System Sensor CO1224A Installation And Maintenance Instructions Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-3247-006
CO1224A Carbon Monoxide Alarm
Specications
Electrical Specifications
System Voltage Nominal: 12/24 VDC Min: 10 VDC Max: 33 VDC Avg. Standby Current: 20 mA Max Alarm Current: 40 mA (75 mA test) Alarm Contact Ratings: 30 VDC @ 0.5 A Trouble Contact Ratings: 30 VDC @ 0.5 A Audible Signal (temp 4 tone): 85 dBA min. in alarm (at 10ft) Max. Start-up Capacitance: 20 uF
NOTICE: This manual shall be left with the owner/user of this equipment.
WARNING: This product is intended for use in ordinary indoor locations of dwelling units, including homes, residential buildings, hotels, schools, dormitories, and day care centers. It is not intended for use in industrial factories or commercial parking garages.
General Description
• Listed to CSA 6.19-01
• Six-wire, system monitored or stand-alone operation
• Local sounder
• Low current draw
• Alarm relay, Form C
• Trouble relay, Form A
• Dual LED’s
• Test/Hush button
• SEMS wiring terminals
• Mount to single gang electrical box or surface mount to wall or ceiling
• Optional drywall anchors included
Figure 1. Alarm Location Diagram:
BEDROOM
TO
BEDROOM BEDROOM
LIVING ROOM
BASEMENT
BR
KITCHEN
CLOSED DOOR
GARAGE
6581 Kitimat Rd., Unit #6, Mississauga, Ontario, L5N 3T5
1-800-SENSOR2, FAX: 905-812-0771
www.systemsensor.ca
Physical Specifications
Operating Temperature Range: 0° to 40°C (32° to 104°F) Operating Humidity Range: 22 – 90% %RH Length: 5.1˝ Width: 3.3˝ Height: 1.3˝ Weight: 7 oz Wire Gauge Acceptance: 14-22 AWG
Table 1. Operation Modes:
OPERATION
MODE
Normal
(standby)
Alarm OFF Temp 4* pattern Temp 4* pattern
Alarm Test OFF Temp 4 pattern Temp 4 pattern
RealTest Mode
CO End of Life OFF OFF
*Temp 4 pattern is repeated pattern of four short indications followed by a five second pause.
When the unit has been in alarm for 30 minutes the alarm signal will be given once every minute.
If ambient conditions return to normal, the unit will self-restore out of alarm and into Normal (standby) mode.
Hush feature: If required, the audible alarm can be silenced for 5 minutes by pushing the button marked “Test/Hush”. The red alarm light will continue to flash in temp-4 pattern. If carbon monoxide is still present after the 5 minute hush period, the audible alarm will sound. The hush facility will not operate at levels above 350 ppm (parts per million) carbon monoxide.
Trouble feature: When the sensor supervision is in a trouble condition (such as a sensor that has been tampered with), the alarm will sound a trouble signal every 30-60 seconds and the trouble contact will open . The alarm must then be replaced.
End of Life Timer feature: When the alarm has reached the end of its life, the trouble signal will sound every 30-60 seconds and the trouble contact will open. This indicates that the CO sensor inside the alarm has passed the end of its life and must be replaced. This alarm’s lifespan is approximately ten years from the date of manufacture. Refer to Alarm Replacement on page 3.
Refer to Figure 4 for wiring of the alarm and trouble relays.
GREEN
LED
Blink 1 per
minute
Blink 1 per
second (waiting
for gas entry)
RED LED
OFF OFF
OFF (Red after CO is sprayed)
SOUNDER
Temp 4 pattern
(after CO is
sprayed)
Chirp every
30-60 seconds
CARBON MONOXIDE ALARM LOCATION FOR MULTI-LEVEL RESIDENCE
1 I56-3247-006 10-28
S0295-00
Installation Guidelines
In a wall location, the alarm should be at least as high as a light switch, and at least six inches from the ceiling. In a ceiling location, the alarm should be at least 12 inches from any wall.
Where to install, ideally:
• Within 10 feet of all sleeping areas
• Inside the bedroom if it contains a fuel burning appliance
• On every floor of the building
• Ideally, install in any room that contains a fuel burning appliance
• If the appliance in the room is not normally used, such as the boiler room, the alarm should be placed just outside the room so the alarm can be heard more easily
Where NOT to install, ideally:
• Alarms operate best if not installed within 10 feet of any cooking appliance
• Directly above a sink, cooker, stove or oven
• Next to a door or window that would be affected by drafts i.e. extractor fan or air vent
• Outside
• Do not install in any environment that does not comply with the alarm’s environmental specifications
• In or below a cupboard
• Where air flow would be obstructed by curtains or furniture
• Where dirt or dust could collect and block the sensor
• Where it could be knocked, damaged, or inadvertently removed
Mounting
The CO1224A can be wall- or ceiling-mounted:
1. To a single gang box, or
2. Direct mount to wall or to ceiling using drywall fasteners.
in place. Do not put wires more than 2 gauge apart under the same clamping plate.
WARNING: Gas detectors on a zone that is bypassed may not signal a trouble condition. Do not bypass zones used for gas detectors.
Wiring diagrams locatsed on page 4, Figure 4.
Installation
WARNING
Remove power from alarm control unit or initiating device circuits before installing detectors.
1. Using a small, flat head screw driver, push in the small tab located on the underside of the alarm. Once the snap is loosened, lift the bottom end of the cover up and unhinge the top to remove the cover.
2. Wire the alarm base screw terminals per Figure 4.
3. Screw the base of the alarm onto a single gang electrical box, or to the surface of the wall or ceiling. Use the hardware included in the packaging.
4. Hinge the top portion of the cover onto the base; with the cover at a 45 degree angle, fit the hinges into the slots of the base.
5. Push the unhinged bottom portion of the cover down until it snaps into place.
6. After all alarms have been installed, apply power to the alarm control unit.
7. Test each alarm as described in Testing.
8. Notify the proper authorities that the system is in operation.
CAUTION
Airborne dust particles can enter the alarm. System Sensor recommends the removal of alarms before beginning construction or any other dust producing activity.
Figure 2. Mounting of Alarm:
S0296-00
S0301-00
Wiring Installation Guidelines
All wiring must be installed in compliance with the Canadian Electrical Code, applicable local codes, and any special requirements of the local Authority Having Jurisdiction (AHJ).
Proper wire gauges should be used. The conductors used to connect carbon monoxide alarms to the alarm control panel and accessory devices should be color-coded to reduce the likelihood of wiring errors. Improper connections can prevent a system from responding properly in the event of a CO.
The screw terminals in the mounting base will accept 14-22 gauge wire. Wire connections are made by stripping approximately of insulation from the end of the feed wire, inserting it into the proper base terminal, and tightening the screw to secure the wire
1
/4˝
Carbon monoxide alarms are not to be used with detector guards unless the combination has been evaluated and found suitable for that purpose.
Testing
Alarm must be tested after installation.
NOTE: Before testing, notify the proper authorities that maintenance is being performed and the system will be temporarily out of service. Disable the zone or system undergoing maintenance to prevent any unwanted alarms.
Ensure proper wiring and power is applied. After power up, allow 80 seconds for the alarm to stabilize before testing.
Test the CO1224A alarm as follows:
1. A test button is located on the detector housing (See Figure
3).
2. Use the tip of your finger to press and hold the test button for 1-4 seconds.
3. If the sounder beeps twice in the Temporal 4 pattern and the LEDs light up, the detector is operational.
4. The detector now enters Realtest speed up test mode indicated by a quickly blinking green LED. See Functional Gas Test section for instructions on testing with canned CO.
Note: The alarm contact has a time delay of approximately
10 second before operation. To test for the alarm contact operation, the test button must be held down for at least 10 seconds.
2 I56-3247-006 10-28
Loading...
+ 2 hidden pages