System Sensor CH24 User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
SpectrAlert Selectable Output CH24 Series Wall Chime/Strobes
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
for Fire Protective Signaling Systems
For use with the following models: CH24 and CH24W U.S. Patent Nos. 5,593,569; 5.914,665; 5,850,178; 5,598,139; 6,049,446; 6,127,935
Specifications: Chime
Mechanical Input Terminals: 12 to 18 AWG (3.31 to 0.82 mm2) Overall Dimensions: 6.9 × 5.0
Electrical
Voltage Input: DC or Full-Wave Rectified 8-33 volts Operating Temperature Range: 32° to 120°F (0° to 49°C)
Listings: UL S4011 Private Mode (Chime/Strobe), UL S5512 (Strobe)
Note for Strobes: Do not exceed 1) 16-33 Voltage range limit, 2) Maximum number of 70 strobe lights when connecting the MDL Sync module with a maximum line imped­ance of 4 Ohms per loop and 3) Maximum line impedance as required by the fire alarm control manufacturer.
NOTICE: This manual shall be left with the owner/user of this equipment.
General Description
The SpectrAlert CH24 series strobe can be installed in systems using 24-volt panels having DC or full-wave rectified (FWR) power supplies. The strobes can also be installed in applications requiring synchronization (MDL required) or applications that do not require synchronization (no module required). Please note that the chime section is not synchronizable with the MDL.
The SpectrAlert CH24 series chime/strobes are designed to meet the requirements of most agencies governing these devices, including: NFPA, ADA, The National Fire Alarm Code, UL, CSFM, MEA. Also, check with your local Authority Having Jurisdiction for other codes or standards that may apply.
Note: The SpectrAlert CH24 Series Chime/Strobe must be
powered from a non-coded power supply. This appli­ance is not intended for use with a coded power sup­ply.
Fire Alarm Considerations
Temporal and Non-Temporal Coded Signals:
The American National Standards Institute and the National Fire Alarm Code require that all horns used for building evacu­ation installed after July 1, 1996, must produce Temporal Coded Signals. Signals other than those used for evacuation purposes do not have to produce the Temporal Coded Signal.
Power Supply Considerations For Strobes
Panels typically supply DC filtered voltage or FWR (full-wave rectified) voltage. The system design engineer must calculate the number of units used in a zone based on the type of panel sup-
Specifications: Strobe
Voltage Range: Regulated 24 DC/FWR Operational Voltage Range: 16-33 Volts Synchronous Applications with MDL Module: 17-33 Volts
Flash Rate: 1 flash per second Selectable Light Outputs: All candelas are selectable via a manual slide switch. 15/75 is listed at 15 candela per UL 1971 but will provide 75 candela on axis (straight ahead). 15, 30, 75, or 110 are rated for that candela.
ply. Be certain the sum of all the device currents do not exceed the current capability of the panel. Calculations are based on using the device current found in Table 3 and must be the current specified for the type of panel power supply used.
Wire Sizes
The designer must be sure that the last device on the circuit has sufficient voltage to operate the device within its rated voltage. When calculating the voltage available to the last device, it is necessary to consider the voltage drop due to the resistance of the wire. The thicker the wire, the less the voltage drop. Generally, for purposes of determining the wire size necessary for the system, it is best to consider all of the devices as “lumped” on the end of the supply circuit (simulates “worst case”).
Typical wire size resistance:
18 AWG solid: Approximately 8 ohms/1,000 ft. 16 AWG solid: Approximately 5 ohms/1,000 ft. 14 AWG solid: Approximately 3 ohms/1,000 ft. 12 AWG solid: Approximately 2 ohms/1,000 ft.
Example: Assume you have 10 devices on a zone and each requires 50 mA average and 2000 Ft. of 14 AWG wiring (total length=outgoing + return). The voltage at the end of the loop is 0.050 amps per device × 10 devices × 3 ohms/1,000 ft. × 2000 ft =3 volts drop.
The same number of devices using 12 AWG wire will produce only 2 volts drop. The same devices using 18 AWG wire will produce 8 volts drop. Consult your panel manufacturer’s specifications, as well as SpectrAlert’s operating voltage range to determine accept­able voltage drop.
Note: If class “A” wiring is installed, the wire length may be up to 4 times the single wire length in this calculation.
D900-24-00 1 I56-0936-003R
Chime Selection
Repeating 1-Second Chime
Repeating 1/4-Second Chime
Temporal 3 Chime
Single Stroke Chime
Continuous 500Hz Electromechanical and 3kHz Electromechanical
Temporal 500Hz Electromechanical and 3kHz Electromechanical
Scale: 1 second
Chimes are factory set for high volume, 1.0K repeating 1 second chime. Tones may be selected by making the appropriate settings on the DIP Switch located on the printed circuit board. The set­tings required for the available tone options are as follows:
Table 1: SpectrAlert Chime Switch Settings
Switch 1=on 0=off
1 2 3 4 Hz Type
1 1 1 1 1.2k
Repeating 1-Second Chime1 0 1 1 1.0k 1 1 0 1 0.8k 1 0 0 1 1.2k
Repeating 1/4-Second Chime1 1 1 0 1.0k 1 0 1 0 0.8k 1 1 0 0 1.2k
Temporal 3 Chime1 0 0 0 1.0k 0 1 1 1 0.8k 0 0 1 1 1.2k
Single Stroke Chime0 1 0 1 1.0k 0 0 0 1 0.8k 0 1 1 0 3.0k Electromechanical Continuous 0 0 1 0 3.0k Electromechanical Temporal 3 0 1 0 0 0.5k Electromechanical Continuous 0 0 0 0 0.5k Electromechanical Temporal 3
Volume Switch
5 6
0 0 LOW 1 0 MED 1 1 HIGH
SpectrAlert Chime Tones
SpectrAlert Electronic Chime Current Draw*
8-33VDC: 10–61mA
*Average current draw varies with tones selected. Current ratings per System Sensor testing at 12VDC and 24VDC. Add current values when connecting in parallel.
Table 2: SpectrAlert Electronic Chime Sound Output Guide
Tone
1.2K Repeating 1-Second Chime 51 52 55 53 54 56 57 61 52 59 61 64
1.0K Repeating 1-Second Chime 48 50 54 51 52 54 54 57 60 57 60 62
0.8K Repeating 1-Second Chime 47 47 53 49 51 52 53 55 58 55 58 60
1.2K Repeating 1/4-Second Chime 53 54 58 55 57 59 59 61 64 61 63 66
1.0K Repeating 1/4-Second Chime 49 50 54 51 53 54 55 57 60 57 59 62
0.8K Repeating 1/4-Second Chime 48 50 53 50 52 53 54 56 59 56 58 61
1.2K Temporal 3 Chime 51 52 56 52 54 55 55 57 61 58 60 63
1.0K Temporal 3 Chime 48 49 54 49 51 51 53 55 58 55 57 60
0.8K Temporal 3 Chime 46 47 51 48 50 51 52 54 57 54 56 59
1.2K Single Stroke Chime 52 53 58 52 54 56 56 58 62 58 60 64
1.0K Single Stroke Chime 47 48 53 50 51 59 53 55 58 56 58 62
0.8K Single Stroke Chime 47 48 53 49 50 52 54 56 60 56 59 61
3.0K Continuous Electromechanical 56 57 61 59 60 67 65 68 70 68 70 74
3.0K Temporal Electromechanical 51 52 56 53 54 61 56 59 62 58 60 64
0.5K Continuous Electromechanical 48 49 53 51 52 56 54 57 60 56 55 61
0.5K Temporal Electromechanical 45 47 51 47 49 53 51 52 58 52 54 60
Low Med. High Low Med. High Low Med. High Low Med. High
NOTE: Factory default setting is 1.0K Repeating 1 Second Chime set at High volume.
Table 3: Strobe Current Draw Measurements
NOTE: All models were only tested at the 16-33 Volt-FWR/DC limits. This does not include the 80% low-end or 110% high-end voltage limits.
Model No. Candela Setting
CH24MC Chime/Strobe
15 84 59 15/75 74 69 30 93 90 75 158 160 110 208 209
8 Volts 12 Volts 24 Volts 33 Volts
FWR Operating
Current–Strobe
(mA RMS)
DC Operating
Current–Strobe
(mA RMS)
D900-24-00 2 I56-0936-003R
Loading...
+ 2 hidden pages