INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-2813-003R
B501BH-2
Sounder Base
Specifications
Base Diameter: 6.0 inches (15.2 cm)
Base Height (less sensor): 2.3 inches (5.9 cm)
Weight: 0.32 lb. (145 gm)
Operating Temperature Range: 32° to 120°F (0° to 49°C)
Operating Humidity Range: 10% to 93% Relative Humidity
Electrical Ratings
External Supply Voltage: 17 to 32 VDC
Standby Current: 1.0 mA maximum
Alarm Current: 15 mA maximum
Maximum Ripple Voltage: 10% of supply voltage
Start-up Capacitance: 200 µF
Communication/Initiating Loop Supply
Current Draw from Remote Output
of Sensor to turn on Horn: 600 µA maximum
Sound Output: Greater than 90 dBA measured in anechoic room at 10 feet, 24 volts. 85 dBA
minimum measured in UL reverberant room.
Sounder Delay Time: 0.75 to 5.7 sec
Before Installing
Please read the System Smoke Detector Application Guide,
which provides detailed information on sensor spacing. placement, zoning, wiring. and special applications. Copies of this
manual are available from System Sensor. NFPA 72 and NEMA
guidelines should be observed.
NOTICE: This manual should be left with the owner/user of
this equipment.
IMPORTANT: The detector used with this base must be tested
and maintained regularly following NFPA 72 requirements.
The detector should be cleaned at least once a year.
General Description
The B501BH-2 sounder base is used with System Sensor 200
Series sensor heads. Refer to the appropriate manual for more
information on sensors.
The sounder base is intended for use with intelligent systems.
Refer to the panel manual for the maximum allowable number of units per loop. The sounder base requires an external
24VDC supply with reverse polarity capability or a relay module configured to reverse the power as in Figure 5. The connections for the external supply (terminals 1 and 2) and the
communication loop (terminals 3 and 4) are isolated to prevent electrical interaction between them.
A loop of horns can be made to sound by reversing the polarity of the external supply when configured as in Figure 4 and
5. When configured as in Figure 5, a loop of horns can also be
made to sound by turning on the Intelligent Relay Module.
NOTE: When not used as a supplementary evacuation system
the external 24 VDC supply shall be treated as a component of
the main power supply system and shall fall under the requirements of the main power supply system per NFPA 72.
B501BH-2 Terminals
No. Function
1 External Supply Positive (+)
2 External Supply Negative (–)
3 Negative (–) Comm. Line In and Out
4 Positive (+) Comm. Line In and Out
5 Sounder Base Interconnect
Terminals 3 and 4 are used for the communication circuit.
Mounting
Mount the B501BH-2 directly to an electrical box, using the
mounting kit, supplied (see Figure 2).
The sounder base is 1.1-inches deep. Electrical boxes must be
4-inches square by at least 11⁄2 inches deep - 21⁄8 inches is recommended.
NOTE: A maximum space of 1⁄8 inch from the outside edge of
the electrical box to the inside edge of the drywall or ceiling
tile is allowable.
Wiring Guidelines
All wiring must be installed in compliance with the National
Electrical Code and the local codes having jurisdiction and
must not be of such length or wire size which would cause
the base to operate outside of its published specifications. The
conductors used to connect smoke sensors to control panels
and accessory devices should be color coded to reduce the
likelihood of wiring errors. Improper connections can prevent
a system from responding properly in the event of a fire.
For signal wiring (the wiring between interconnected sensors
or modules), it is recommended that the wire be no smaller
than 18 gauge (1.0 square mm). Wire sizes up to 12 gauge (2.5
square mm) may be used with the base. For best system performance, the power (+ and –) wires and the communication
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
D250-04-00 1 I56-2813-003R
circuit wires should be twisted pair or shielded cable installed
MOUNT B501BH-2
TO ELECTRICAL BOX
4 INCH SQUARE BOX
in separate grounded conduit to protect the communication
loop from electrical interference.
Make wire connections by stripping about 3⁄8˝ of insulation
from the end of the wire. Then, slide the bare end of the wire
under the clamping plate, and tighten the clamping plate
screw. Do NOT loop the wire under the clamping plate (See
Figure 3).
The zone wiring of the sensor base should be checked before
the sensor heads are installed. Check the wiring for continuity
and polarity in the base.
See the individual sensor manual for the maximum sensor installation temperature.
Wiring Instructions
NOTE: External supply shown in normal standby configuration in Figure 4 and 5.
The wiring diagram for a typical 2-wire intelligent system is
shown in Figure 4 and 5. (the monitor module is supervising
the external supply).
Testing
Sensors and bases must be tested after installation and as
an integral part of periodic maintenance. Test the B501BH-2
as follows:
NOTE: Before testing, notify the proper authorities that the
smoke sensor system is undergoing maintenance and, therefore, will be temporarily out of service. Disable the system undergoing maintenance to prevent unwanted alarms.
1. If configured as in Figure 4 and 5, reverse the polarity
of the external 24VDC supply. If configured as in Fig-
ure 5, turn on the Intelligent Relay Module. All B501BH2 bases on the loop should sound in approximately 0.75
to 5.7 seconds.
2. Latch the sensor LED on from the control panel. That
unit’s B501BH-2 should sound in approximately 0.75 to
5.7 seconds.
NOTES:
1. There is approximately a 0.75 to 5.7 second delay built
into the B501BH-2 before sounding. This delay is present
whether the control signal comes from the sensor or from
the external power supply polarity being reversed.
2. During automatic testing cycles, the horn may sound if
the associated sensor is left in the test mode with LEDs
latched on for more than 0.75 seconds. Therefore, it is
necessary to complete testing of each sensor within this
0.75-second limit to prevent the horn from sounding.
Figure 1. Terminal layout:
C0736-00
Figure 2. Mounting:
C0889-00
Figure 3:
D250-04-00 2 I56-2813-003R
C0737-00