System Sensor CO1224T, CO1224TR User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-3111-006
CO1224T/CO1224TR Carbon Monoxide Detector
SPECIFICATIONS
Electrical Specifications
System Voltage Nominal: 12/24 VDC Min: 10 VDC Max: 33 VDC Avg. Standby Current: 20 mA Max Alarm Current: 40 mA (75 mA test) Alarm Contact Ratings: 30 VDC @ 0.5 A Trouble Contact Ratings: 30 VDC @ 0.5 A Audible Signal (temp 4 tone): 85 dBA min. in alarm (at 10ft) Max. Start-up Capacitance: 20 uF
NOTICE: This manual shall be left with the owner/user of this equipment.
GENERAL DESCRIPTION
• Listed to standard 2075
• Round shape allows for mounting in aesthetically demanding areas
• 4 wire, system monitored
• Optional CO detector replacement plate for previously installed detectors
• Local sounder
• Low current draw
• Alarm relay, Form C
• Trouble relay, Form A
• Dual LED’s
• Test/Hush button
• SEMS wiring terminals
• Mount to single gang electrical box or surface mount to wall or ceiling
• Optional drywall anchors included
FIGURE 1. ALARM LOCATION DIAGRAM:
BEDROOM
TO
BEDROOM BEDROOM
LIVING ROOM
BASEMENT
BR
KITCHEN
CLOSED DOOR
CARBON MONOXIDE ALARM LOCATION FOR MULTI-LEVEL RESIDENCE
GARAGE
S0295-00
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6583
www.systemsensor.com
Physical Specifications
Operating Temperature Range: 0° to 40°C (32° to 104°F) Operating Humidity Range: 22 – 90% %RH Diameter: 6.0˝ Height: 1.25˝ Weight: 7 oz Wire Gauge Acceptance: 14-22 AWG
TABLE 1. DETECTOR OPERATION MODES:
OPERATION
MODE
Normal
(standby)
Alarm OFF
Alarm Test OFF
GREEN
LED
Blink 1
per minute
RED LED
SOUNDER
OFF OFF
Temp 4*
pattern
Temp 4
pattern
Temp 4*
pattern
Temp 4
pattern
Temp 4
RealTest
Mode
Blink 1
per second
OFF
pattern
(after CO is
sprayed)
Alarm Test: Will send alarm signal to panel.
Hush feature/Alarm Silence: If required, the audible alarm can be silenced
for 5 minutes by pushing the button marked “Test/Hush”. The red alarm light will continue to flash in temp-4 pattern. If carbon monoxide is still present after the 5 minute hush period, the audible alarm will sound. The hush facility will not operate at levels above 350 ppm (parts per million) carbon monoxide.
RealTest Alarm Silence: Alarm will automatically silence after about 20 sec­onds of alarm from spraying canned CO into the detector. Alarm Reset: Alarm automatically resets after CO has cleared from the sensor.
Trouble feature: When the sensor supervision is in a trouble condition (such as a sensor that has been tampered with), the detector will send a trouble sig­nal to the panel. The detector must then be replaced. There is no local audible signal when detector is in trouble.
End of Life Timer feature: When the detector has reached the end of its life, the trouble contact will open. This indicates that the CO sensor inside the de­tector has passed the end of its life and must be replaced. This detector’s lifes­pan is approximately six years from the date of manufacture. There is no local audible signal when detector is in trouble. Periodically check the “Replace by” sticker located under the detector cover. The detector must be replaced by this date. Refer to Detector Replacement on page 3.
Per UL 2075, it is mandatory that a trouble signal be sent to the panel upon CO cell trouble or cell end of life. Refer to Figure 4 for wiring of the trouble relay.
SS-500-000 1 I56-3111-006
INSTALLATION GUIDELINES
Ceiling: Detector should be at least 12 inches from any wall.
Wall: Detector should be at least as high as a light switch, and at least six inches from the ceiling.
• Do not install in any environment that does not comply with the detec­tor’s environmental specifications
• Install in accordance with NFPA 720–the Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment
• As of 2009, NFPA 720 defines standards for both commercial and resi­dential installations of CO detectors. If the installation can be interpreted as a commercial application, consult the section of NFPA 720 that out­lines commercial applications.
• For example, Chapter 5.5.5.3.1 states that carbon monoxide detectors shall be installed in accordance with manufacturers published instruc­tions in the following locations:
(1) On the ceiling in the same room as permanently installed fuel
burning appliances
(2) Centrally located on every habitable level and in every HVAC zone
of the building
• If the installation can be interpreted as residential, consult the section of NFPA 720 that outlines residential applications.
• For example, chapter 9.4.1.1 states that carbon monoxide alarms or detectors shall be installed as follows:
(1) Outside each separate dwelling unit sleeping area in the immedi-
ate vicinity of the bedrooms
(2) On every level of a dwelling unit, including basements
(3) Other locations where required by applicable laws, codes or standards
MOUNTING
The CO1224T/CO1224TR can be ceiling-mounted or wall-mounted:
1. To a single gang box.
2. Direct mount to ceiling or to wall using drywall fasteners.
3. Mounted with optional replacement plate model CO-PLATE*.
FIGURE 2. MOUNTING OF DETECTOR:
CO1224T CO1224TR
INSTALLATION WIRING INSTALLATION GUIDELINES
All wiring must be installed in compliance with the NFPA 70, National Electrical Code, applicable state and local codes, and any special requirements of the local Authority Having Jurisdiction (AHJ).
Proper wire gauges should be used. The conductors used to connect carbon monoxide detectors to the alarm control panel and accessory devices should be color-coded to reduce the likelihood of wiring errors. Improper connections can prevent a system from responding properly in the event of a CO.
The screw terminals in the mounting base will accept 14-22 gauge wire. Wire connections are made by stripping approximately 1⁄4
˝ of insulation from the end of the feed wire, inserting it into the proper base terminal, and tightening the screw to secure the wire in place. Do not put wires more than 2 gauge apart under the same clamping plate.
WARNING: This product does not have a local audible trouble signal, and may fail without supervision if trouble loop remains unconnected. WARNING: Gas detectors on a zone that is bypassed may not signal a trouble condition. Do not bypass zones used for gas detectors.
Wiring diagrams located on page 4, Figure 4.
WARNING
Remove power from alarm control unit or initiating device circuits before in­stalling detectors.
1. Using a small, flat head screw driver, push in the small tab located on the underside of the detector. Once the snap is loosened, lift the bottom end of the cover up and unhinge the top to remove the cover.
2. Wire the detector base screw terminals per Figure 5.
3. Screw the base of the detector onto a single gang electrical box, or to the
surface of the wall or ceiling. Use the hardware included in the packaging.
4. If mounting with the System Sensor replacement plate model CO-PLATE*:
* Hold replacement plate over desired mounting area. * Use hook feature to hold CO1224T onto the replacement plate. * Mount detector and plate together using hardware provided with
the CO1224T.
5. Hinge the top portion of the cover onto the base; with the cover at a 45
degree angle, fit the hinges into the slots of the base.
6. Push the unhinged bottom portion of the cover down until it snaps into place.
7. After all detectors have been installed, apply power to the alarm control unit.
8. Test each detector as described in Testing.
9. Notify the proper authorities that the system is in operation.
CAUTION
Airborne dust particles can enter the detector. System Sensor recommends the installation of detectors before beginning construction or any other dust producing activity. Carbon monoxide detectors are not to be used with detec­tor guards unless the combination has been evaluated and found suitable for that purpose.
S0296-01
FIGURE 3: MOUNTING OF CO1224T DETECTOR TO CO-PLATE*
CO DETECTOR REPLACEMENT PLATE
MOUNT DETECTOR TO
CENTER OF PLATE
S0320-00
TESTING
Detector must be tested after installation.
NOTE: Before testing, notify the proper authorities to avoid any nuisance alarms. Ensure proper wiring and power is applied. After power up, allow 80 seconds for the detector to stabilize before testing.
Test the CO1224T/CO1224TR detector as follows:
1. A test button is located on the detector housing (See Figure 4).
2. Use the tip of your finger to press and hold the test button.
3. If the sounder beeps and the LED’s light up after 1-4 seconds, the detec-
tor is operational.
If a detector fails the above test method, its wiring should be checked. If the detector still fails after rewiring, it should be replaced.
S0319-00
*NOTE: The CO-PLATE has not been evaluated or approved by a NRTL.
SS-500-000 2 I56-3111-006
Loading...
+ 2 hidden pages