOARD
Tube Installation Chart:
Supplemental Duct Tube Holes Width
512-14 614-16 716-18
holes as indicated on the template. Insert the two jack nut receptacles. Drive a #10 machine screw into the jacknut to flare the retainer and then back the screw out to use for de­tector mounting.
[5.2.1] Sampling Tube Installation for Ducts Less Than 11/2 Feet Wide (see Figure 2)
1. Remove the front cover.
2. Use the tube installation chart above to determine the set screw setting.
3. Slide the sampling tube into the housing bushing.
4. Align the holes in the bushing with the holes in the sam­pling tube. Make sure the number of holes exposed on the supplemental tube matches the number as deter­mined in step 2. Secure with the #8 self-tapping screw into the bottom hole of the permanent tube.
NOTE: For ducts greater than 11/2 feet in width, refer to
sections [5.4.1] and [5.4.2].
Figure 2. Sampling tubes connected to duct smoke detector:
[5.2] Drill The Mounting Holes
Remove the paper backing from the mounting template supplied. Affix the template to the duct at the desired mounting location. Make sure the template lies flat and smooth on the duct. Center punch holes A and B. Drill the
D100-67-00 2 I56-1148-04
[5.3] Secure The Detector Housing To The Duct
Slide the foam gaskets over the tube bushings as shown in Figure 3. Use the two machine screws to screw the detector housing to the duct. CAUTION: Do not overtighten the screws.
Figure 3. Installation of foam gaskets over sampling tube bushings:
A78-2045-00
[5.4] Sampling Tube Installation of Ducts Greater Than 11/2 Feet Wide
The sampling tube is identified by a series of air inlet holes on the tube. One telescoping tube is included for ducts up to 18 in width. All other lengths must be purchased sepa­rately. Order the correct length, as specified in Table 1, for width of the duct where it will be installed. The exhaust tube is molded onto the base of the duct housing, and the A2440-00 Exhaust Tube Extension is available as an acces­sory in those cases where the molded exhaust port does not extend at least 2 inches into the duct.
the inlet tube. Make sure the hole is 1 to 2 below the in­let hole on the opposite side of the duct to allow for mois­ture drainage. If the tube is shorter than the width of the air duct, install the end plug into the inlet tube as shown in Figure 4. Sampling tubes over 3 ft. long must be supported at the end opposite the duct detector.
2. Slide the tube into the housing bushing that meets the
air flow first. Position the tube so that the arrows point into the air flow.
#6 self-tapping screws.
4. For tubes longer than the width of the air duct, the tube
should extend out of the opposite side of the duct. If there are more than 2 holes in the section of the tube ex­tending out of the duct, select a different length using Table 1. Otherwise, trim the end of the tube protruding through the duct so that 1 to 2 of the tube extend out­side the duct. Plug this end with the end plug and tape closed any holes in the protruding section of the tube. Be sure to seal the duct when the tube protrudes.
Figure 4. Air duct detector inlet sampling tube:
FLANGE
AIR HOLES
ARROWS
MUST FACE
INTO AIR FLOW
AIR FLOW DIRECTION
INLET TUBE END PLUG
Table 1. Inlet tubes required for different duct widths:
Outside Duct Width Inlet Tube Required
1 to 2 ft. ST-1.5 2 to 4 ft. ST-3 4 to 8 ft. ST-5
8 to 12 ft. ST-10
[5.4.1] Installation For Ducts Greater Than 1 1/2 Feet But Less Than 8 Feet Wide
1. If the tube is longer than the width of the air duct, drill a
3
/4-inch hole in the duct opposite the hole already cut for
A78-2047-00
Figure 5. Tube mounting configurations with varying air flow direction:
DOTS INDICATE POSITION OF
SAMPLING TUBE HOLES
INLET TUBE
INLET TUBE
AIR FLOW
DIRECTION
DUCT DETECTOR HOUSING
B.
DUCT DETECTOR HOUSING
D.
A78-1812-08
AIR FLOW
DIRECTION
DUCT DETECTOR HOUSING
DUCT DETECTOR HOUSING
TUBE
INLET TUBE
A.
C.
INLET TUBE
EXHAUST
TUBE
EXHAUST
AIR FLOW
DIRECTION
NOTE: Orientations C and D apply only to metal sampling tubes.
EXHAUST
TUBE
EXHAUST
TUBE
AIR FLOW
DIRECTION
D100-67-00 3 I56-1148-04
Loading...
+ 5 hidden pages