System Sensor CB500 User Manual

INSTALLATION INSTRUCTIONS
Cut here for modules whose Communication Lines attach to Terminals 0 and 1.
Cut here for modules whose Communication Lines attach to Terminals 1 and 2.
CB500 Wiring Barrier
I56-1483-00
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
The CB500 barrier is used to separate power limited and non­power limited wiring in a junction box. It is designed for multiple applications, and one plastic tab must be removed prior to instal­lation into a junction box.
Refer to the installation manual for the module being installed to determine which screw terminals are used to attach the Com­munication Lines. Then, use diagonal cutters to cut off the ap­propriate tab on the barrier, as shown in the diagram below.
Prior to installing the barrier into the junction box, peel off the label which says SIGNALING LOOP CIRCUIT TERMINALS ARE POWER LIMITED. OTHERS ARE NOT. Affix this label over that portion of the label on the back of the module which says ALL
CIRCUITS ARE POWER LIMITED.
Additional instructions on the installation of this barrier can be found in the installation manual for the module.
C0686-00
D500-43-00 I56-1483-00
Loading...