System Sensor CZ-6 User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
CZ-6 Six Zone Interface Module
SPECIFICATIONS
Normal Operating Voltage: 15-32 VDC Stand-By Current: 2 mA Alarm Current: 40 mA (assumes all six LEDs solid on) Temperature Range: 32°F to 120°F (0°C to 49°C) Humidity: 10 to 93% Non-condensing Dimensions: 6.8˝H x 5.8 Accessories: CH-6 Chassis; BB-2 Cabinet; BB-6 Cabinet Wire Gauge: 12-18 AWG Maximum IDC Wiring Resistance: 25 Ohms External Power Supply Voltage: Regulated 24VDC Ripple Voltage: 0.1 volts RMS maximum IDC (supervised and power limited) DC Voltage: 18-28 volts power limited Frequency: DC Current: 90mA per circuit
˝W x 1.25˝D
I56-1799-005
3825 Ohio Avenue, St. Charles, Illinois 60174
800/736-7672, FAX: 630/377-6495
www.systemsensor.com
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to the appropriate control panel installation manual for detailed system information. If the modules will be installed in an existing operational system, inform the operator and local au­thority that the system will be temporarily out of service. Discon­nect the power to the control panel before installing the modules. This system contains static sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. The module hous­ing should also be grounded.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The CZ-6 Six Zone Interface Module is intended for use in an intelligent alarm system. Each module provides an interface be­tween the intelligent alarm system and a conventional alarm sys­tem loop. A common SLC input is used for all modules, and the initiating device loops share a common supervisory supply and ground. Otherwise, each monitor operates independently from the others. Each module has its own unique address.
A pair of rotary code switches is used to set the address of the first module from 01 to 94. The remaining modules are automatically assigned to the next five higher addresses. Provisions are included for disabling a maximum of two unused modules to release the addresses to be used elsewhere. Each module also has panel con­trolled bicolor LED indicators. The panel can cause the LEDs to blink, latch on, or latch off.
Compatible Two-wire System Sensor Smoke Detectors for use with CZ-6 with Zone Identifier A
DET. DETECTOR MODEL COMP. ID MANUFACTURER BASE MODEL MAX DET.
1151 A SYSTEM SENSOR B110LP, B401 20 1451 A SYSTEM SENSOR B401, B401B 20 1451DH A SYSTEM SENSOR DH400 20 2151 A SYSTEM SENSOR B110LP, B401 20 2451 A SYSTEM SENSOR DH400, B401B, B401 20 2451TH A SYSTEM SENSOR B401, B401B 20 5451 A SYSTEM SENSOR B401 20 1100 A SYSTEM SENSOR N/A 20 1400 A SYSTEM SENSOR N/A 20 ** 2100AT A SYSTEM SENSOR N/A 20 2100B A SYSTEM SENSOR N/A 20 2100D A SYSTEM SENSOR N/A 20 2100S A SYSTEM SENSOR N/A 20 2100TB A SYSTEM SENSOR N/A 20 2100TD A SYSTEM SENSOR N/A 20 2100TS A SYSTEM SENSOR N/A 20 2300B A SYSTEM SENSOR N/A 20 2300TB A SYSTEM SENSOR N/A 20 2400 A SYSTEM SENSOR N/A 20 2400TH A SYSTEM SENSOR N/A 20 * 2W-B A SYSTEM SENSOR N/A 20 * 2W-TB A SYSTEM SENSOR N/A 20 DH100LP A SYSTEM SENSOR N/A 20 * Class B, Style B only ** No Accessory will be supported by 2100AT
D500-49-00 1 I56-1799-005
Backbox Mounting Holes
Mount with self-threading screws
to back of cabinet
2
3
1
Included:
0
1
2
3
4
5
6 7 8
9
0
7 8
6
5
4
3
2
1
9 1 0
11
1 2
1 3
1 4
15
BASE
ADDRESS
ADDRESS
DISABLE
N O N E
O N E
T W O
T H R E E
0
1
2
3
4
5
6 7 8
9
0
7 8
6
5
4
3
2
1
9 1 0
1 1
1 2
1 3
1 4
1 5
BASE
ADDRESS
ADDRESS
DISABLE
NONE
ONE
TW O
THREE
(5) 1 x 4 Terminal Blocks (2) 1
1
/4” Stand offs (3) Shunts
(4) Machine Screws (2) Nuts (1) Long Power Supply Jumper
(6) 3.9k Ohm End of Line Resistors
Shipped on Board:
C0202-00
(2) Shunts in Class A/B position (Shipped in Class B position, remove shunts for Class A)
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible system control panel. Contact System Sensor for a list of compatible detectors.
COMPONENTS
Following are descriptions of the CZ-6 mounting frameworks. There are two mounting options for CZ-6 modules:
• Up to six CZ-6 modules can be installed on a CH-6 in a BB-6 cabinet
• One or two CZ-6 modules can be installed in a BB-2 cabinet
Chassis
The CH-6 chassis is used to mount CZ-6 modules in a BB-6, cabi­net. It accommodates up to six CZ-6 modules in a single cabinet row three modules wide and two modules deep.
Figure 1. CH-6 Chassis:
Cabinets
A BB-6 cabinet will house the CH-6 chassis with up to six CZ-6 modules installed on it. Refer to cabinet installation documents for dimensions.
The BB-2 cabinet houses one or two CZ-6 modules on the internal chassis that is part of the cabinet. Refer to cabinet installation documents for dimensions.
INSTALLATION STEPS
1. Cabinet Mounting
In a clean, dry area, mount the backbox using the four holes
provided in the back surface of the cabinet (Figure 3).
2. Chassis Installation
The CH-6 chassis is mounted in the BB-6 cabinet. It is shipped
with two self-threading screws, which are used to fasten the chassis to the back wall of the cabinet. (Figure 4).
Figure 3. Typical mounting hole locations:
C0235-00
Figure 4. Mounting the CH-6 chassis:
The BB-2 cabinet comes with the chassis already installed, so no mounting is necessary.
C0206-00
The BB-2 cabinet has a built-in chassis that will accommodate one or two CZ-6 modules.
Figure 2: BB-2 Cabinet
3. Module Installation
There are two methods for installing a module in the rear posi
tion of a chassis. Method one is for installation of a rear mod­ule only, when no module will be installed in front of it. Refer to Figure 5 for instructions. Method two is for installation of a rear module when another module will be installed in the chassis position in front of it. Refer to Figures 6a and 6b for method two. All necessary screws and standoffs are supplied with the modules.
Figure 5. Installation of rear module only, method one:
The front CZ-6 module positions of each chassis are offset below the rear CZ-6 module positions so that all of the status indicators are visible.
D500-49-00 2 I56-1799-005
C0234-00
C0236-00
-
C0237-00
Loading...