System Sensor CO1224A Installation And Maintenance Instructions Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-3247-006
CO1224A Carbon Monoxide Alarm
Specications
Electrical Specifications
System Voltage Nominal: 12/24 VDC Min: 10 VDC Max: 33 VDC Avg. Standby Current: 20 mA Max Alarm Current: 40 mA (75 mA test) Alarm Contact Ratings: 30 VDC @ 0.5 A Trouble Contact Ratings: 30 VDC @ 0.5 A Audible Signal (temp 4 tone): 85 dBA min. in alarm (at 10ft) Max. Start-up Capacitance: 20 uF
NOTICE: This manual shall be left with the owner/user of this equipment.
WARNING: This product is intended for use in ordinary indoor locations of dwelling units, including homes, residential buildings, hotels, schools, dormitories, and day care centers. It is not intended for use in industrial factories or commercial parking garages.
General Description
• Listed to CSA 6.19-01
• Six-wire, system monitored or stand-alone operation
• Local sounder
• Low current draw
• Alarm relay, Form C
• Trouble relay, Form A
• Dual LED’s
• Test/Hush button
• SEMS wiring terminals
• Mount to single gang electrical box or surface mount to wall or ceiling
• Optional drywall anchors included
Figure 1. Alarm Location Diagram:
BEDROOM
TO
BEDROOM BEDROOM
LIVING ROOM
BASEMENT
BR
KITCHEN
CLOSED DOOR
GARAGE
6581 Kitimat Rd., Unit #6, Mississauga, Ontario, L5N 3T5
1-800-SENSOR2, FAX: 905-812-0771
www.systemsensor.ca
Physical Specifications
Operating Temperature Range: 0° to 40°C (32° to 104°F) Operating Humidity Range: 22 – 90% %RH Length: 5.1˝ Width: 3.3˝ Height: 1.3˝ Weight: 7 oz Wire Gauge Acceptance: 14-22 AWG
Table 1. Operation Modes:
OPERATION
MODE
Normal
(standby)
Alarm OFF Temp 4* pattern Temp 4* pattern
Alarm Test OFF Temp 4 pattern Temp 4 pattern
RealTest Mode
CO End of Life OFF OFF
*Temp 4 pattern is repeated pattern of four short indications followed by a five second pause.
When the unit has been in alarm for 30 minutes the alarm signal will be given once every minute.
If ambient conditions return to normal, the unit will self-restore out of alarm and into Normal (standby) mode.
Hush feature: If required, the audible alarm can be silenced for 5 minutes by pushing the button marked “Test/Hush”. The red alarm light will continue to flash in temp-4 pattern. If carbon monoxide is still present after the 5 minute hush period, the audible alarm will sound. The hush facility will not operate at levels above 350 ppm (parts per million) carbon monoxide.
Trouble feature: When the sensor supervision is in a trouble condition (such as a sensor that has been tampered with), the alarm will sound a trouble signal every 30-60 seconds and the trouble contact will open . The alarm must then be replaced.
End of Life Timer feature: When the alarm has reached the end of its life, the trouble signal will sound every 30-60 seconds and the trouble contact will open. This indicates that the CO sensor inside the alarm has passed the end of its life and must be replaced. This alarm’s lifespan is approximately ten years from the date of manufacture. Refer to Alarm Replacement on page 3.
Refer to Figure 4 for wiring of the alarm and trouble relays.
GREEN
LED
Blink 1 per
minute
Blink 1 per
second (waiting
for gas entry)
RED LED
OFF OFF
OFF (Red after CO is sprayed)
SOUNDER
Temp 4 pattern
(after CO is
sprayed)
Chirp every
30-60 seconds
CARBON MONOXIDE ALARM LOCATION FOR MULTI-LEVEL RESIDENCE
1 I56-3247-006 10-28
S0295-00
Installation Guidelines
In a wall location, the alarm should be at least as high as a light switch, and at least six inches from the ceiling. In a ceiling location, the alarm should be at least 12 inches from any wall.
Where to install, ideally:
• Within 10 feet of all sleeping areas
• Inside the bedroom if it contains a fuel burning appliance
• On every floor of the building
• Ideally, install in any room that contains a fuel burning appliance
• If the appliance in the room is not normally used, such as the boiler room, the alarm should be placed just outside the room so the alarm can be heard more easily
Where NOT to install, ideally:
• Alarms operate best if not installed within 10 feet of any cooking appliance
• Directly above a sink, cooker, stove or oven
• Next to a door or window that would be affected by drafts i.e. extractor fan or air vent
• Outside
• Do not install in any environment that does not comply with the alarm’s environmental specifications
• In or below a cupboard
• Where air flow would be obstructed by curtains or furniture
• Where dirt or dust could collect and block the sensor
• Where it could be knocked, damaged, or inadvertently removed
Mounting
The CO1224A can be wall- or ceiling-mounted:
1. To a single gang box, or
2. Direct mount to wall or to ceiling using drywall fasteners.
in place. Do not put wires more than 2 gauge apart under the same clamping plate.
WARNING: Gas detectors on a zone that is bypassed may not signal a trouble condition. Do not bypass zones used for gas detectors.
Wiring diagrams locatsed on page 4, Figure 4.
Installation
WARNING
Remove power from alarm control unit or initiating device circuits before installing detectors.
1. Using a small, flat head screw driver, push in the small tab located on the underside of the alarm. Once the snap is loosened, lift the bottom end of the cover up and unhinge the top to remove the cover.
2. Wire the alarm base screw terminals per Figure 4.
3. Screw the base of the alarm onto a single gang electrical box, or to the surface of the wall or ceiling. Use the hardware included in the packaging.
4. Hinge the top portion of the cover onto the base; with the cover at a 45 degree angle, fit the hinges into the slots of the base.
5. Push the unhinged bottom portion of the cover down until it snaps into place.
6. After all alarms have been installed, apply power to the alarm control unit.
7. Test each alarm as described in Testing.
8. Notify the proper authorities that the system is in operation.
CAUTION
Airborne dust particles can enter the alarm. System Sensor recommends the removal of alarms before beginning construction or any other dust producing activity.
Figure 2. Mounting of Alarm:
S0296-00
S0301-00
Wiring Installation Guidelines
All wiring must be installed in compliance with the Canadian Electrical Code, applicable local codes, and any special requirements of the local Authority Having Jurisdiction (AHJ).
Proper wire gauges should be used. The conductors used to connect carbon monoxide alarms to the alarm control panel and accessory devices should be color-coded to reduce the likelihood of wiring errors. Improper connections can prevent a system from responding properly in the event of a CO.
The screw terminals in the mounting base will accept 14-22 gauge wire. Wire connections are made by stripping approximately of insulation from the end of the feed wire, inserting it into the proper base terminal, and tightening the screw to secure the wire
1
/4˝
Carbon monoxide alarms are not to be used with detector guards unless the combination has been evaluated and found suitable for that purpose.
Testing
Alarm must be tested after installation.
NOTE: Before testing, notify the proper authorities that maintenance is being performed and the system will be temporarily out of service. Disable the zone or system undergoing maintenance to prevent any unwanted alarms.
Ensure proper wiring and power is applied. After power up, allow 80 seconds for the alarm to stabilize before testing.
Test the CO1224A alarm as follows:
1. A test button is located on the detector housing (See Figure
3).
2. Use the tip of your finger to press and hold the test button for 1-4 seconds.
3. If the sounder beeps twice in the Temporal 4 pattern and the LEDs light up, the detector is operational.
4. The detector now enters Realtest speed up test mode indicated by a quickly blinking green LED. See Functional Gas Test section for instructions on testing with canned CO.
Note: The alarm contact has a time delay of approximately
10 second before operation. To test for the alarm contact operation, the test button must be held down for at least 10 seconds.
2 I56-3247-006 10-28
Figure 3. Test Button Location and Operation:
T
GAS ENTRY PORTS
EST/HUSH
BUTTON
If an alarm fails the above test method, its wiring should be checked. If the alarm still fails after rewiring, it should be replaced.
Functional Gas Test
NOTE: Check with local codes and the AHJ to determine whether or not a functional gas test is necessary for an installation.
Solo C6 brand canned CO testing agent may be used to verify the alarm’s ability to sense CO by utilizing the functional speed-up test feature of the CO1224A as follows:
1. Press the test button as described in Testing above.
2. Once the alarm has entered the speed-up test mode, indicated by a quickly flashing green LED, spray a small mount of CO agent within 1/4" of the alarm’s gas entry ports (see Figure 3). The unit will go into alarm if gas entry is successful.
3. The alarm will automatically exit the speed-up test mode 20 seconds after entering speed-up test mode.
Testing the alarm will activate the alarm relay and send a signal to the panel.
CAUTION: This carbon monoxide alarm is designed for indoor use
only. Do not expose to rain or moisture. Do not knock or drop the alarm. Do not open or tamper with the alarm as this could cause malfunction. The alarm will not protect against the risk of carbon monoxide poisoning if not properly wired. The alarm will only indicate the presence of carbon monoxide gas at the sensor. Carbon monoxide gas may be present in other areas.
This carbon monoxide alarm is NOT:
• Designed to detect smoke, fire or any gas other than carbon
monoxide
• To be seen as a substitute for the proper servicing of fuel-
burning appliances or the sweeping of chimneys.
• To be used on an intermittent basis, or as a portable alarm
for the spillage of combustion products from fuel-burning appliances or chimneys.
Carbon monoxide gas is a highly poisonous gas which is released when fuels are burnt. It is invisible, has no smell and is therefore impossible to detect with the human senses. Under normal conditions in a room where fuel burning appliances are well maintained and correctly ventilated, the amount of carbon monoxide released into the room by appliances should not be dangerous.
Symptoms of carbon monoxide poisoning: Carbon monoxide bonds to the hemoglobin in the blood and reduces the amount of oxygen being circulated in the body. The following symptoms are related to carbon monoxide poisoning and should be discussed with all members of the household:
Mild exposure: Slight headache, nausea, vomiting, fatigue
(often described as “flu-like” symptoms).
3 I56-3247-006 10-28
S0298-01E
Medium exposure: Sever throbbing headache, drowsiness, confusion, fast heart rate.
Extreme exposure: Unconsciousness, convulsions, cardio respiratory failure, death.
Concentration (ppm CO) Symptoms
200 Mild headache after 2-3 hours
of exposure
400 Headache and nausea after
1-2 hours of exposure
800 headache, nausea, and diz-
ziness after 45 minutes of
exposure;
collapse and unconsciousness
after 2 hours of exposure
Many causes of reported carbon monoxide poisoning indicate that while victims are aware that they are not well, they become so disoriented that they are unable to save themselves by either exiting the building or calling for assistance. Also young children and pets may be the first to be affected.
Per CSA 6.19-01 the CO1224A has been tested to the following sensitivity limits.
Parts Per Million Detector response time, min.
30 ±3ppm No alarm within 30 days
70 ±5ppm 60-240
150 ±5ppm 10-50
400 ±10ppm 4-15
What to do if the carbon monoxide alarm goes into alarm:
Immediately move to a spot where fresh air is available, preferably outdoors. Find a phone in an area where the air is safe and call your security service provider. Tell your provider the alarm status, and that you require professional assistance in ridding your home of the carbon monoxide.
IMPORTANT: This alarm should be tested and maintained regularly following National Fire Protection Association (NFPA) 720 requirements.
Maintenance
Occasionally clean the outside casing with a cloth. Ensure that the holes on the front of the alarm are not blocked with dirt and dust.
Do not paint, and do not use cleaning agents, bleach, or polish on the alarm.
Alarm Replacement
This alarm is manufactured with a long-life carbon monoxide sensor. Over time the sensor will lose sensitivity, and will need to be replaced with a new System Sensor carbon monoxide alarm. This alarm’s lifespan is approximately ten years from the date of manufacture.
Periodically check the alarm’s replacement date. Remove the alarm cover and refer to the sticker placed on the inside of the alarm. The sticker will indicate the date that the alarm should be replaced.
This alarm is also equipped with a feature that will sound a trouble signal every 30-60 seconds and open the trouble relay once it has reached the end of its useful life. If this occurs, it is time to replace the alarm.
NOTE: Before replacing the alarm, notify the proper authorities that maintenance is being performed and the system will be temporarily out of service. Disable the zone or system undergoing maintenance to prevent any unwanted alarms. Dispose of alarm in accordance with any local regulations.
Figure 4. Wiring Diagram:
SINGLE UNIT, SINGLE ZONE, 4 CONDUCTOR CABLE
MULTIPLE UNIT, SINGLE ZONE, 6 CONDUCTOR CABLE
NON-RESETTABLE PWR
CO ZONE
UL LISTED PANEL
+
CLOSED WITH POWER APPLIED AND NO FAULT
+ −
TT
C
ALARM INITIATION CONTACTS
NO
DETECTED
EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER
S0313-00
CAUTION
It should be noted the installation, operation, testing and main­tenance of the CO1224A is different than System Sensor conven­tional 4-wire smoke detectors, such as the i3 Series. Below are specific installation requirements for the CO1224A:
* Connect to a non-resettable power supply * Connect to a non-fire zone: Per NFPA 720 section 5.3.7.2 the CO1224A
shall not be connected to a zone that signals a fire condition
* Per NFPA 720 section 5.3.7, do not connect the CO1224A on a zone
with other fire or intrusion initiating devices - i.e. do not connect on the same zone as smoke detectors
* Wiring of the trouble relay will send a trouble signal to the control
panel upon an open circuit, a ground fault, sensor removal or sensor
end of life * If wiring one CO1224A per zone: Use 4 conductors * If wiring multiple CO1224A alarms per zone: Use 4 conductors from
panel to first CO1224A, then use 6 conductors from the second
CO1224A to other alarms on the zone
NON-RESETTABLE PWR
CO ZONE
UL LISTED PANEL
+
+ −
TT TT
C
ALARM INITIATION CONTACTS
NO
FIRST CO1224
DETECTOR
IN LOOP
Input powered (12 or 24 VDC) from ULC Listed Fire/Burg Control Panel (Class 2).
Please refer to insert for the limitations of Carbon Monoxide Alarms
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to pro­vide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: – Reorient or relocate the receiving antenna. – Increase the separation between the equipment and receiver. – Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. – Consult the dealer or an experienced radio/TV technician for help. This Class B digital apparatus complies with Canadian ICES-003.
System Sensor warrants its enclosed product to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for the enclosed product. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the replacement of any part of the product which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defec­tive units postage prepaid to: System Sensor, Returns Department, RA
System Sensor® is a registered trademark of Honeywell International, Inc.
4 I56-3247-006 ©2016 System Sensor. 10-28
SUPERVISORY TROUBLE CONTACTS
+ −
C
NO
LAST CO1224
DETECTOR
FCC Statement
Three-Year Limited Warranty
IN LOOP
ALARM INITIATION CONTACTS
CLOSED WITH POWER APPLIED AND NO FAULT DETECTED
EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER
POSITIVE
NEGATIVE
TROUBLE
TROUBLE
NORMALLY CLOSED
COMMON
NORMALLY OPEN
S0314-00
#__________, 6581 Kitimat Road, Unit 6, Mississauga, Ontario L5N-3T5. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to replace units which are found to be defective because of damage, unreasonable use, modi­fications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limita­tion of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
POWER
}
TROUBLE RELAY
}
ALARM RELAY
S0300-01
Loading...